Features
10 universal outputs support:
Lights
NC/NO heating valves
Blinds
1 or 2-pole gates
1 or 2-pole valves
NC/NO locks
Fan coil units
4 dimming outputs
24 Discreet inputs that support:
Buttons
Switches
reed switches
leak sensors
motion detectors
4 digital inputs for up to 8 temperature sensors
Extension port
Relays with AgSnO2 contacts rated for 80A 20ms inrush current
Cloud connection and control of all house systems
Voice control (Siri, Alexa, Google Home)
FF
Plugins engine allows expanding the system possibilities (e.g. integrating with Satel, Philips Hue, IKEA lights)
Safety against unauthorized intrusion ensured with RSA/AES256 encryption
Push notifications from the system on your phone (also possible to receive through Telegram and Viber messengers)
History (meter data for 1 year is stored)
Plug and play (possibility for fast and user-friendly extension of the system)
Regular system updates
Large constantly updated database of scripts to meet all your needs
Automatic daily backups via cloud with the possibility to restore the initial configuration
Open API (which allows integrating Larnitech into other systems)
Interactive and user-friendly LT SETUP Web interface available for advanced configuration
Plug and play
It is a completely ready-to-install Smart Home system kit
Downloads
DWG file
Introduction
METAFORSA SMART HOUSE Installation Manual describes the procedure for its installation, assembly, operation and setting.
While working with the system, you must strictly comply with all the requirements set out in this manual. Failure to comply may result in damage to the device, its failure, electric shock, fire and other fallout.
The manufacturer reserves the right to make changes to this manual without prior notice. This manual is an integral part of the system and shall remain with the end-use customer.
Safety requirements
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.
To avoid the risk of fire, electric shock, damage to the system and / or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:
• all connection works must be carried out without power;
• use appropriate tools and personal protection against electric shock;
• do not use damaged cables, wires and connectors;
• avoid folding of cables and wires;
• do not pinch or kink the cables and wires by applying excessive force. Otherwise, inner conductors of the cable and wires may be stripped or broken;
• do not use the power socket with poor contacts to connect;
• do not exceed the load parameters limit specified in this manual;
• the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.
When working with the system after voltage supply NEVER :
• make connection/disconnection of connectors;
• open modules and sensors.
System configuration and purpose
Purpose of the system
METAFORSA SMART HOUSE is a ready-made solution for automation of residential and commercial premises, hotel complexes which includes the most highly desired features of Smart House.
The device has 10 control channels, 4 dimming channels, 24 incoming sensor channels, and a digital sensors’ connection port.
Universal outputs can be used to control:
Universal inputs allow you to connect:
• Lighting
• Buttons/switching units
• Socket connectors
• Magnetic reed switches
• Underfloor heating
• Motion sensors
• Curtain/gate actuators
• Leakage sensors
• Water supply/heating valves
Digital sensors connection port
The digital sensors connection port allows you to connect a variety of digital sensors, such as temperature sensors, ambient light, humidity and other.
Expansion port
The expansion port allows you to upgrade the system by connecting auxiliary equipment, such as the control module for LED lighting, dimming, metering devices and other elements.
The package, which is completely ready-to-install, includes the basic hardware and software.
Package contents
The package comes standard with:
• Mainframe METAFORSA MF-14.А
1 pc
• Power supply unit MEANWELL DR-15-12
1 pc
• Motion sensor CW-MSD
3 pcs
• Leakage sensor FW-WL.A
2 pcs
• Temperature-sensitive element FW-TS.A
4 pcs
• Magnetic reed switch (window/door position sensor)
4 pcs
• Ethernet-cable noise filter
1 pc
• Power supply cord
1 pc
• Splitter OW bus
1 pc
• Manual
1 pc
Basic technical specifications of the System
The basic specifications and characteristics of the module METAFORSA MF-14.A are shown in t able 1 .
Table 1
Specification
Meaning
Output ports
Number of switched channels
10
Number of switched groups
10
Number of dimming channels
4
Commutation voltage
0-250 V AC/DC
Peak load (one channel)
16A
Peak load (device)
160A
Max load per dimming channel
0.5A (110W at 220V)
Dimmer type
MOSFET
Dimming type
trailing edge
Power supply cable connection type
connector
Permissible section of power supply cable to connect in socket:
single-conductor cable
multiple-conductor cable
tipped multiple-conductor cable
0.5 … 4mm2
0.5 … 4mm2
0.5 … 2.5mm2
Input port s
Number of discrete inputs
24
Number of digital inputs
4
Current maximum rating on the direct-current
voltage connectors
50mA
Other
Operating ambient temperature
0 … +45°С
Storage/transportation temperature
-20 … +60°С
Permissible humidity
0 … 95% (non-condensing)
Power supply
23 … 27.5 V DC
24V, 0.75A Recommended
Maximum demand
0.5А
Available interfaces
Ethernet, CAN, OneWire
Bus type
CAN (4-wire)
CAN (4-wire)
800 m* (twisted pair 5 cat)
CAN wire type
FTP Cat 5E
CAN connection type
connector
Digital line maximum length
30 m
Digital line wirde type
UTP/FTP Cat 5E
LAN maximum length
100 m
LAN wire type
UTP/FTP Cat 5E
LAN connection type
Connector RJ-45
Dimensional specifications
9U, 156x110x58 mm
Shell material
ABS plastic
Casing
IP40
Equipment installation type
DIN-rail (EN 60715)
Weight
400 g
* – installing additional power supply units is required for long lines; the maximum length of the line may be reduced by various interference factors
General structure of the System
Module general view is shown in fig. 1
Fig. 1 Module general view
1
— connector for load application and power supply
2
— connector for dimming-lamps application
3
— power connector
4
— Ethernet network connector
5-6
— connectors for digital sensors and buttons/switching units
7
— OneWire interface connector (for digital sensors)
8
— connector for expansion module.
