Difference between revisions of "Metaforsa2 MF-14/sr"

From Larnitech wiki page
Jump to navigation Jump to search
(Created page with "<div class="cautoin">OPREZ! Napon naizmenične struje mora da se obezbedi na ulaz sistema kroz sklop prekidača. Trebalo bi da se instalira blizu izvora napajanja.</div> #'''S...")
Tags: Mobile web edit Mobile edit
(Created page with "Tipični dijagram METAFORSA MF-14. Veza modula je prikazana na '''sl. 3.'' <div style="clear: both">700px|Fig. 3</div>")
Tags: Mobile web edit Mobile edit
Line 315: Line 315:
  
  
Typical diagram of METAFORSA MF-14.A module connection is shown in '''fig. 3.'''
+
Tipični dijagram METAFORSA MF-14. Veza modula je prikazana na '''sl. 3.''
 
<div style="clear: both">[[File:Mf14chcon.png|700px|Fig. 3]]</div>
 
<div style="clear: both">[[File:Mf14chcon.png|700px|Fig. 3]]</div>
  

Revision as of 08:26, 12 March 2024

Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF-14
Metaforsa2.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs24
Number of digital inputs4
General
Max CAN devices50
Max CAN bus length800 m (twisted pair 5 cat)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


Uvod

Instruktsiya z montazhu METAFORSA SMART HOUSE opysuye poryadok yoho montazhu, montazhu, ekspluatatsiyi ta nalashtuvannya. Pry roboti z systemoyu neobkhidno suvoro dotrymuvatysya vsikh vymoh, vykladenykh u tsiy instruktsiyi. Nedotrymannya mozhe pryzvesty do poshkodzhennya prystroyu, yoho polomky, urazhennya elektrychnym strumom, pozhezhi ta inshykh naslidkiv. Vyrobnyk zalyshaye za soboyu pravo vnosyty zminy v tsey posibnyk bez poperednʹoho povidomlennya. Tsey posibnyk ye nevidʺyemnoyu chastynoyu systemy ta maye zalyshatysya u kintsevoho korystuvacha.

Karakteristike

  • Podržava 10 univerzalnih izlaza:
    • Lights
    • NC/NO ventili za grejanje
    • Blinds
    • 1 ili 2-polne kapije
    • 1 ili 2-polni ventili
    • NC/NO brave
    • Fan coil jedinice
  • 4 izlaza za zatamnjivanje
  • 24 diskretna ulaza koji podržavaju:
    • Dugmad
    • Prekidači
    • prekidači
    • senzori curenja
    • detektori pokreta
  • 4 digitalna ulaza za do 8 temperaturnih senzora
  • Priključak za proširenje
  • Releji sa AgSnO2 kontaktima predviđeni za udarnu struju od 80A 20ms
  • Klaud veza i kontrola svih kućnih sistema
  • Upravljanje glasom (Siri, Aleka, Google Home)
  • Plugins engine omogućava proširenje mogućnosti sistema (npr. integracija sa Satel, Philips Hue, IKEA lampama)
  • Sigurnost od neovlašćenog upada osigurana RSA/AES256 enkripcijom
  • Push obaveštenja iz sistema na vašem telefonu (moguće je i primanje preko Telegram i Viber mesindžera)
  • Istorija (podaci brojila za godinu dana se čuvaju)
  • Plug and plai (mogućnost brzog i jednostavnog proširenja sistema)
  • Redovna ažuriranja sistema
  • Velika baza skripti koja se stalno ažurira kako bi zadovoljila sve vaše potrebe
  • Automatsko dnevno pravljenje rezervnih kopija preko oblaka sa mogućnošću vraćanja početne konfiguracije
  • Otvoreni API (koji omogućava integraciju Larnitech-a u druge sisteme)
  • Interaktivan i prilagođen korisniku LT SETUP Veb interfejs dostupan za naprednu konfiguraciju
  • Plug and plai
  • To je komplet sistema Smart Home spreman za instalaciju

Zahtevi za bezbednost

'OPREZ! Sve radove u vezi sa instalacijom, povezivanjem, podešavanjem, servisiranjem i podrškom mora izvoditi kvalifikovano osoblje sa dovoljnim veštinama i iskustvom u radu sa električnom opremom.

