WATER LEAKAGE PROTECTION MODULE

The module supports the connection of 2 valves of water supply
shutoff and 4 leakage sensors (up to 16 FW-WL.B/EW-WL.B ).

Features

  • Supports 1p/2p valves
  • Valve feedback reed switch
  • 4 leakage zones
  • Ability to connect up to 16 FW-WL.B/EW-WL.B sensors
  • Sensor detection and diagnostics

Overview


Example of connection

Module dimensions

Internal layout

Module parameters

Parameter name Value
Output channels qty 4
Number of sensor inputs 4 FW-WL.A/EW-WL.A
16 FW-WL.B/EW-WL.B (4 per input)
Number of dry contact inputs 2
Input voltage 0-250 V AC/DC
Current type AC/DC
Max load per channel 5 А
Power supply 11.5 … 27.5 V DC from CAN
Max current(24V) 60 mA
Sensors VCC output 8..12 V
Sensors max VCC current 70 mA
R1-R2 inputs max current 3 mA
Sensor line max length 30m
Bus type CAN (4-wire)
Equipment installation type DIN-rail (EN 60715)
Case material ABS
Protection IP40
Temperature range -10 … +50 °C
Size 4U, 69x110x58 mm
Weight 100 g

Indication of module operation.

Bootloader

Indicator Status Description
Device in bootloader
Waiting for bootloader command
Flashing firmware

Firmware mode

Indicator Status Description
Identification
Operational mode

Error
Lost connection to server
Overheat
Overload

Module installation and connection procedure

  1. Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
  2. Connect the CAN connector.
  3. Connect the inputs and outputs.
  4. Configure the module using LT setup.
  5. Apply power to the load.
  6. Check all equipment for proper operation.

Module shut-off and deinstallation procedure

  1. Disconnect the power from the load.
  2. Disconnect the inputs and outputs.
  3. Disconnect the CAN connector.
  4. Remove the module from the DIN rail, releasing the latch at the bottom of the module base.

HW Settings

Example: leak='LLLL'

Name Type, range SUBID Default Description
runtime integer 0-100 1-4 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
hold integer 0-10000 1-4 500 hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
def string 'ON' 1-4 'OFF' Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
out char[4] 98 'V-V-' Each char is responsible for the type of a particular channel

  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • '-'-none, nothing is connected.

Example: out='V-V-'

leak char[4] 98 'LLLL' Each char is responsible for the type of a particular channel

  • 'L'-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • 'N'-Third party leakage sensor;
  • 'S' – Leak, on-the-floor (FW-WL.B) leakage sensor
  • '-'-none
in char[2] 98 'KK' Each char is responsible for the type of a particular channel

  • 'K' – Contact;
  • 'H' – Inverted contact;
  • '-' – none;

Example: in='HHKK'

Example:

<item addr="500:1" cfgid="53" hw="runtime=30" name="Valve" type="valve" uniq_id="4105"/>
<item addr="500:3" cfgid="53" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4117"/>
<item addr="500:11" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4107"/>
<item addr="500:12" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4108"/>
<item addr="500:13" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4109"/>
<item addr="500:14" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4110"/>
<item addr="500:21" cfgid="53" name="Door" type="door-sensor" uniq_id="4111"/>
<item addr="500:22" cfgid="53" name="Door" type="door-sensor" uniq_id="4112"/>
<item addr="500:23" cfgid="53" name="Door" type="door-sensor" uniq_id="4113"/>
<item addr="500:24" cfgid="53" name="Door" type="door-sensor" uniq_id="4114"/>
<item addr="500:97" cfgid="53" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4115"/>
<item addr="500:98" cfgid="53" hw="leak='NNLL' in='HHKK' out='V-B-'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4116"/>