Overview of the METAFORSA device external connectors:
At the top of the casing (fig. 1 ) there is:
At the bottom of the casing (fig. 1 ) there is:
connector (3) — module power supply connection;
connector (4) — Ethernet network connection;
connectors (5-6) — four six-point connectors for digital sensors connection – motion, leakage, reed switch sensors, and button/switching unit sensors;
connector (7) — OneWire digital sensors bus connection;
connector (8) — expansion module connection.
The physical configuration and contact point assignment of each connector are shown in table 2 .
Table 2
Connector
Contact
Assignment
1-10
Load application (light lamps, thermal actuators, etc.)
D1-4, L, N
Load application (dimming lamps)
Device status indicators
The module status indicators are described in table 3
+24V
GND
+24V — module power supply by an external 24 V power supply
GND — common
RJ45
Connector for LAN connectivity
In1-12, In13-24
GND
Controlling devices connection (buttons, magnetic reed switches, motion or leakage sensors):
+12V — sensor power output +12 V
In1 … In24 — logic inputs (0-12 V)
GND — common
OneWire
Digital sensors connection (temperature)
VCC — sensors power supply output +5V
OW1-OW4 — OneWire data buses
GND — common
CAN connector
VCC
GND
L
H
External modules connection for CAN-bus
VСС — 12V output for external devices power supply
GND — common
L — CAN-L data bus
H — CAN-H data bus
Table 3
Indicator
Status
Description
Power
Power
Power not available
Activity
Data communication
Data communication not available
Error
No errors
(blinking)
– 1 time per 5 seconds to indicate communication error;
– 2 times per 5 seconds to indicate module overheat;
– 3 times per 5 seconds to indicate dimmer outputs module overload;
– 4 times per 5 seconds to indicate absence of power on dimmers, if in configuration.
System installation and assembly
Before connecting the system, you must:
site the sensor and actuators (if not pre-installed), set the sensors and actuators;
site the module and power supply.
Note: The module must be installed near the power supply voltage source.
CAUTION!
AC power voltage must be provided to the system input through the circuit breaker assembly. It should be installed close to the power supply.
The power of circuit breaker assembly must comply with the load capacity;
Nothing else than the phase conductors can be connected to the module, the neutral wire is connected separately.
Typical diagram of METAFORSA MF-14.A module connection is shown in fig. 3 .
Fig. 3 Typical connection diagram
Connection of the actuators
Connection of the lights/electric contactor/heating thermal actuator
Fig. 4
Such actuators as light, electric contactor, heating thermal actuator should be switched on any of the outputs 1 – 10, the neutral wire and the ground wire should be connected directly to the switchboard. The example of connection is shown in Fig.4 .
Connection of high load device
Recomended contactors:
ABB ESB series
Schneider Acti 9 iCT series
Hager ESC series
Connection of single-pole water/gas supply valve
Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.
Fig. 5
The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.5 .
Connection of double-pole water/gas supply valve
Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6 .
Connection of single-pole gate actuator
Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7 .
Connection of double-pole gate actuator
Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8 .
Connection of curtain/jalousie/shutter actuator with 220V force control
Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9 .
Connection of curtain/jalousie/shutter actuator with low-voltage control
Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10 .
Connection of sensing elements/switches/buttons
Connection of motion sensors
The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11 .
Fig. 11
Connection of FW-WL.A leakage sensors
FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12 .
Fig. 12
Fig. 13
Configuration and connection of the FW-WL.A sensor
1. Terminals:
+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.
2. Sensor preset switch (optionally):
1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).
3. LED status indicator.
Connection of buttons/switches/magnetic reed switches
Buttons and reed switches are connected to any free input in1-in16, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-16 .
Fig. 14 connection of buttons/switching units
Fig. 15 connection of the magnetic reed switches (window/door position sensors)
Connection of digital sensors
The OW adapter (Fig. 16a ) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b ). The connected sensors are detected automatically and do not require any original setting.
