Difference between revisions of "DW-HC08.A"
Jump to navigation
Jump to search
(Created page with "{{RevisionChanger | hasA = 1 | hasB = 1 | hasC = 1}} {{Infobox module | name = DW-HC10.A | image = DW-HC10A.png | outCount = 10 | dimmOut = | peakl = 0.5...") |
|||
Line 1: | Line 1: | ||
{{RevisionChanger | hasA = 1 | hasB = 1 | hasC = 1}} | {{RevisionChanger | hasA = 1 | hasB = 1 | hasC = 1}} | ||
{{Infobox module | {{Infobox module | ||
− | | name = DW- | + | | name = DW-HC08.A |
− | | image = DW- | + | | image = DW-HC08A.png |
− | | outCount = | + | | outCount = 8 |
| dimmOut = | | dimmOut = | ||
| peakl = 0.5A | | peakl = 0.5A | ||
Line 9: | Line 9: | ||
| dt = | | dt = | ||
| inDisc = | | inDisc = | ||
− | | inDigit = | + | | inDigit = 8 |
| voltage = 11.5...27.5 V DC | | voltage = 11.5...27.5 V DC | ||
| dim = 4U, 69x110x58 mm | | dim = 4U, 69x110x58 mm | ||
}} | }} | ||
− | == | + | ==8-CHANNEL HEATING CONTROLLER== |
The device is designed for controlling heating devices (radiators, floor heating, fan coil units, etc.). | The device is designed for controlling heating devices (radiators, floor heating, fan coil units, etc.). | ||
− | The device is equipped with | + | The device is equipped with 8 inputchannels for connection of temperature sensors (FW-FT or FW-TS). |
==Features== | ==Features== | ||
− | * | + | *8 outputs for NO/NC valves or contactors |
− | * | + | *8 inputs for digital temperature sensors (FW-FT or FW-TS) |
*Can to use temperature data from other modules | *Can to use temperature data from other modules | ||
− | * | + | *8 independed heating zones with weekly shedule |
*Up to 20 heating profiles | *Up to 20 heating profiles | ||
*Built-in real time clock | *Built-in real time clock | ||
Line 45: | Line 45: | ||
==Overview== | ==Overview== | ||
− | [[File: | + | [[File:HC08A VIEW.png|500px]] |
− | ==Connection of | + | ==Connection of 8 valves== |
− | [[File: | + | [[File:HC08A OUT.png|300px]] |
− | ==Connection of | + | ==Connection of 8 temperature sensors== |
− | [[File: | + | [[File:HC08A IN.png|300px]] |
==Module dimensions== | ==Module dimensions== | ||
− | [[File: | + | [[File:HC08A DIM.png|500px]] |
==Internal layout== | ==Internal layout== | ||
− | [[File: | + | [[File:HC08A IL.png|500px]] |
==Module parameters== | ==Module parameters== | ||
{{Mp | {{Mp | ||
− | | outqty = | + | | outqty = 8 |
− | | inqty = | + | | inqty = 8 |
| involtage = 20-250V | | involtage = 20-250V | ||
| currtype = AC/DC | | currtype = AC/DC | ||
| maxperch = 0.5A(110W at 220V) | | maxperch = 0.5A(110W at 220V) | ||
| power = 11.5 … 27.5 V DC from CAN | | power = 11.5 … 27.5 V DC from CAN | ||
− | | maxcur24v = | + | | maxcur24v = 90 mA |
| smaxlen = 30m | | smaxlen = 30m | ||
| bustype = CAN (4-wire) | | bustype = CAN (4-wire) | ||
Line 87: | Line 87: | ||
{| class="wikitable" style="max-width:800px" ; | {| class="wikitable" style="max-width:800px" ; | ||
|- | |- | ||
− | |[[File: | + | |[[File:HC08Aexa1.png|200px|Contactor]]|| style="margin:20px" |Recomended contactors: |
*ABB ESB series | *ABB ESB series | ||
*Schneider Acti 9 iCT series | *Schneider Acti 9 iCT series | ||
Line 116: | Line 116: | ||
!Name!!Type, range!!SUBID!!Default!!Description | !Name!!Type, range!!SUBID!!Default!!Description | ||
|- | |- | ||
− | |runtime||integer 0-100||1- | + | |runtime||integer 0-100||1-8||15||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15 |
+ | |||
|- | |- | ||
− | |hold||integer 0-10000||1- | + | |hold||integer 0-10000||1-8||500||hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500 |
|- | |- | ||
− | |def||string 'ON'||1- | + | |def||string 'ON'||1-8||'OFF'||Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON' |
|- | |- | ||
− | |offset||integer -39 – 39||31- | + | |offset||integer -39 – 39||31-38||0||It is the sensor values offset; Example: offset='-15' |
|- | |- | ||
− | |stop||Char 'R'||1- | + | |stop||Char 'R'||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is 'r' or 'R' then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., 'd' ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop='r' |
|- | |- | ||
− | |out||char[ | + | |out||char[8]||98||'HHHHHHHH'||Each char is responsible for the type of a particular channel |
*'L'-Lamp; | *'L'-Lamp; | ||
*'M'-Lamp Inverse; | *'M'-Lamp Inverse; | ||
Line 149: | Line 150: | ||
*'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control; | *'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control; | ||
*'-'-none, nothing is connected. | *'-'-none, nothing is connected. | ||
− | Example: | + | Example: dm='BGLKMX' |
|} | |} | ||
Line 175: | Line 176: | ||
<item addr="348:37" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4095"/> | <item addr="348:37" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4095"/> | ||
<item addr="348:38" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4096"/> | <item addr="348:38" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4096"/> | ||
− | |||
− | |||
<item addr="348:97" cfgid="43" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4041"/> | <item addr="348:97" cfgid="43" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4041"/> | ||
− | <item addr="348:98" cfgid="43" hw="out='B-LG-KHJ | + | <item addr="348:98" cfgid="43" hw="out='B-LG-KHJ'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4042"/> |
</syntaxhighlight> | </syntaxhighlight> |
Revision as of 07:39, 9 August 2021
DW-HC08.A | |||||||
---|---|---|---|---|---|---|---|
| |||||||
| |||||||
|
8-CHANNEL HEATING CONTROLLER
The device is designed for controlling heating devices (radiators, floor heating, fan coil units, etc.). The device is equipped with 8 inputchannels for connection of temperature sensors (FW-FT or FW-TS).
