Metaforsa2 MFC-14

Revision as of 11:14, 3 January 2022 by Rusanov (talk | contribs) (Created page with "{{ConExC |Внимание! Перед подачей питания на модуль необходимо правильно настроить выходы в прилож...")
Other languages:
English • ‎русский
MFC-14
Metaforsa2-Cloud.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs24
Number of digital inputs4
General
Max CAN devices50
Max CAN bus length800 m (twisted pair 5 cat)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


Введение

Руководство по установке модуля METAFORSA SMART HOUSE описывает порядок его установки, сборки, эксплуатации и настройки. При работе с системой необходимо строго соблюдать все требования, изложенные в данном руководстве. Несоблюдение этих требований может привести к повреждению устройства, его выходу из строя, поражению электрическим током, возгоранию и другим последствиям. Производитель оставляет за собой право вносить изменения в данное руководство без предварительного уведомления. Это руководство является неотъемлемой частью системы и должно храниться у конечного потребителя.

Функции

  • 10 универсальных выходов обеспечивают управление:
    • Освещением
    • Клапанами отопления NC/NO
    • Жалюзи
    • 1- или 2-х полюсными воротами
    • 1- или 2-х полюсными клапанами
    • Замками NC/NO
    • Фанкойлами
  • 4-мя выходами диммирования
  • 8-ю выходами PWM
  • 24 отдельных входа обеспечивают управление:
    • Кнопками
    • Выключателями
    • герконами
    • датчиками утечек
    • детекторами движения
  • 4 цифровых входа для 8 датчиков температуры
  • Порт расширения
  • Реле с контактами AgSnO2, рассчитаны на пиковую нагрузку 80 А, 20 мсек.
  • Облачное подключение и управление всеми системами дома
  • Голосовое управление (Siri, Alexa, Google Home)

Требования безопасности

ВНИМАНИЕ! Все работы, связанные с установкой, подключением, настройкой, обслуживанием и поддержкой, должны выполняться квалифицированным персоналом, имеющим достаточные навыки и опыт работы с электрооборудованием.

Во избежание риска возгорания, поражения электрическим током, повреждения системы и/или травм, установка и сборка системы должны выполняться в соответствии с инструкциями, перечисленными ниже:


  • все работы по подключению должны производиться на обесточенном оборудовании;
  • необходимо использовать соответствующие инструменты и средства индивидуальной защиты от поражения электрическим током;
  • запрещается использовать поврежденные кабели, провода и разъемы;
  • избегайте перегиба проводов и кабелей;
  • не пережимайте и не перегибайте кабели и провода, прилагая чрезмерные усилия. В противном случае внутренние проводники кабеля и проводов могут быть оголены или повреждены;
  • не используйте для подключения разъемы с плохими контактами;
  • не превышайте предельные параметры нагрузки, указанные в данном руководстве;
  • сечение питающих проводов зависит от требований к пределу плотности тока, типу изоляции и материалу проводов. Недостаточное сечение может привести к перегреву кабеля и возгоранию.


При работе с системой после подачи напряжения НИКОГДА:

  • не производите подключение/отключение разъемов;
  • не открывайте модули и датчики.

Конфигурация и назначение системы

Назначение системы

METAFORSA SMART HOUSE - это готовое решение для автоматизации жилых и коммерческих помещений, гостиничных комплексов, которое включает в себя самые востребованные функции Умного дома.


Устройство имеет 10 каналов управления, 4 канала диммирования, 24 входных канала для датчиков и порт для подключения цифровых датчиков.


Универсальные выходы могут использоваться для управления: Универсальные входы позволяют подключать:
Освещение Кнопки/коммутационные блоки
Коннекторы розеток Магнитные герконы
Пол с подогревом Магнитные герконы
Приводы для штор/ворот Датчики утечек
Клапаны водоснабжения/отопления


Порт подключения цифровых датчиков


Порт подключения цифровых датчиков позволяет подключать различные цифровые датчики, такие как датчики температуры, окружающего освещения, влажности и другие.


Порт расширения


Порт расширения позволяет модернизировать систему, подключая дополнительное оборудование, такое как модуль управления светодиодным освещением, диммированием, измерительными приборами и другими элементами. Комплект, полностью готовый к установке, включает в себя базовое оборудование и программное обеспечение.

Комплектация

В стандартную комплектацию входят:

Основной модуль METAFORSA MFC-14.А 1 шт
Блок питания MEANWELL DR-15-12 1 шт
Датчик движения CW-MSD 3 шт
Датчик протечек FW-WL.A 2 шт
Термочувствительный элемент FW-TS.A 4 шт
Магнитный геркон (датчик положения окна/двери) 4 шт
Фильтр подавления помех для Ethernet-кабеля 1 шт
Шнур питания 1 шт
Руководство по эксплуатации 1 шт