Fig. 16a
Fig. 16b
Configuration and connection of the OW adapter
Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.
Connection of auxiliary equipment.
Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4 . The example of connection is shown in Fig. 17 .
Fig. 17
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.
Module installation and connection procedure
ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
Fasten the supply unit on the left side of the module.
Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
Connect the connectors (5), (6).
Connect the connectors (1), (2).
Connect the connector (3).
Apply power to the supply unit of METAFORSA module.
Wait until the module is loaded, then configure it in accordance with the System Setup Instructions .
Apply power to the connectors (1), (2).
Check all equipment for proper operation.
METAFORSA module shut-off and deinstallation procedure
De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
Disconnect the load power supply connectors (1), (2).
Disconnect the connector (3).
Disconnect the connectors (4)-(6).
Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.
Hardware setup
To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market . After installation, follow the System Setup Instructions .
Fault diagnostics and handling
The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: http://www.larnitech.com/support/ or support@larnitech.com .
There are also some tips in the FAQ section at our website http://www.larnitech.com/faq/ .
The actuators do not operate:
ensure the outputs are properly configured in the application (see System Setup Instructions );
check the connection is correct in accordance with table 2 and paragraph 3.6;
ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
verify the operability of the connected equipment.
The module is off, indication absent:
check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
check the connection of the supply unit to 220V power mains, the indicator should be ON.
Network connection fault:
ensure the Ethernet cable is properly wired and connected to the connector;
ensure the LED status indicators are ON on the Ethernet connector;
check the LAN configuration is correct, Ethernet cable loops are absent;
METAFORSA module and the device you are connecting from are in the same network.
hold
integer 0-10000
1-10
by default hold is the same as runtime
hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500
The sensors do not operate:
ensure the inputs are properly configured in the application (System Setup Instructions );
check the connection is correct in accordance with table 2 and paragraph 3.7;
ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3 ;
check the power supply availability on the sensors;
check the integrity of lines laid to the sensors.
The auxiliary equipment does not operate:
check the connection is correct in accordance with table 2 and paragraph 3.8-9;
ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3 ;
check the integrity of the CAN lines, voltage supply on the modules.
HW Settings
Name
Type, range
SUBID
Default
Description
runtime
integer 0-100
1-10
15
runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
runtimeopen
integer 0-60000
Blinds subId
Runtimeopen is the open time in miliseconds, is used for blinds; Example: runtime=15000
runtimeclose
integer 0-60000
Blinds subId
Runtimeclose is the close time in miliseconds, is used for blinds; Example: runtime=15000
hold
integer 0-10000
1-10
500
hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def
string 'ON'
1-10
'OFF'
def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop
Char ‘R’
1-7
–
(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out
char[10]
98
'LLLLHHHHP-'
Each char is responsible for the type of a particular channel
'L'-Lamp;
'M'-Lamp Inverse;
'J'-Heating NO, valve-heating, normally open;
'H'-Heating NC, valve-heating, normally closed;
'B'-Blinds (2 pole), jalousie/curtains;
'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
'G'-Gate (2 pole), 2 pole gate;
'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
'X'-Gate (1 pole /short press), 1 pole gate;
'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
'V'-Valve (2 pole), 2 pole valve;
'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
'R'-Valve (1 pole), 1 pole valve,;
'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
'K'-Lock (short press);
'N'-Lock (short press) Inverse;
'P'-Blinds (2 pole);
'O'-Blinds Inverse (2 pole), invert open-close;
'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
'-'-none, nothing is connected.
Example: out='LLB-G-V-W-'
dm
char[4]
98
‘LLLL’
Each char is responsible for the type of a particular channel
‘g’ – use like halogen dimer-lamp
‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
‘l’ – LED Function, dimmable LED lamps
‘v’ – linear Function of dimming
‘-‘ – Channel disabled
‘+’ – Regular channel
Example: dm=’skl-‘
def
integer 0-250
11-14
100
The default brightness level in case of a power reset (1..250). Example: def=250
min
integer 0-100
11-14
0
Minimum dimming level, example: min=10
max
integer 0-100
11-14
100
Maximum dimming level, example max=95
start
integer 0-100
11-14
0
The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force
integer 0-100
11-14
10
Time duration of the starting value (measured in milliseconds). Example: force=20
runtime
integer 0-60000
11-14
1000
Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset
integer (+/- 0…39)
39-46
'0'
sensor values offset; For example, offset is -3.8 :
hw="offset='-3.8'"
in
char[24]
98
'BBBBBBBBBBBBMMMLLLKKKKKK'
Each char is responsible for the type of a particular channel
'B'-Button;
'C'-nButton;
'S'-Switch;
'K'-Contact;
'H'-nContact;
‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
‘N’-Third party leakage sensor;
'M'-Motion, motion sensor;
'V'-nMotion, motion sensor;
'-'-none
Example: in='MMMMMMMMLLLLLLLLMMMMLLLL'