Difference between revisions of "AC"
Jump to navigation
Jump to search
(Created page with "===Example of description in XML=== <syntaxhighlight lang="xml" line> <item type="AC" name="AC" addr="123:4"/> </syntaxhighlight> ===Additional parameters=== {|class="wikit...") |
|||
Line 17: | Line 17: | ||
|t-min||number||temperature low value||16 | |t-min||number||temperature low value||16 | ||
|- | |- | ||
− | |t-delta||number||temperature | + | |t-delta||number||temperature range||16 |
|- | |- | ||
|modes||bit mask||Mask of operation modes (fan, cool, dry, heat, auto)||0x1F | |modes||bit mask||Mask of operation modes (fan, cool, dry, heat, auto)||0x1F |
Revision as of 15:26, 19 August 2021
Example of description in XML
1<item type="AC" name="AC" addr="123:4"/>
Additional parameters
Name | type and variety | description | default value |
---|---|---|---|
path* | string | Path to script | - |
script-id | string | script id from the description for interface | - |
t-min | number | temperature low value | 16 |
t-delta | number | temperature range | 16 |
modes | bit mask | Mask of operation modes (fan, cool, dry, heat, auto) | 0x1F |
fans | bit mask | Mask of airflow mode (auto, 1, 2, 3, 4, 5, silent mode) | 0x1F |
vane-ver | bit mask | Mask of vertical fins mode (auto, top, top-center, center, center-bottom, bottom, swing) | 0x7E |
vane-hor | bit mask | Mask of horizontal fins mode (left, left-center, center, center-right, right, sides (low angle), sides (high angle), from sides to center) | 0 |
temperature-sensors | list | list of valve temperature sensors | - |
t-outside | addr | addr of outside temperature sensors | - |
t-outside-treshold | value | critically low temperature treshold | - |
t-outside-hyst | value | critically low temperature hysteresis | - |
* – required fields
Device status upon status request (8 bytes)
!Byte number | Bit number | Description |
---|---|---|
0 | 0 3 4-7 |
On/Off Autostate Mode: 0 – fan 1 – cool 2 – dry 3 – heat 4 – auto |
1-2 | 8-23 | Temperature setpoint |
3 | 24-27 28-31 |
Horizontal vanes: 0 – left 1 – left-center 2 – center 3 – center-right 4 – right 5 – sides (low angle) 6 – sides (high angle) 7 – from sides to center Vertical vanes: 0 – auto 1 – top 2 – top-center 3 – center 4 – center-bottom 5 – bottom 6 – swing |
4 | 32-35 | Fan: 0 – auto 1 – 1st speed 2 – 2nd speed 3 – 3rd speed 4 – 4th speed 5 – 5th speed 6 – silent mode |
5-6 | 40-55 | Current temperature |
7 | 56-63 | Flags |
8 | 64-71 | Errors |
Possible variants of setting the status
1-byte
Byte | Description |
---|---|
0 | 0 – off 1 – on 0xFF – Change the status for the opposite one |
2-bytes
Byte | Description |
---|---|
0 | 0xf |
1 | 1 – Target +1 17 – Mode +1 cyclic 33 – Fan +1 cyclic 49 – Horizontal vanes +1 cyclic 65 – Vertical vanes +1 cyclic |
3-bytes
Byte | Description |
---|---|
0 | 0xf |
1 | 16 – Mode (value) 18 – Mode (step) 32 – Fan (value) 34 – Fan (step) 48 – Horizontal vanes (value) 50 – Horizontal vanes (step) 64 – Vertical vanes (value) 66 – Vertical vanes (step) |
2 | value – select value (for example status {0xf0, 32, 2} set fan 2) step – set step (cyclic) (for example status {0xf0, 34, 2} set fan +2; status {0xf0, 34, -1} set fan -1) |
4-bytes
Byte | Description |
---|---|
0 | 0xf |
1 | 0 – Target (value) 2 – Target (step) |
2 | fractional part of temperature (0-255) |
3 | integer part of temperature |