3-CHANNEL MODULE FOR BLINDS MOTOR CONTROL

This module provides control of curtains, projector screens, valves or other electrical motors.

Features

  • Supported load types:
    • curtains with force/low-current control
    • 1 / 2 pole valves
  • Overcurrent protection

Overview

Connection of curtain/jalousie/shutter actuators

Module dimensions

Internal layout

Module parameters

Parameter name Value
Output channels qty 3
Input voltage 0-250 V AC/DC
Current type AC/DC
Max load per channel 5 A
Power supply 11.5 … 27.5 V DC from CAN
Max current(24V) 55 mA
Connection type CAN
Permissible section of power supply cable to connect in socket 0.5 … 2.5mm2
Bus type CAN (4-wire)
Equipment installation type DIN-rail (EN 60715)
Case material ABS
Protection IP40
Temperature range -10 … +50 °C
Size 4U, 69x110x58 mm
Weight 95g

Indication of module operation.

Bootloader

Indicator Status Description
Device in bootloader
Waiting for bootloader command
Flashing firmware

Firmware mode

Indicator Status Description
Identification
Operational mode

Error
Lost connection to server
Overheat
Overload

Module installation and connection procedure

  1. Connect the outputs.
  2. Connect the Can connector.
  3. Configure the module using LT setup.
  4. Apply power to the load
  5. Check all equipment for proper operation.

Module shut-off and deinstallation procedure

  1. Disconnect the power from the load
  2. Disconnect the CAN connector.
  3. Disconnect the outputs.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-6 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in miliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in miliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-6 500 hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
current integer 0;1 1;3;5 1
  • 0 – Disable current sensor.
  • 1 – Use current sensor to detect blinds movement.
out_l_protect_on integer 1;3;5;98 1000 Overload protection threshold (mA). (Setting to 98 subId applies to all three current sensors.)
def string 'ON' 1-6 'OFF' Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char 'R' 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is 'r' or 'R' then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., 'd' ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop='r'
out char[6] 98 'PPP' Each char is responsible for the type of a particular channel

  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • '-'-none, nothing is connected.

Example: dm='BGV'

Example:

<item addr="449:1" cfgid="46" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4069"/>
<item addr="449:3" cfgid="46" name="Gate" sub-type="120" type="gate" uniq_id="4077" hw="runtime=55"/>
<item addr="449:5" cfgid="46" name="Valve" type="valve" uniq_id="4078"/>
<item addr="449:30" cfgid="46" name="Current" system="yes" type="current-sensor" uniq_id="4072"/>
<item addr="449:31" cfgid="46" name="Current" system="yes" type="current-sensor" uniq_id="4073"/>
<item addr="449:32" cfgid="46" name="Current" system="yes" type="current-sensor" uniq_id="4074"/>
<item addr="449:97" cfgid="46" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4075"/>
<item addr="449:98" cfgid="46" hw="out='BGV'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4076"/>