FW-WL.B | |||||||
---|---|---|---|---|---|---|---|
|
WALL LEAKAGE SENSOR
The sensor is placed on the wall. Used together with DW-WL02 or BW-LSA modules.
Features
- Sensor presence detection
- Adjusting the sensor sensitivity
- Connections of several sensors to one bus
Example of connection
Module parameters
Parameter name | Value |
---|---|
Power supply | 9-12 V DC |
Max current(24V) | 20 mA |
Compatible with | Metaforsa devices DW-WL02/HTxx BW-LSA |
Equipment installation type | Free |
Case material | ABS |
Protection | IP64 |
Temperature range | -10 … +50 °C |
Size | 57x47x22 mm |
Weight | 35g |
HW settings
Name | Type, range | SUBID | Default | Description |
---|---|---|---|---|
c0 | int[4] | sensors subId | 0;0;255;15 | Normal state color in format 'red;green;blue;blink'
red, green, blue – 0..255; blink:
Example: 1c0='150;150;255;0'
|
c1 | int[4] | sensors subId | 0;0;255;15 | On-start color in format 'red;green;blue;blink'
red, green, blue – 0..255; blink:
Example: 1c1='150;150;255;0'
|
c2 | int[4] | sensors subId | 255;100;0;15 | 'Leak was previously reported' color in format 'red;green;blue;blink'
red, green, blue – 0..255; blink:
Example: 1c2='150;150;255;0'
|
c3 | int[4] | sensors subId | 255;0;0;15 | On-leak color in format 'red;green;blue;blink'
red, green, blue – 0..255; blink:
Example: 1c3='150;150;255;0'
|
sens | int | sensors subId | 128 | Sensor sensitivity
Example: 1sens='180'
|
test | int(0,1) | sensors subId | 1 | 0 - Disable the test signal to detect the presence of the sensor |
- Removing HW does not return the above parameters to their default values.To return to their default values, they must be set explicitly.
- Green and blue cannot be used at the same time. Green has priority.