DW-RC12.B
DW-RC12.B.png
Output ports
Number of switched channels12
Peak load16A
Input ports
Number of discrete inputs24
Number of digital inputs4
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


12-CHANNEL EXTENSION MODULE

Has 12 outputs for connecting loads and 24 inputs for connecting various sensors/buttons.

Module general view is shown in fig. 1


Fig. 1 Module general view



System installation and assembly

Before connecting the system, you must:


  • site the sensor and actuators (if not pre-installed), set the sensors and actuators;
  • site the module and power supply.


Typical diagram of DW-RC12.B module connection is shown in fig. 2.

Fig. 2

Features

  • 12 universal outputs support:
    • Lights
    • NC/NO heating valves
    • Blinds
    • 1 or 2-pole gates
    • 1 or 2-pole valves
    • NC/NO locks
    • Fan coil units
  • 24 Discreet inputs that support:
    • Buttons
    • Switches
    • Reed switches
    • Leak sensors
    • Motion detectors
  • 4 digital inputs for up to 8 temperature sensors

CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment. To avoid the risk of fire, electric shock, damage to the system and/or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:

  • all connectivity work must be carried out with the power turned OFF;
  • use appropriate tools and personal protection against electric shock;
  • do not use damaged cables, wires and connectors;
  • avoid folding the cables and wires;
  • do not apply excessive force to the wires by kinking or pressing them too hard: the inner conductors of the cables and wires may get stripped or damaged;
  • do not use the power socket with poor contacts to connect;
  • do not exceed the load limit parameters specified in the manual;
  • the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.

When the power is on, NEVER:

  • connect/disconnect the connectors;
  • open modules and sensors.

Module parameters

Parameter name Value
Input channels qty
Input/output channels qty
0-10 input port quantity
Buttons
LED Buttons
Number of sensor inputs
Number of dry contact inputs
RS485 ports qty
RS232 ports qty
UART ports qty
M-BUS port quantity
Pulse inputs quantity
DALI ports qty
DALI-line voltage supply
Peak current of DALI-line power supply
Peak current in DALI-line
Maximum DALI devices quantity
Dimming channels qty
Output channels qty 12
0-10 output port quantity
Analog output channels qty
Output
Digital line maximum length 30 m
Discrete input channels qty 24
Digital input channels qty 4
Speakers
Max power output audio channel
Camera
IR lighting
Card reader
Connection type
Protocols
Backlight voltage
Load type
Dimmer load type
Supported sensors
Input voltage 0-250V
Current type AC/DC
Adjustment type
Max load
Min load
Max load per channel 16A
Max load per group
Max load per device
Control parameters
Angle of vision IR °
Angle of motion °
Temperature measuring range °C
Humidity measuring range
Dimmer type
Dimming type
Voltage that may be applied to the input channels 0-250V
Max output switching voltage
Max output switching current
Power supply 20.0 … 27.5 V DC from CAN
Max current(24V) ??? mA
Max current(13V)
Max detection distance
Max IR distance
Max BT distance
Max current
Relay
Data transfer speed
Permissible section of power supply cable to connect in socket:
Sensors VCC output
Sensors max VCC current
R1-R2 inputs max current
Push-button/reed switches line recommended length
Temperature sensor line max length
Sensor cable length
Sensors line max length
Bus type CAN
Compatible with
Output voltage
Output current
Equipment installation type DIN rail (EN 60715)
Mounting
Max cabel lenght
Case material ABS
Protection IP40
Temperature range -10 … +50 °C
Size 9U, 156x110x58 mm
Weight ??? g
* -
** -
*** -
1 -
2 -
3 -


Connectivity recommendations

In order to protect the actuator and loads connected to it, installing a circuit breaker is recommended. The nominal value of the circuit breaker should be calculated based on the maximum total load of connected devices and at the same time should not significantly exceed the maximum permissible characteristics of the actuator. Depending on the requirements, you can use one circuit breaker for one actuator (it is recommended) or one circuit breaker per each group of connected loads, or, if necessary, a separate circuit breaker can be installed for each load.

Connection of actuators

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. If free (unused) channels remain in a given group after a curtain/jalousie/shutter actuator with low-voltage control or gate actuator has been connected to it, these channels need to be left unused. (Do not connect other devices to them!)

Connection of the lights/electric contactor/heating thermal actuator

Lamps.png
Sample HW for this configuration

1hw="out='LLL----'"


Connection of high load device

Contactor Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.

Connection of curtain/jalousie/shutter actuator with 220V force control

Pjalousie.png
Sample HW for this configuration

1hw="out='B------'"

Connection of curtain/jalousie/shutter actuator with low-voltage control

Ljalousie.png
Sample HW for this configuration

1hw="out='B------'"

Connection of single-pole gate actuator

1pgate.png
Sample HW for this configuration

1hw="out='X------'"

Connection of double-pole gate actuator

2pgate.png
Sample HW for this configuration

1hw="out='G------'"


Connection of single-pole water/gas supply valve

1pvalve.png
Sample HW for this configuration

1hw="out='R------'"

Connection of double-pole water/gas supply valve

2pvalve.png
Sample HW for this configuration

1hw="out='V------'"

Connection of fancoil control unit

Fancoil.png
Sample HW for this configuration

1hw="out='FFF----'"

