Difference between revisions of "Metaforsa 3/3.plus/pt"

From Larnitech wiki page
Jump to navigation Jump to search
(Created page with "====Conexão da válvula unipolar de abastecimento de água/gás====")
Tags: Mobile web edit Mobile edit
(Created page with "{| class="wikitable" style="width:800px"; |- |colspan="2" style="background-color:#dededf" |'''Cuidado: Antes de alimentar a carga, certifique-se de que a configuração de sa...")
Tags: Mobile web edit Mobile edit
Line 339: Line 339:
 
{| class="wikitable" style="width:800px";
 
{| class="wikitable" style="width:800px";
 
|-
 
|-
|colspan="2" style="background-color:#dededf" |'''Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.'''
+
|colspan="2" style="background-color:#dededf" |'''Cuidado: Antes de alimentar a carga, certifique-se de que a configuração de saída do módulo METAFORSA esteja correta. A configuração incorreta ou conexão incorreta pode causar falha do módulo e/ou falha dos equipamentos a ele conectados, e até mesmo incêndio.'''
 
|-
 
|-
|[[File:1pvalve.png|350px|valve]]<br>'''Fig. 5'''|| style="margin:20px"|The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in '''Fig.5'''.
+
|[[File:1pvalve.png|350px|valve]]<br>'''Fig. 5'''|| style="margin:20px"|A válvula unipolar de abastecimento de água/gás é conectada a qualquer uma das saídas de 1 – 10, o (fio neutro e o fio terra são conectados diretamente ao quadro. O exemplo de conexão é mostrado na '''Fig.5'''.
 
|}
 
|}
  

Revision as of 10:17, 8 April 2024

Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF3/MF3.plus
METAFORSA 3 MF3-14.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs28
General
Max CAN devices4 (can be extended with the license) 99 (for Metaforsa 3.plus)
Max CAN bus length800 m (twisted pair CAT5e)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x90x58 mm


Introdução

O Manual de Instalação METAFORSA SMART HOUSE descreve o procedimento para sua instalação, montagem, operação e configuração. Ao trabalhar com o sistema, você deve cumprir rigorosamente todos os requisitos estabelecidos neste manual. O não cumprimento pode resultar em danos ao dispositivo, sua falha, choque elétrico, incêndio e outras consequências. O fabricante reserva-se o direito de fazer alterações neste manual sem aviso prévio. Este manual é parte integrante do sistema e deve permanecer com o cliente final.

Recursos

  • Suporte para 10 saídas universais:
    • Luzes
    • Válvulas de aquecimento NC/NO
    • Persianas
    • Portões de 1 ou 2 pólos
    • Válvulas de 1 ou 2 pólos
    • Bloqueios NC/NO
    • Unidades ventiloconvectoras
  • 4 saídas de escurecimento
  • 28 entradas que suportam:
    • Botões
    • Botões LED
    • Comuta
    • Interruptores Reed
    • Sensores de vazamento
    • Detectores de movimento
    • Sensores de temperatura
    • Tiras de LED
    • Tiras RGB de 3-4-5 canais
    • Tiras WS2812B
    • Dispositivos RS485 (apenas para Metaforsa 3.plus)
  • Porta de extensão
  • Relés com contatos AgSnO2 classificados para corrente de partida de 80A 20ms
  • Conexão em nuvem e controle de todos os sistemas domésticos
  • Controle de voz (Siri, Alexa, Google Home)

Requisitos de segurança

CUIDADO! Todos os trabalhos relacionados com a instalação, ligação, configuração, manutenção e suporte devem ser realizados por pessoal qualificado com competências e experiência suficientes no trabalho com equipamentos elétricos.

Para evitar o risco de incêndio, choque elétrico, danos ao sistema e/ou ferimentos pessoais, a instalação e montagem do sistema devem ser realizadas de acordo com as instruções listadas abaixo:


  • todos os trabalhos de ligação devem ser realizados sem energia;
  • utilizar ferramentas adequadas e proteção individual contra choques elétricos;
  • não utilize cabos, fios e conectores danificados;
  • evite dobrar cabos e fios;
  • não aperte ou dobre os cabos e fios aplicando força excessiva. Caso contrário, os condutores internos do cabo e dos fios poderão ficar descascados ou quebrados;
  • não utilize tomada com mau contato para conectar;
  • não exceda o limite dos parâmetros de carga especificados neste manual;
  • a seção do fio dos condutores de alimentação está sujeita às especificações de limite de densidade de corrente, tipo de isolamento e material do fio. A seção leve pode resultar em superaquecimento do cabo e incêndio.


