All translations
Enter a message name below to show all available translations.
Found 2 translations.
Name | Current message text |
---|---|
h English (en) | {|class="wikitable |- !Byte number!!Bit number!!Description |- |0||0<br>1<br>2<br>3<br>4-7||On/Off<br>Cooling/Heating<br>Fan On/Off<br>Boost On/Off<br>Integration algorithm (slow,medium,fast,boost) |- |1-2||8-23||T set (<-100 - no automation) |- |3-4||24-39||T cur (<-100 - no automation or undefined all T sensors) |- |5||40-43<br>44-47||Current automation time interval index<br>Current automation index |- |6||48-55||Current fan level (0-250) |- |7||56<br>57<br>58<br>59<br>60<br>61<br>62<br>63||Error: Has undefined T sensor(s)<br>Error: Has no any defined T sensor<br>Error: valve state is undefined<br>Error: reverse valve is on<br>Error: heat transfer sensor is undefined or has bad level<br>Error: low power for accessing setpoint<br>Error: fan state is undef<br>Reserved |} |
h русский (ru) | {|class="wikitable |- !Номер байта!!Номер бита!!Описание |- |0||0<br>1<br>2<br>3<br>4-7||Вкл./Выкл.<br>Охлаждение/Нагрев<br>Вентилятор Вкл./Выкл.<br>Ускорение Вкл./Выкл.<br > Алгоритм интеграции (медленный, средний, быстрый, ускоренный) |- |1-2||8-23||T установленная (<-100 - без автоматизации) |- |3-4||24-39||T текущая (<-100 - нет автоматизации или не определены все датчики T) |- |5||40-43<br>44-47||Текущий индекс временного интервала автоматизации<br>Текущий индекс автоматизации |- |6||48-55||Текущий уровень вентилятора (0-250) |- |7||56<br>57<br>58<br>59<br>60<br>61<br>62<br>63||Ошибка: есть неопределенные датчики T<br>Ошибка: нет определенного датчика T<br>Ошибка: состояние клапана не определено<br>Ошибка: обратный клапан включен<br>Ошибка: датчик теплопередачи не определен или имеет низкий уровень<br>Ошибка: низкая мощность для доступа к заданному значению<br> Ошибка: состояние вентилятора не определено<br>Зарезервировано |} |