  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' |- |colspan="3"|Only for Metaforsa 3.plus |- |cfg||string||98||9600/8N1||cfg='SPEED/BPS', where

  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"

|- |[Protocol]||string||98||—||Protocol setting is described by protocol parameter. The following protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"

|- |echo||on; off||98||'off'||For settings check out and testing echo parameter can be used. Module echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"

|}