Difference between revisions of "Conditioner"
Jump to navigation
Jump to search
(Created page with "Air conditioner virtual device ===Example of description in XML=== <syntaxhighlight lang="xml" line> <item addr="335:112" name="Conditioner" type="conditioner" vane-ver="0x3"/...") |
(No difference)
|
Revision as of 14:41, 19 August 2021
Air conditioner virtual device
Example of description in XML
1<item addr="335:112" name="Conditioner" type="conditioner" vane-ver="0x3"/> // Conditioner virtual device description
2 <import-script id="335" CONDID="140" IRID="335:17" path="conditioner-MITS-4.txt"/> // Conditioner control script description
3//Description with the help of one tag:
4<item IRT="566:64" addr="566:250" name="conditioner" script-id="con" path="scripts/con.txt" type="conditioner"/>
Additional parameters
Name | type and variety | description | default value |
---|---|---|---|
path* | string | Path to script | - |
script-id | string | script id from the description for interface | - |
t-min | number | temperature low value | 16 |
t-delta | number | temperature range | 16 |
modes | bit mask | Mask of operation modes | 0xFF |
funs | bit mask | Mask of airflow mode | 0xFF |
vane-ver | bit mask | Mask of vertical fins mode | 0xFF |
vane-hor | bit mask | Mask of horizontal fins mode | 0xFF |
temperature-sensors | list | list of valve temperature sensors | - |
* – required fields
Device status (6 bytes)
Byte number | Description |
---|---|
0 | 0 bit – 0 is off, 1 is on 4-7th bit – mode of operation 0 – Fan, 1 – Cool, 2 – Dry, 3 – Heat, 4 – Auto. |
1 | temperature (t-min is to be added to the value) |
2 | reserved |
3 | 0-3d bit – position of horizontal fins 4-7th bit – position of vertical fins |
4 | 0-3d bit – airflow capacity |
Status setting
from the 1st to the 6th correspondingly