Difference between revisions of "Translations:Metaforsa2 MF-14/71/en"

From Larnitech wiki page
Jump to navigation Jump to search
(Importing a new version from external source)
 
(No difference)

Latest revision as of 12:59, 25 December 2021

Information about message (contribute)
This message has no documentation. If you know where or how this message is used, you can help other translators by adding documentation to this message.
Message definition (Metaforsa2 MF-14)
#De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
#Disconnect the load power supply connectors (1), (2).
#Disconnect the connector (3).
#Disconnect the connectors (4)-(6).
#Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.
Translation#De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
#Disconnect the load power supply connectors (1), (2).
#Disconnect the connector (3).
#Disconnect the connectors (4)-(6).
#Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.
  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.