Example: in='MMMMMMMMMMMMLLLLLLLLLLLL'
 
Example: in='MMMMMMMMMMMMLLLLLLLLLLLL'
 
12 motion sensors and 12 leak-sensors;
 
12 motion sensors and 12 leak-sensors;
in='BBBBBBBBSSSSSSRRRRSSRRRR'
+
in='BBBBBBBBSSSSSSBBBBSSSSSS'
8 buttons; 8 switches and 8 LED channels.
+
12 buttons; 12 switches.
 
|}
 
|}

Latest revision as of 14:50, 8 February 2024

Information about message (contribute)
This message has no documentation. If you know where or how this message is used, you can help other translators by adding documentation to this message.
Message definition (Metaforsa2 MF-14)
==HW Settings==
{| class="wikitable"
|-
!Name!!Type, range!!SUBID!!Default!!Description
|-
|runtime||integer 0-100 || 1-10 || 15 ||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); 
<br>Example: runtime=15
|-
|runtimeopen||integer 0-60000||Blinds subId || ||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
|-
|runtimeclose||integer 0-60000||Blinds subId|| ||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
|-
|hold||integer 0-10000||1-10||500||hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
|-
|def||string 'ON'||1-10||'OFF'||def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
|-
|stop||Char ‘R’||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
|-
|out||char[10]||98||'LLLLHHHHP-'||Each char is responsible for the type of a particular channel
*'L'-Lamp;
*'M'-Lamp Inverse;
*'J'-Heating NO, valve-heating, normally open;
*'H'-Heating NC, valve-heating, normally closed;
*'B'-Blinds (2 pole), jalousie/curtains;
*'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
*'G'-Gate (2 pole), 2 pole gate;
*'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
*'X'-Gate (1 pole /short press), 1 pole gate;
*'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
*'V'-Valve (2 pole), 2 pole valve;
*'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
*'R'-Valve (1 pole), 1 pole valve,;
*'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
*'K'-Lock (short press);
*'N'-Lock (short press) Inverse;
*'P'-Blinds (2 pole);
*'O'-Blinds Inverse (2 pole), invert open-close;
*'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
*'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
*'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
*'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
*'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
*'-'-none, nothing is connected.
Example: out='LLB-G-V-W-'
|-
|dm||char[4]||98||‘LLLL’||Each char is responsible for the type of a particular channel
*‘g’ – use like halogen dimer-lamp
*‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
*‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
*‘l’ – LED Function, dimmable LED lamps
*‘v’ – linear Function of dimming
*‘-‘ – Channel disabled
*‘+’ – Regular channel
Example: dm=’skl-‘
|-
|def||integer 0-250||11-14||100||The default brightness level in case of a power reset (1..250). Example: def=250
|-
|min||integer 0-100||11-14||0||Minimum dimming level, example: min=10
|-
|max||integer 0-100||11-14||100||Maximum dimming level, example max=95
|-
|start||integer 0-100||11-14||0||The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
|-
|force||integer 0-100||11-14||10||Time duration of the starting value (measured in milliseconds). Example: force=20
|-
|runtime||integer 0-60000||11-14||1000||Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
|-
|offset||integer (+/- 0…39)||39-46||'0'||sensor values offset; For example, offset is -3.8 :
Example: hw="offset='-3.8'"
|-
|in||char[24]||98||'BBBBBBBBBBBBMMMLLLKKKKKK'||Each char is responsible for the type of a particular channel
*'B'-Button;
*'C'-nButton;
*'S'-Switch;
*'K'-Contact;
*'H'-nContact;
*‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
*‘N’-Third party leakage sensor;
*'M'-Motion, ​motion sensor;
*'V'-nMotion, motion sensor;
*'-'-none
Example: in='MMMMMMMMMMMMLLLLLLLLLLLL'
12 motion sensors and 12 leak-sensors;
in='BBBBBBBBSSSSSSBBBBSSSSSS'
12 buttons; 12 switches.
|}
Translation==HW Settings==
{| class="wikitable"
|-
!Name!!Type, range!!SUBID!!Default!!Description
|-
|runtime||integer 0-100 || 1-10 || 15 ||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); 
<br>Example: runtime=15
|-
|runtimeopen||integer 0-60000||Blinds subId || ||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
|-
|runtimeclose||integer 0-60000||Blinds subId|| ||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
|-
|hold||integer 0-10000||1-10||500||hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
|-
|def||string 'ON'||1-10||'OFF'||def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
|-
|stop||Char ‘R’||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
|-
|out||char[10]||98||'LLLLHHHHP-'||Each char is responsible for the type of a particular channel
*'L'-Lamp;
*'M'-Lamp Inverse;
*'J'-Heating NO, valve-heating, normally open;
*'H'-Heating NC, valve-heating, normally closed;
*'B'-Blinds (2 pole), jalousie/curtains;
*'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
*'G'-Gate (2 pole), 2 pole gate;
*'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
*'X'-Gate (1 pole /short press), 1 pole gate;
*'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
*'V'-Valve (2 pole), 2 pole valve;
*'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
*'R'-Valve (1 pole), 1 pole valve,;
*'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
*'K'-Lock (short press);
*'N'-Lock (short press) Inverse;
*'P'-Blinds (2 pole);
*'O'-Blinds Inverse (2 pole), invert open-close;
*'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
*'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
*'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
*'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
*'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
*'-'-none, nothing is connected.
Example: out='LLB-G-V-W-'
|-
|dm||char[4]||98||‘LLLL’||Each char is responsible for the type of a particular channel
*‘g’ – use like halogen dimer-lamp
*‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
*‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
*‘l’ – LED Function, dimmable LED lamps
*‘v’ – linear Function of dimming
*‘-‘ – Channel disabled
*‘+’ – Regular channel
Example: dm=’skl-‘
|-
|def||integer 0-250||11-14||100||The default brightness level in case of a power reset (1..250). Example: def=250
|-
|min||integer 0-100||11-14||0||Minimum dimming level, example: min=10
|-
|max||integer 0-100||11-14||100||Maximum dimming level, example max=95
|-
|start||integer 0-100||11-14||0||The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
|-
|force||integer 0-100||11-14||10||Time duration of the starting value (measured in milliseconds). Example: force=20
|-
|runtime||integer 0-60000||11-14||1000||Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
|-
|offset||integer (+/- 0…39)||39-46||'0'||sensor values offset; For example, offset is -3.8 :
Example: hw="offset='-3.8'"
|-
|in||char[24]||98||'BBBBBBBBBBBBMMMLLLKKKKKK'||Each char is responsible for the type of a particular channel
*'B'-Button;
*'C'-nButton;
*'S'-Switch;
*'K'-Contact;
*'H'-nContact;
*‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
*‘N’-Third party leakage sensor;
*'M'-Motion, ​motion sensor;
*'V'-nMotion, motion sensor;
*'-'-none
Example: in='MMMMMMMMMMMMLLLLLLLLLLLL'
12 motion sensors and 12 leak-sensors;
in='BBBBBBBBSSSSSSBBBBSSSSSS'
12 buttons; 12 switches.
|}

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSBBBBSSSSSS' 12 buttons; 12 switches.