Ao trabalhar com o sistema após alimentação de tensão NUNCA:

  • fazer conexão/desconexão de conectores;
  • módulos e sensores abertos.

Configuração e finalidade do sistema

Objetivo do sistema

METAFORSA SMART HOUSE é uma solução pronta para automação de instalações residenciais e comerciais, complexos hoteleiros que inclui as características mais desejadas da Smart House.


O dispositivo possui 10 canais de controle, 4 canais de dimerização e 28 canais de entrada.


As saídas universais podem ser usadas para controlar: As entradas universais permitem conectar:
Iluminação Botões/botões LED/unidades de comutação
Conectores de soquete Interruptores reed magnéticos
Aquecimento por piso radiante Sensores de vazamento
Cortina Detectores de movimento
Atuadores de portão Sensores de temperatura
Abastecimento de água Tiras de LED/tiras RGB de 3-4-5 canais/tiras WS2812B
Válvulas de aquecimento Dispositivos RS485*

* – Somente para Metaforsa 3.plus


Porta de expansão


A porta de expansão permite atualizar o sistema conectando equipamentos auxiliares, como módulo de controle de iluminação LED, dimmer, dispositivos de medição e outros elementos. O pacote, totalmente pronto para instalação, inclui hardware e software básicos.

Conteúdo do pacote

O pacote vem de fábrica com:

Mainframe METAFORSA 3/3.plus 1 unidade
Fonte de alimentação MEANWELL DR-15-12 1 unidade
Sensor de movimento CW-MSD 3 pecas
Sensor de vazamento FW-WL.B 2 peças
Elemento sensível à temperatura FW-TS 4 PCS
Interruptor magnético de lâminas (sensor de posição de janela/porta) 4 PCS
Filtro de ruído do cabo Ethernet 1 unidade
Cabo de alimentação 1 unidade

Especificações técnicas básicas do Sistema

As especificações e características básicas do módulo METAFORSA 3/3.plus são mostradas na tabela 1

Tabela 1
Especificação Significado
Portas de saída
Número de canais comutados 10
Número de grupos comutados 10
Número de canais de regulação de intensidade 4
Tensão de comutação 0-250 V CA/CC
Carga máxima (um canal) 16A
Carga máxima (dispositivo) 160A
Carga máxima por canal de dimerização 0,5A (110W a 220V)
Tipo de dimmer MOSFET
Tipo de carga de dimmer R,C
Tipo de escurecimento borda de fuga
Tipo de conexão do cabo de alimentação conector
Seção permitida do cabo de alimentação para conectar no soquete:
cabo de condutor único
cabo de condutores múltiplos
cabo de condutores múltiplos com ponta

0,5 … 4mm2
0,5 … 4mm2
0,5…2,5 mm2
Portas de entrada
Número de entradas discretas 28
Classe máxima de corrente nos conectores de tensão de corrente contínua 5mA*
Outro
Temperatura ambiente de funcionamento 0 … +45°С
Temperatura de armazenamento/transporte -10… +50°С
Umidade admissível 0… 95% (sem condensação)
Fonte de alimentação 11,5 a 27,5 V CC
24 V, 0,75 A recomendado
Procura máxima 0,5А
Interfaces disponíveis Ethernet, PODE
Tipo de barramento CAN (4 fios)
CAN (4 fios) 800 m** (par trançado CAT5e)
Tipo de fio CAN FTP Cat 5E
Tipo de conexão CAN Conector
Comprimento máximo da linha digital 30 metros
Tipo fio de linha digital UTP/FTP Cat5E
Comprimento máximo da LAN 100 metros
Tipo de fio LAN UTP/FTP Cat5E
Tipo de conexão LAN Conector RJ-45
Quantidade de portas RS485 1***
Velocidade de transferência de dados 1200-115200 b/s***
Especificações dimensionais 9U, 156x90x58mm
Material da casca abdômen
Invólucro IP40
Tipo de instalação do equipamento Trilho DIN (EN 60715)
Peso 400g