Da biste izbegli rizik od požara, strujnog udara, oštećenja sistema i/ili ličnih povreda, instalacija i montaža sistema se moraju izvršiti u skladu sa uputstvima navedenim u nastavku:


  • svi radovi na priključenju moraju se izvoditi bez struje;
  • koristite odgovarajući alat i ličnu zaštitu od strujnog udara;
  • ne koristite oštećene kablove, žice i konektore;
  • izbegavajte savijanje kablova i žica;
  • nemojte štipati ili savijati kablove i žice primenom prekomerne sile. U suprotnom, unutrašnji provodnici kabla i žica mogu biti ogoljeni ili slomljeni;
  • za povezivanje nemojte koristiti utičnicu sa lošim kontaktima;
  • ne prekoračite ograničenje parametara opterećenja navedeno u ovom priručniku;
  • presek žice provodnika za napajanje podleže specifikacijama za ograničenje gustine struje, tip izolacije i materijal žice. Lagani deo može dovesti do pregrevanja kabla i požara.


Kada radite sa sistemom nakon napajanja naponom NIKAD:

  • izvršiti spajanje/isključivanje konektora;
  • otvoreni moduli i senzori.

Konfiguracija sistema i svrha

Svrha sistema

METAFORSA SMART HOUSE je gotovo rešenje za automatizaciju stambenih i poslovnih prostora, hotelskih kompleksa koje uključuje najpoželjnije karakteristike Smart House.


Uređaj ima 10 kontrolnih kanala, 4 kanala za zatamnjivanje, 24 ulazna senzorska kanala i port za povezivanje digitalnih senzora.


Univerzalni izlazi se mogu koristiti za kontrolu: Univerzalni ulazi vam omogućavaju da povežete:
Rasveta Dugmad/preklopne jedinice
Utičnice Magnetni prekidači
Podno grejanje Senzori pokreta
Aktivatori za zavese/kapije Senzori curenja
Ventili za vodosnabdevanje/grejanje


Priključak za digitalne senzore


Port za povezivanje digitalnih senzora vam omogućava da povežete različite digitalne senzore, kao što su senzori temperature, ambijentalnog svetla, vlažnosti i drugih.


Port za proširenje


Port za proširenje vam omogućava da nadogradite sistem povezivanjem pomoćne opreme, kao što je kontrolni modul za LED osvetljenje, zatamnjenje, merne uređaje i druge elemente. Paket, koji je potpuno spreman za instalaciju, uključuje osnovni hardver i softver.

Sadržaj paketa

Paket standardno dolazi sa:

Mainframe METAFORSA MF-14.A 1 kom
Napajanje MEANVELL DR-15-12 1 kom
Senzor pokreta CV-MSD 3 kom
Senzor curenja FV-VL.A 2 kom
Element osetljiv na temperaturu FV-TS.A 4 kom
Magnetni reed prekidač (senzor položaja prozora/vrata) 4 kom
Filter šuma za Ethernet kabl 1 kom
Kabl za napajanje 1 kom

Osnovne tehničke specifikacije sistema

Osnovne specifikacije i karakteristike modula METAFORSA MF-14.A prikazane su u tabeli 1

Table1
Specifikacija Značenje
Izlazni portovi
Broj preklopljenih kanala 10
Broj preklopljenih grupa 10
Broj kanala zatamnjivanja 4
Napon komutacije 0-250 V AC/DC
Vršno opterećenje (jedan kanal) 16A
Vršno opterećenje (uređaj) 160A
Maksimalno opterećenje po kanalu za zatamnjenje 0,5 A (110 V na 220 V)
Tip dimera MOSFET
Tip opterećenja dimera R,C
Tip zatamnjivanja zadnja ivica
Vrsta priključka kabla za napajanje konektor
Dozvoljeni deo kabla za napajanje za povezivanje u utičnicu:
jednožilni kabl
kabl sa više provodnika
kabl sa više provodnika

