10-CHANNEL HEATING CONTROLLER
The device is designed for controlling heating devices (radiators, floor heating, fan coil units, etc.).
The device is equipped with 10 inputchannels for connection of temperature sensors (FW-FT or FW-TS).
Features
- 10 outputs for NO/NC valves or contactors
- 10 inputs for digital temperature sensors (FW-FT or FW-TS)
- Can to use temperature data from other modules
- 10 independed heating zones with weekly shedule
- Up to 20 heating profiles
- Built-in real time clock
Downloads
Connection of 10 valves
Connection of 10 temperature sensors
Module dimensions
Internal layout
Module parameters
Parameter name | Value |
---|---|
Input channels qty | 10 |
Output channels qty | 10 |
Input voltage | 20-250 V |
Current type | AC/DC |
Max load per channel | 0.5A(110W at 220V) |
Power supply | 11.5 … 27.5 V DC from CAN |
Max current(24V) | 110 mA |
Sensors line max length | 30 m |
Bus type | CAN (4-wire) |
Equipment installation type | DIN-rail (EN 60715) |
Case material | ABS |
Protection | IP40 |
Temperature range | -10 … +50 °C |
Size | 4U, 69x110x58 mm |
Weight | 140 g |
Connection of high load device

Indication of module operation.
Indicator | Status | Description |
Power | ![]() |
Power |
![]() |
Power not available | |
Activity | ![]() |
Transferring data |
![]() |
No data transferring | |
Error | ![]() |
No errors |
![]() |
Overheating | |
|
The device blinks once every two seconds. The data has not been transferred via the CAN bus for at least 5 minutes. |
Module installation and connection procedure
- Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
- Connect the CAN connector.
- Connect the X1 – X3 connectors.
- Configure the module using LT setup.
- Apply power to the load.
- Check all equipment for proper operation.
Module shut-off and deinstallation procedure
- Disconnect the power from the load.
- Disconnect the connectors X1 – X3.
- Disconnect the CAN connector.
- Remove the module from the DIN rail, releasing the latch at the bottom of the module base.
HW Settings
Name | Type, range | SUBID | Default | Description |
---|---|---|---|---|
runtime | integer 0-100 | 1-10 | 15 | runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15 |
hold | integer 0-10000 | 1-10 | 500 | hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500 |
def | string 'ON' | 1-10 | 'OFF' | Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON' |
offset | integer -39 – 39 | 31-40 | 0 | It is the sensor values offset; Example: offset='-15' |
stop | Char ‘R’ | 1-9 | – | (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’ |
out | char[10] | 98 | 'HHHHHHHHHH' | Each char is responsible for the type of a particular channel
Runtime is the open/close time, is used for jalousie(2 pole), gate(2 pole), valve(2 pole); Example: out='BGLKMVX' |
Example:
<item addr="348:1" cfgid="43" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4097" hw="runtime=45"/> <item addr="348:3" auto-period="600" cfgid="43" name="Lamp" type="lamp" uniq_id="4098" hw="def='ON'"/> <item addr="348:4" cfgid="43" name="Gate" sub-type="120" type="gate" uniq_id="4099" hw="runtime=30"/> <item addr="348:6" cfgid="43" name="Lock" type="lamp" uniq_id="4100" hw="hold=5000"/> <item addr="348:7" cfgid="43" name="Radiator" type="valve-heating" uniq_id="4029" hw="def='ON'"> <automation name="Eco" temperature-level="16" uniq_id="4030"/> <automation name="Comfort" temperature-level="22" uniq_id="4031"/> <automation name="Hot" temperature-level="25" uniq_id="4032"/> </item> <item addr="348:8" cfgid="43" name="Radiator" type="valve-heating" uniq_id="4033" hw="def='OFF'"> <automation name="Eco" temperature-level="16" uniq_id="4034"/> <automation name="Comfort" temperature-level="22" uniq_id="4035"/> <automation name="Hot" temperature-level="25" uniq_id="4036"/> </item> <item addr="348:31" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4089" hw="offset=10"/> <item addr="348:32" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4090" hw="offset=-15"/> <item addr="348:33" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4091"/> <item addr="348:34" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4092" hw="offset=5"/> <item addr="348:35" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4093"/> <item addr="348:36" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4094"/> <item addr="348:37" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4095"/> <item addr="348:38" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4096"/> <item addr="348:39" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4097"/> <item addr="348:40" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4098"/> <item addr="348:97" cfgid="43" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4041"/> <item addr="348:98" cfgid="43" hw="out='B-LG-KHJ--'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4042"/>