* – Os canais de saída só devem ser conectados usando um amplificador que usa sinal PWM de 5V da saída IO como entrada

** – a instalação de unidades de fonte de alimentação adicionais é necessária para linhas longas; o comprimento máximo da linha pode ser reduzido por vários fatores de interferência

*** – Somente para Metaforsa 3.plus

Estrutura geral do Sistema

A visão geral do módulo é mostrada na fig. 1


Fig. 1 Visão geral do módulo


1 — conector para aplicação de carga
2 — conector para aplicação de lâmpadas dimmer
3 - conector de força
4 — Conector de rede Ethernet
5-6 — conectores para canais de entrada/saída universais
7 — conector para módulo de expansão.


Visão geral dos conectores externos do dispositivo METAFORSA: Na parte superior da caixa (fig. 1) existe:


  • conector (1) — Conexão de dispositivos;
  • conector (2) — Conexão de lâmpadas dimmer;


Na parte inferior da caixa (fig. 1) existe:


  • conector (3) — conexão de alimentação do módulo;
  • conector (4) — conexão de rede Ethernet;
  • conectores (5-6) — conexão universal de canais de entrada/saída – botões, interruptores reed, botões de LED, sensores de vazamento, sensores de movimento, sensores de temperatura, tiras de LED, tiras RGB de 3-4-5 canais, tiras WS2812B, dispositivos RS485 ( Apenas para Metaforsa 3.plus);
  • conector (7) — conexão do módulo de expansão.

A configuração física e atribuição dos pontos de contato de cada conector são mostradas na tabela 2.

Tabela 2
Conector Contato Atribuição
Out.png 1-10 Aplicação de carga (lâmpadas de luz, atuadores térmicos, etc.)
Dimm.png D1-4, L, N Load application (dimming lamps)
Indicadores de estado do dispositivo Os indicadores de status do módulo estão descritos na Tabela 3
24vconn.png +24V
GND
+24V — alimentação do módulo por uma fonte externa de 24 V GND — comum
Rj45.jpg RJ45 Conector para conectividade LAN
IOC CONN.png In1-14, In15-28 GND Conexão de dispositivos de controle (botões, botões LED, interruptores magnéticos de palheta, detectores de movimento, sensores de vazamento, sensores de temperatura, etc.):
In1 … In28 — entradas lógicas
GND — comum
Can.jpg VCC
GND
L
H
Conexão de módulos externos para barramento CAN
VСС — saída 24V para alimentação de dispositivos externos
GND — comum
L — barramento de dados CAN-L
H — barramento de dados CAN-H
Table3
Indicator Status Description
Power G.png Power
E.png Power not available
Activity Y.png Data communication
E.png Data communication not available
Error E.png No errors
R.png Communication error
R.pngR.png Module overheat
R.pngR.pngR.png Dimmer outputs module overload
R.pngR.pngR.pngR.png Absence of power on dimmers, if in configuration

Instalação e montagem do sistema

Antes de conectar o sistema, você deve:


  • localize o sensor e os atuadores (se não estiverem pré-instalados), configure os sensores e atuadores;
  • localize o módulo e a fonte de alimentação.


Nota: O módulo deve ser instalado próximo à fonte de tensão da fonte de alimentação.


CUIDADO! A tensão de alimentação CA deve ser fornecida à entrada do sistema através do conjunto do disjuntor. Deve ser instalado próximo à fonte de alimentação.
  1. A potência do conjunto do disjuntor deve estar de acordo com a capacidade de carga;
  2. Nada além dos condutores de fase pode ser conectado ao módulo, o fio neutro é conectado separadamente.


O diagrama típico de conexão do módulo METAFORSA 3/3.plus é mostrado na fig. 3.

Fig. 3


Conexão dos atuadores

Conexão das luzes/contator elétrico/atuador térmico de aquecimento

lamp
Fig. 4
Atuadores como luz, contator elétrico, atuador térmico de aquecimento devem ser ligados em qualquer uma das saídas 1 – 10, o fio neutro e o fio terra devem ser conectados diretamente ao quadro de distribuição. O exemplo de conexão é mostrado na Fig.4.