0,5 … 4mm2
0,5 … 4mm2
0,5 … 2,5 mm2
Ulazni portovi
Broj diskretnih ulaza 24
Broj digitalnih ulaza 4
Maksimalna struja na konektorima jednosmernog napona 50mA
Ostalo
Radna temperatura okoline 0 … +45°S
temperatura skladištenja/transporta -20 … +60°S
Dozvoljena vlažnost 0 … 95% (bez kondenzacije)
Napajanje 12 … 27,5 V DC
24V, 0,75A Preporučeno
Maksimalna potražnja 0.5A
Dostupni interfejsi Ethernet, CAN, OneVire
Tip autobusa CAN (4-žični)
CAN (4-vire) 800 m* (upredeni par 5 mačaka)
CAN tip žice FTP Cat 5E
CAN tip veze konektor
Maksimalna dužina digitalne linije 30 m
Tip digitalne linije UTP/FTP Cat 5E
LAN maksimalna dužina 100 m
vrsta LAN žice UTP/FTP Cat 5E
vrsta LAN veze Konektor RJ-45
Dimenzionalne specifikacije 9U, 156k110k58 mm
Materijal školjke ABS plastika
Cusing IP40
Tip ugradnje opreme DIN šina (EN 60715)
Težina 400 g

<noviki>*</noviki> – potrebno je instaliranje dodatnih jedinica za napajanje za duge linije; maksimalna dužina linije može biti smanjena različitim faktorima interferencije

Opšta struktura sistema

Opšti prikaz modula je prikazan na 'sl. 1


Fig. 1 Module general view


1 — connector for load application
2 — connector for dimming-lamps application
3 — power connector
4 — Ethernet network connector
5-6 — connectors for digital sensors and buttons/switching units
7 — OneWire interface connector (for digital sensors)
8 — connector for expansion module.


Overview of the METAFORSA device external connectors: At the top of the casing (fig. 1) there is:


  • connector (1) — Devices connection;
  • connector (2) — Dimming lamps connection;


Na dnu kućišta (sl. 1) nalazi se:


  • konektor (3) — priključak za napajanje modula;
  • konektor (4) — Ethernet mrežna veza;
  • konektori (5-6) — četiri konektora u šest tačaka za povezivanje digitalnih senzora – senzori pokreta, curenja, reed prekidača i * senzori dugmeta/prekidača;
  • konektor (7) — OneVire digitalni senzori bus priključak;
  • konektor (8) — priključak modula za proširenje.

Fizička konfiguracija i dodela kontaktnih tačaka svakog konektora su prikazani u tabela 2.


Table2
Konektor Kontakt - Out.png 1-10 Primena opterećenja (svetleće lampe, termički aktuatori, itd.)
Dimm.png D1-4, L, N Aplikacija opterećenja (zatamnjenje lampe)
Indikatori statusa uređaja Indikatori statusa modula su opisani u tabela 3
24vconn.png +24V
GND
+24V — napajanje modula preko eksternog napajanja od 24 V GND — zajedničko
Rj45.jpg RJ45 Konektor za LAN povezivanje
Inputs.png In1-12, In13-24 GND Povezivanje kontrolnih uređaja (dugmad, magnetni reed prekidači, senzori pokreta ili curenja): +12V — izlazna snaga senzora +12 V
In1 … In24 — logički ulazi (0-12 V)
GND — zajednički
OW.png OneWire Povezivanje digitalnih senzora (temperatura)
VCC — izlaz napajanja senzora +5V
OV1-OV4 — OneVire sabirnice podataka
GND — zajednički
Can.jpg VCC
GND
L
H
Veza eksternih modula za CAN-bus
VSS — 24V izlaz za napajanje eksternih uređaja
GND — uobičajena
L — CAN-L magistrala podataka
H — CAN-H magistrala podataka
Table3
Indicator Status Description
Power G.png Power
E.png Power not available
Activity Y.png Data communication
E.png Data communication not available
Error E.png No errors
R.png Communication error
R.pngR.png Module overheat
R.pngR.pngR.png Dimmer outputs module overload
R.pngR.pngR.pngR.png Absence of power on dimmers, if in configuration

Instalacija i montaža sistema

Pre povezivanja sistema, morate:


  • postavite senzor i aktuatore (ako nisu unapred instalirani), podesite senzore i aktuatore;
  • lokacija modula i napajanja.


Napomena: Modul mora biti instaliran blizu izvora napona napajanja.


OPREZ! Napon naizmenične struje mora da se obezbedi na ulaz sistema kroz sklop prekidača. Trebalo bi da se instalira blizu izvora napajanja.
  1. Snaga sklopa prekidača mora biti u skladu sa kapacitetom opterećenja;
  2. Ništa drugo osim faznih provodnika se ne može povezati na modul, neutralna žica je odvojeno povezana.