Features
- 8 outputs for NO/NC valves or contactors
- 8 inputs for digital temperature sensors (FW-FT or FW-TS)
- Can to use temperature data from other modules
- 8 independed heating zones with weekly shedule
- Up to 20 heating profiles
- Built-in real time clock
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment. To avoid the risk of fire, electric shock, damage to the system and/or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:
- all connectivity work must be carried out with the power turned OFF;
- use appropriate tools and personal protection against electric shock;
- do not use damaged cables, wires and connectors;
- avoid folding the cables and wires;
- do not apply excessive force to the wires by kinking or pressing them too hard: the inner conductors of the cables and wires may get stripped or damaged;
- do not use the power socket with poor contacts to connect;
- do not exceed the load limit parameters specified in the manual;
- the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.
When the power is on, NEVER:
- connect/disconnect the connectors;
- open modules and sensors.
Overview
Connection of 8 valves
Connection of 8 temperature sensors
Module dimensions
Internal layout
Module parameters
Parameter name | Value |
---|---|
Input channels qty | 8 |
Output channels qty | 8 |
Input voltage | 20-250V |
Current type | AC/DC |
Max load per channel | 0.5A(110W at 220V) |
Power supply | 11.5 … 27.5 V DC from CAN |
Max current(24V) | 90 mA |
Sensors line max length | 30m |
Bus type | CAN (4-wire) |
Equipment installation type | DIN rail (EN 60715) |
Case material | ABS |
Protection | IP40 |
Temperature range | -10 … +50 °C |
Size | 4U, 69x110x58 mm |
Weight | 140 g |
Connection of high load device
Recomended contactors:
|
Indication of module operation
Indicator | Status | Description |
---|---|---|
Power | Power | |
Power not available | ||
Activity | Data communication | |
Data communication not available | ||
Error | No errors | |
Overheating | ||
The data has not been transferred via the CAN bus for at least 5 minutes. |
Module installation and connection procedure
- Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
- Connect the CAN connector.
- Connect the X1-X3 connectors.
- Configure the module using LT setup.
- Apply power to the load.
- Check all equipment for proper operation.
Module shut-off and deinstallation procedure
- Disconnect the power from the load.
- Disconnect the X1-X3 connectors.
- Disconnect the CAN connector.
- Remove the module from the DIN rail, releasing the latch at the bottom of the module base.
HW settings
Name | Type, range | SUBID | Default | Description |
---|---|---|---|---|
runtime | integer 0-100 | 1-8 | 15 | runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15 |
hold | integer 0-10000 | 1-8 | 500 | hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500 |
def | string 'ON' | 1-8 | 'OFF' | Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON' |
offset | integer -39 – 39 | 31-38 | 0 | It is the sensor values offset; Example: offset='-15' |
stop | Char 'R' | 1-7 | – | (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is 'r' or 'R' then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., 'd' ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop='r' |
out | char[8] | 98 | 'HHHHHHHH' | Each char is responsible for the type of a particular channel
Example: dm='BGLKMX' |
1<item addr="348:1" cfgid="43" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4097" hw="runtime=45"/>
2<item addr="348:3" auto-period="600" cfgid="43" name="Lamp" type="lamp" uniq_id="4098" hw="def='ON'"/>
3<item addr="348:4" cfgid="43" name="Gate" sub-type="120" type="gate" uniq_id="4099" hw="runtime=30"/>
4<item addr="348:6" cfgid="43" name="Lock" type="lamp" uniq_id="4100" hw="hold=5000"/>
5<item addr="348:7" cfgid="43" name="Radiator" type="valve-heating" uniq_id="4029" hw="def='ON'">
6 <automation name="Eco" temperature-level="16" uniq_id="4030"/>
7 <automation name="Comfort" temperature-level="22" uniq_id="4031"/>
8 <automation name="Hot" temperature-level="25" uniq_id="4032"/>
9</item>
10<item addr="348:8" cfgid="43" name="Radiator" type="valve-heating" uniq_id="4033" hw="def='OFF'">
11 <automation name="Eco" temperature-level="16" uniq_id="4034"/>
12 <automation name="Comfort" temperature-level="22" uniq_id="4035"/>
13 <automation name="Hot" temperature-level="25" uniq_id="4036"/>
14</item>
15<item addr="348:31" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4089" hw="offset=10"/>
16<item addr="348:32" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4090" hw="offset=-15"/>
17<item addr="348:33" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4091"/>
18<item addr="348:34" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4092" hw="offset=5"/>
19<item addr="348:35" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4093"/>
20<item addr="348:36" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4094"/>
21<item addr="348:37" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4095"/>
22<item addr="348:38" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4096"/>
23<item addr="348:97" cfgid="43" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4041"/>
24<item addr="348:98" cfgid="43" hw="out='B-LG-KHJ'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4042"/>