Conexão do dispositivo de alta carga

Contactor Contatores recomendados:
  • Série ABB ESB
  • Série Schneider Acti 9 iCT
  • Série Hager ESC.


Conexão da válvula unipolar de abastecimento de água/gás

Cuidado: Antes de alimentar a carga, certifique-se de que a configuração de saída do módulo METAFORSA esteja correta. A configuração incorreta ou conexão incorreta pode causar falha do módulo e/ou falha dos equipamentos a ele conectados, e até mesmo incêndio.
valve
Fig. 5
A válvula unipolar de abastecimento de água/gás é conectada a qualquer uma das saídas de 1 – 10, o (fio neutro e o fio terra são conectados diretamente ao quadro. O exemplo de conexão é mostrado na Fig.5.


Connection of double-pole water/gas supply valve

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
valve
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Connection of single-pole gate actuator

Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.

1pgate
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

2pgate
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

Pjalousie
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

ljalousie
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors/leakage sensors

The motion sensors/leakage sensors should be connected to any free input in1-in28; in these conditions their power is connected to the contact points of +5V and GND of the relevant group. The example of connection is shown in Fig.11.

IOC CONN LM.png
Fig. 11 connection of motion sensors/leakage sensors


Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 12-13.

Buttons MF3.png

Fig. 12 connection of buttons/switching units
Reed-sv MF3.png

Fig. 13 connection of the magnetic reed switches (window/door position sensors)

Connection of temperature sensors

Temperature sensors are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 14.

IOC CONN T.png

Fig. 14 connection of temperature sensors

RGB connection scheme

CAUTION! Output channels should only be connected using amplifier which uses 5V PWM signal from IO output as input

IOC RGB EX.png

Fig. 15 RGB connection

WS2812B connection scheme

IOC CONN WS.png

Fig. 16 WS2812B connection

RS485 connection scheme

CAUTION! RS485 connection is only available for Metaforsa 3.plus and only occurs on 21 channel

MF3plus rs485.png

Fig. 17 RS485 connection

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 18.

CAN MF3.png
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

io char[28] 98 io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • '0' - led-dimmer
  • '1' - halogen-dimmer
  • '2' - linear-dimmer
  • '3'..'6' - RGB-3..6 channels
  • 'z' - WS2812B -string
  • 'e' - led-button inverse
  • 'd' - led-button
  • 'c' - button inverse
  • 'b' - button
  • 's' - switch
  • 'k' - contact inverse
  • 'h' - contact
  • 'l' - leak
  • 'n' - Neptun
  • 'v' - motion inverse
  • 'm' - motion
  • 'r' - thermo-resistor
  • 't' - DALLAS
  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK'

hw string 98 - hw="...", where
  • pwm_invert – PWM inverting [1, 0];
  • lbn_bright – brightness of led buttons, range (0 - 255);
  • f – by default PWM frequency is 1000, range (1 - 5000).

Example:

1hw="io='4---zdd----t--' pwm_invert=1 lbn_bright=255 f=1000"
Only for Metaforsa 3.plus
cfg string 98 9600/8N1 cfg='SPEED/BPS', where
  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"
[Protocol] string 98 Protocol setting is described by protocol parameter. The following

protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"
echo on; off 98 'off' For settings check out and testing echo parameter can be used. Module

echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"
 1		<item addr="349:1" auto-period="600" cfgid="197" name="Lamp 1" type="lamp"/>
 2		<item addr="349:2" auto-period="600" cfgid="197" name="Lamp 2" type="lamp"/>
 3		<item addr="349:3" auto-period="600" cfgid="197" name="Lamp 3" type="lamp"/>
 4		<item addr="349:4" auto-period="600" cfgid="197" name="Lamp 4" type="lamp"/>
 5		<item addr="349:5" auto-period="600" cfgid="197" name="Lamp 5" type="lamp"/>
 6		<item addr="349:6" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
 7			<automation name="Eco" temperature-level="16"/>
 8			<automation name="Comfort" temperature-level="22"/>
 9			<automation name="Hot" temperature-level="25"/>
10		</item>
11		<item addr="349:7" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
12			<automation name="Eco" temperature-level="16"/>
13			<automation name="Comfort" temperature-level="22"/>
14			<automation name="Hot" temperature-level="25"/>
15		</item>
16		<item addr="349:8" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
17			<automation name="Eco" temperature-level="16"/>
18			<automation name="Comfort" temperature-level="22"/>
19			<automation name="Hot" temperature-level="25"/>
20		</item>
21		<item addr="349:9" cfgid="197" name="Jalousie" sub-type="120" type="jalousie"/>
22		<item addr="349:11" auto-period="600" cfgid="197" name="Dimmer 1" type="dimmer-lamp"/>
23		<item addr="349:12" auto-period="600" cfgid="197" name="Dimmer 2" type="dimmer-lamp"/>
24		<item addr="349:13" auto-period="600" cfgid="197" name="Dimmer 3" type="dimmer-lamp"/>
25		<item addr="349:14" auto-period="600" cfgid="197" name="Dimmer 4" type="dimmer-lamp"/>
26		<item addr="349:16" cfgid="197" name="Door 1" type="door-sensor"/>
27		<item addr="349:17" cfgid="197" name="Door 2" type="door-sensor"/>
28		<item addr="349:18" cfgid="197" name="Door 3" type="door-sensor"/>
29		<item addr="349:19" cfgid="197" name="Door 4" type="door-sensor"/>
30		<item addr="349:20" cfgid="197" name="Door 5" type="door-sensor"/>
31		<item addr="349:21" cfgid="197" name="Door 6" type="door-sensor"/>
32		<item addr="349:22" cfgid="197" name="Door 7" type="door-sensor"/>
33		<item addr="349:23" cfgid="197" name="Door 8" type="door-sensor"/>
34		<item addr="349:24" cfgid="197" name="Door 9" type="door-sensor"/>
35		<item addr="349:25" cfgid="197" name="Door 10" type="door-sensor"/>
36		<item addr="349:26" cfgid="197" name="Door 11" type="door-sensor"/>
37		<item addr="349:27" cfgid="197" name="Door 12" type="door-sensor"/>
38		<item addr="349:28" cfgid="197" name="Door 13" type="door-sensor"/>
39		<item addr="349:29" cfgid="197" name="Door 14" type="door-sensor"/>
40		<item addr="349:30" cfgid="197" name="Door 15" type="door-sensor"/>
41		<item addr="349:31" cfgid="197" name="Door 16" type="door-sensor"/>
42		<item addr="349:32" cfgid="197" name="Door 17" type="door-sensor"/>
43		<item addr="349:33" cfgid="197" name="Door 18" type="door-sensor"/>
44		<item addr="349:34" cfgid="197" name="Door 19" type="door-sensor"/>
45		<item addr="349:35" cfgid="197" name="Door 20" type="door-sensor"/>
46		<item addr="349:36" cfgid="197" name="Door 21" type="door-sensor"/>
47		<item addr="349:37" cfgid="197" name="Door 22" type="door-sensor"/>
48		<item addr="349:38" cfgid="197" name="Door 23" type="door-sensor"/>
49		<item addr="349:39" cfgid="197" name="Door 24" type="door-sensor"/>
50		<item addr="349:40" cfgid="197" name="Door 24" type="door-sensor"/>
51		<item addr="349:41" cfgid="197" name="Door 25" type="door-sensor"/>
52		<item addr="349:43" cfgid="197" name="IR receiver" type="ir-receiver"/>
53		<item addr="349:44" cfgid="197" name="RS485" type="com-port"/>
54		<item addr="349:90" cfgid="197" name="Current" system="yes" type="current-sensor"/>
55		<item addr="349:95" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
56		<item addr="349:96" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
57		<item addr="349:97" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
58		<item addr="349:98" cfgid="197" hw="out='LLLLLHHHB-' dm='LLLL' io='KKKKKKKKKKKKKKKKKKKKUKKKKKK-'" logic-ver="19" name="Temperature" sn="2533726919" system="yes" type="temperature-sensor"/>
59		<item addr="349:100" cfgid="197" name="RS232" type="com-port"/>