Tipični dijagram METAFORSA MF-14. Veza modula je prikazana na 'sl. 3.

Fig. 3


Connection of the actuators

Connection of the lights/electric contactor/heating thermal actuator

lamp
Fig. 4
Such actuators as light, electric contactor, heating thermal actuator should be switched on any of the outputs 1 – 10, the neutral wire and the ground wire should be connected directly to the switchboard. The example of connection is shown in Fig.4.


Connection of high load device

Contactor Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.


Connection of single-pole water/gas supply valve

Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.
valve
Fig. 5
The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.5.


Connection of double-pole water/gas supply valve

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
valve
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Connection of single-pole gate actuator

Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.

1pgate
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

2pgate
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

Pjalousie
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

ljalousie
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors

The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11.

ms
Fig. 11


Connection of FW-WL.A leakage sensors

FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12.

Leak1.png

Fig12
Leak2.png

Fig13

Configuration and connection of the FW-WL.A sensor 1. Terminals:

+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.

2. Sensor preset switch (optionally):

1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).

3. LED status indicator.

Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in24, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-15.

Buttons.png

Fig14 connection of buttons/switching units
Reed-sv.png

Fig15 connection of the magnetic reed switches (window/door position sensors)

Connection of digital sensors

The OW adapter (Fig. 16a) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b). The connected sensors are detected automatically and do not require any original setting.

Ow1Conn.png

Fig16 a
Ow2Conn.png

Fig16 b

Configuration and connection of the OW adapter

Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 17.

Canex.png
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSBBBBSSSSSS' 12 buttons; 12 switches.

 1<item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> 
 2<item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> 
 3    <automation name="Eco" temperature-level="16" uniq_id="3781"/> 
 4    <automation name="Comfort" temperature-level="22" uniq_id="3782"/> 
 5    <automation name="Hot" temperature-level="25" uniq_id="3783"/> 
 6</item> 
 7<item addr="339:3" cfgid="40" hw="runtime=9" name="Jalousie" sub-type="120" type="jalousie" uniq_id="32"/> 
 8<item addr="339:5" cfgid="40" hw="runtime=13" name="Gate" sub-type="120" type="gate" uniq_id="3784"/> 
 9<item addr="339:7" cfgid="40" hw="hold=4600" name="Gate" sub-type="120" type="gate" uniq_id="3785"/> 
10<item addr="339:8" cfgid="40" hw="runtime=10" name="Valve" type="valve" uniq_id="3786"/> 
11<item addr="339:11" cfgid="40" name="Motion" type="motion-sensor" uniq_id="17"/> 
12<item addr="339:12" cfgid="40" name="Motion" type="motion-sensor" uniq_id="18"/> 
13<item addr="339:13" cfgid="40" name="Motion" type="motion-sensor" uniq_id="19"/> 
14<item addr="339:16" cfgid="40" name="Leak" type="leak-sensor" uniq_id="21"/> 
15<item addr="339:17" cfgid="40" name="Leak" type="leak-sensor" uniq_id="41"/> 
16<item addr="339:19" cfgid="40" name="Switch" type="switch" uniq_id="22"/> 
17<item addr="339:20" cfgid="40" name="Switch" type="switch" uniq_id="23"/> 
18<item addr="339:21" cfgid="40" name="Switch" type="switch" uniq_id="24"/> 
19<item addr="339:22" cfgid="40" name="Switch" type="switch" uniq_id="25"/> 
20<item addr="339:23" cfgid="40" name="Door" type="door-sensor" uniq_id="26"/>
21<item addr="339:24" cfgid="40" name="Door" type="door-sensor" uniq_id="27"/> 
22<item addr="339:25" cfgid="40" name="Door" type="door-sensor" uniq_id="28"/> 
23<item addr="339:26" cfgid="40" name="Door" type="door-sensor" uniq_id="29"/> 
24<item addr="339:30" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3772"/> 
25<item addr="339:31" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3773"/> 
26<item addr="339:32" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3774"/> 
27<item addr="339:33" cfgid="40" hw="offset='-10.8'" name="Temperature" type="temperature-sensor" uniq_id="3775"/> 
28<item addr="339:34" cfgid="40" hw="offset='25.1'" name="Temperature" type="temperature-sensor" uniq_id="3776"/> 
29<item addr="339:35" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3777"/> 
30<item addr="339:36" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3778"/> 
31<item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/>