Example of sensors connection

SensorsCon4.png
2-wire connection recommended

Indication of module operation

Bootloader

Indicator Status Description
Top.png
Yl.png Device in bootloader
Bot.png
B.pngB.png Downloading firmware
R.pngR.png Flashing firmware

Firmware mode

Indicator Status Description
Top.png
G.pngG.pngG.pngDots.png Network configuration
B.pngB.pngB.pngDots.png Identification
Gl.png Operational mode
Yl.png Operational mode
Bot.png

Error
R.png Lost connection to server
R.pngR.png Overheat
R.pngR.pngR.png Overload
R.pngR.pngR.pngR.png No AC power
R.pngR.pngR.pngR.pngR.png RTC error
Bot.png

Activity
Y.png CAN activity
Bg.png OW activity
M.png RS-485 activity
B.png Ethernet activity


Module installation and connection procedure

  1. Connect the outputs.
  2. Connect the inputs.
  3. Connect the Can connector.
  4. Configure the module using LT setup.
  5. Apply power to the load
  6. Check all equipment for proper operation.

Module shut-off and deinstallation procedure

  1. Disconnect the power from the load
  2. Disconnect the CAN connector.
  3. Disconnect the inputs.
  4. Disconnect the outputs.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-12 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
runtimeopen integer 0-60000 Blinds subId - Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId - Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-12 500 hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
def string 'ON' 1-12 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-12 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[12] 98 'LLLLLLLLLLLL' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds, jalousie/curtains(2 pole);
  • 'C'-Blinds Inverse, jalousie/curtains, invert open-close(2 pole);
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLMMHHB-FFFF'

offset float SubID of OW temperature sensors '0' [+/- 0..39] – sensor values offset;

For example, offset is -3.8 : hw="offset='-3.8'"

in char[24] 98 'KKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-Inverted button;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-Inverted contact;
  • 'L'-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • 'N'-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-Motion sensor (CW-MSD);
  • '-'-none

Example: in='MMM--LL-BBBBKKKKNSSSKKKK'

 1<item addr="372:1" auto-period="600" cfgid="193" hw="def='OFF'" name="Lamp 1" type="lamp"/>
 2		<item addr="372:2" auto-period="600" cfgid="193" hw="def='OFF'" name="Lamp 2" type="lamp"/>
 3		<item addr="372:3" auto-period="600" cfgid="193" hw="def='OFF'" name="Lamp 3" type="lamp"/>
 4		<item addr="372:4" auto-period="600" cfgid="193" hw="def='OFF'" name="Lamp 4" type="lamp"/>
 5		<item addr="372:5" cfgid="193" hw="def='OFF'" name="Radiator" temperature-lag="0.2" type="valve-heating">
 6			<automation name="Eco" temperature-level="16"/>
 7			<automation name="Comfort" temperature-level="22"/>
 8			<automation name="Hot" temperature-level="25"/>
 9		</item>
10		<item addr="372:6" cfgid="193" hw="def='OFF'" name="Radiator" temperature-lag="0.2" type="valve-heating">
11			<automation name="Eco" temperature-level="16"/>
12			<automation name="Comfort" temperature-level="22"/>
13			<automation name="Hot" temperature-level="25"/>
14		</item>
15		<item addr="372:7" cfgid="193" name="Jalousie" sub-type="120" type="jalousie"/>
16		<item addr="372:13" cfgid="193" name="Motion" type="motion-sensor"/>
17		<item addr="372:14" cfgid="193" name="Motion" type="motion-sensor"/>
18		<item addr="372:15" cfgid="193" name="Motion" type="motion-sensor"/>
19		<item addr="372:18" cfgid="193" name="Leak" type="leak-sensor"/>
20		<item addr="372:19" cfgid="193" name="Leak" type="leak-sensor"/>
21		<item addr="372:21" cfgid="193" name="Switch 1" type="switch"/>
22		<item addr="372:22" cfgid="193" name="Switch 2" type="switch"/>
23		<item addr="372:23" cfgid="193" name="Switch 3" type="switch"/>
24		<item addr="372:24" cfgid="193" name="Switch 4" type="switch"/>
25		<item addr="372:25" cfgid="193" name="Door 1" type="door-sensor"/>
26		<item addr="372:26" cfgid="193" name="Door 2" type="door-sensor"/>
27		<item addr="372:27" cfgid="193" name="Door 3" type="door-sensor"/>
28		<item addr="372:28" cfgid="193" name="Door 4" type="door-sensor"/>
29		<item addr="372:29" cfgid="193" name="Leak" type="leak-sensor"/>
30		<item addr="372:30" cfgid="193" name="Switch 5" type="switch"/>
31		<item addr="372:31" cfgid="193" name="Switch 6" type="switch"/>
32		<item addr="372:32" cfgid="193" name="Switch 7" type="switch"/>
33		<item addr="372:33" cfgid="193" name="Door 5" type="door-sensor"/>
34		<item addr="372:34" cfgid="193" name="Door 6" type="door-sensor"/>
35		<item addr="372:35" cfgid="193" name="Door 7" type="door-sensor"/>
36		<item addr="372:36" cfgid="193" name="Door 8" type="door-sensor"/>
37		<item addr="372:50" cfgid="193" name="Fancoil" type="fancoil"/>
38		<item addr="372:98" cfgid="193" hw="out='LLMMHHB-FFFF' in='MMM--LL-BBBBKKKKNSSSKKKK'" logic-ver="19" name="Temperature" sn="2516678146" system="yes" type="temperature-sensor"/>