9-CHANNEL LED CONTROLLER

The module allows connecting RGB and monochrome LED strips.

Features

  • Supported load types:
    • 3x RGB
    • 2x RGBW + 1 monochrome channels
    • 1x RGBWW + 1x RGB or 4x monochrome channels

Downloads

DWG file

Overview

Module dimensions

Internal layout

Connection of LED lamps and LED RGB.

Example of connection RGBWW/RGBW LED

Example of connection RGB LED with Amp

Module parameters

Parameter name Value
Output channels qty 9
Input voltage 0 … 25V DC
Current type DC
Adjustment type PWM
Max current (per channel) 3A (36W at 12V)
Power supply 11.5 … 27.5 V DC from CAN
Max current(24V) 55 mA
Bus type CAN (4-wire)
Equipment installation type DIN-rail (EN 60715)
Case material ABS
Protection IP40
Temperature range -10 … +40 °C
Size 4U, 69x110x58 mm
Weight 85 g

Indication of module operation.

Indicator Status Description
Power Power
Power not available
Activity Transferring data
No data transferring
Error No errors
Overheating

(blinking)

The device blinks once every two seconds. The data has not been transferred via the CAN bus for at least 5 minutes.

Module installation and connection procedure

  1. Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
  2. Connect the CAN connector.
  3. Connect the channels.
  4. Configure the module using LT setup.
  5. Apply power to the load.
  6. Check all equipment for proper operation.

Module shut-off and deinstallation procedure

  1. Disconnect the power from the load.
  2. Disconnect the channels.
  3. Disconnect the CAN connector.
  4. Remove the module from the DIN rail, releasing the latch at the bottom of the module base.

HW Settings

Name Type, range SUBID Default Description
dm char[9] 98 'RGBRGBRGB' Each char is responsible for the type of a particular channel, RGB takes 3 channels

  • 'RGB' – Use like RGB lamp
    • 'L' – LED Function, dimmable LED lamps
    • 'G' – Use like halogen dimer-lamp
    • 'Y' – Linear Function of dimming
    • 'B' – Blinds
    • 'F' – Fancoil
    • 'S' – Lamp
    • 'M' – Inverse lamp
    • 'V' – Valve
    • 'W' – Inverse valve
    • 'K' – Lock
    • 'N' – Inverse lock
    • 'H' – Valve heating
    • 'J' – Inverse valve heating
    • '-' – Channel disabled
    • Example: dm='LLLRGBLLL'

    def integer 0-250 1-5 100 The default brightness level in case of a power reset (1..250). Example: def=250
    min integer 0-100 1-5 0 Minimum dimming level, example: min=10
    max integer 0-100 1-5 100 Maximum dimming level, example max=95
    start integer 0-100 1-5 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
    force integer 0-100 1-5 10 Time duration of the starting value (measured in milliseconds). Example: force=20
    runtime integer 0-60000 1-9 5 Runtime is the speed of changing the brightness(measured in miliseconds for dimmer and in seconds for RGB). Example: runtime=5000

    Example:

    <item addr="555:1" auto-period="600" cfgid="66" name="Dimmer" type="dimer-lamp" uniq_id="4054"/>
    <item addr="555:2" auto-period="600" cfgid="66" name="Dimmer" type="dimer-lamp" uniq_id="4055"/>
    <item addr="555:3" auto-period="600" cfgid="66" name="Dimmer" type="dimer-lamp" uniq_id="4056"/>
    <item addr="555:4" auto-period="600" cfgid="66" name="RGB" type="rgb-lamp" uniq_id="4053"/>
    <item addr="555:7" auto-period="600" cfgid="66" name="Dimmer" type="dimer-lamp" uniq_id="4057"/>
    <item addr="555:8" auto-period="600" cfgid="66" name="Dimmer" type="dimer-lamp" uniq_id="4058"/>
    <item addr="555:9" auto-period="600" cfgid="66" name="Dimmer" type="dimer-lamp" uniq_id="4059"/>
    <item addr="555:97" cfgid="66" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4010"/>
    <item addr="555:98" cfgid="66" hw="dm='DDDRGBDDD'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4011"/>