Основные технические характеристики системы

Таблица 1
Название параметра Значение
Выходные порты
Количество релейных каналов 10
Количество каналов диммирования 4
Напряжение коммутации 0-250 В переменного/постоянного тока
Пиковая нагрузка (на один канал) 16 А
Пиковая нагрузка (на устройство) 160 А
Максимальная нагрузка на канал диммирования 0,5 А (110 Вт при 220 В)
Максимальная нагрузка на выходы PWM 50 мА
Тип диммера МОП-транзистор
Тип диммирования задний фронт импульса
Тип подключения кабеля питания коннектор
Допустимое сечение кабеля питания для подключения в разъем:
одножильный кабель
многожильный кабель
многожильный кабель с

наконечником||
0,5 … 4 мм2
0,5 … 4 мм2
0,5 … 2.5 мм2

Входные порты
Количество отдельных входов 24
Количество цифровых входов 4
Максимальный ток на разъемах постоянного напряжения 50 мА
Другие параметры
Рабочая температура окружающей среды 0 … +45°С
Температура хранения/транспортировки -20 … +60°С
Допустимая влажность 0 … 95% (без конденсации)
Напряжение питания 11,5… 27,5 В постоянного тока
Максимальная нагрузка 1 А
Доступные интерфейсы Ethernet, CAN, OneWire
Тип шины CAN (4-х проводная)
CAN (4-х проводная) 800 м* (витая пара 5 кат)
Тип провода шины CAN FTP Cat 5E
Тип подключения шины CAN коннектор
Максимальная длина цифровой линии 30 м
Тип провода цифровой линии UTP/FTP Cat 5E
Тип подключения цифровой линии Коннектор RJ-12
Максимальная длина LAN 100 м
Тип провода LAN UTP/FTP Cat 5E
Тип подключения LAN Коннектор RJ-45
Габаритные характеристики 9U, 156x110x58 мм
Материал корпуса АБС-пластик
Класс защиты IP40
Тип установки оборудования DIN-рейка (EN 60715)
Масса 300 г

* - на протяженных линиях требуется установка дополнительных блоков питания; максимальная длина линии может быть уменьшена из-за различных факторов помех

Общая структура системы

Общий вид модуля представлен на рис. 1 


 


1 — разъем для подключения нагрузки и питания
2 — разъем для подключения диммирующего освещения
3 — разъем питания
4 — разъем для подключения сети Ethernet
5-6 — разъемы для цифровых датчиков и кнопок/коммутационных устройств
7 — разъем интерфейса OneWire (для цифровых датчиков)
8 — разъем для модуля расширения.


Общая схема внешних разъемов устройства METAFORSA В верхней части корпуса (рис. 1) расположены:


  • разъем (1) - подключение устройств;
  • разъем (2) - подключение диммирующего освещения;


В нижней части корпуса (рис. 1) расположены:


  • разъем (3) - подключение питания модуля;
  • разъем (4) - подключение к сети Ethernet;
  • разъемы (5-6) - четыре шестиконтактных разъема для подключения цифровых датчиков - датчиков движения, протечек, геркона и *датчиков кнопок/коммутационного блока;
  • разъем (7) - подключение цифровых датчиков шины OneWire;
  • разъем (8) - подключение модуля расширения.

Конфигурация и назначение контактов каждого разъема показаны в Таблице 2.


Table2
Разъем Контакт Назначение
  1-10 Подключение нагрузки (лампы освещения, термоприводы и т. д.)
  D1-4, L, N Подключение нагрузки (освещение с диммированием)
Индикаторы состояния устройства Индикаторы состояния модуля описаны в Таблице 3
  +24V
GND
+24V — - питание модуля от внешнего источника питания 24 В GND - общий
  RJ45 Разъем для подключения к сети LAN
  In1-12, In13-24 GND Подключение управляющих устройств (кнопки, герконы, датчики движения или утечки): +12V — выход питания датчика +12 В
In1 … In24 — логические входы (0-12 В)
GND — общий common
  OneWire Подключение цифровых датчиков (температуры)
VCC — выход питания датчиков + 5 В
OW1-OW4 — шины данных OneWire
GND — общий
  VCC
GND
L
H
Подключение внешних модулей к шине CAN
VСС — выход 12 В для питания внешних устройств
GND — общий
L — шина данных CAN-L
H — шина данных CAN-H
Table3
Indicator Status Description
Bootloader mode
 
  bootloader
 
     Reset button is pressed
     Clearing flash memory
     Network configuration
     Downloading firmware
     Flashing firmware
  Firmware download error
Firmware mode
 
     Network configuration
     Identification
  Operational mode
  IR command received
 

Error
  Lost connection to server
   Overheat
    Dimming channels overload
     No AC power
      RTC error
 

Activity
  CAN activity
  OW activity
  RS-485 activity
  Ethernet activity

Установка и сборка системы

Перед подключением системы необходимо:


  • определить места установки датчиков и реле (если они не были предварительно установлены), установить датчики и реле;
  • определить места установки модуля и блока питания.


Примечание: модуль необходимо устанавливать рядом с источником питания.


ВНИМАНИЕ! Напряжение переменного тока должно подаваться на вход системы через автоматический выключатель (предохранитель). Он должен быть установлен рядом с источником питания.
  1. Мощность предохранителя должна соответствовать допустимой нагрузке;
  2. К модулю нельзя подключать ничего, кроме фазных проводов, нейтральный провод подключается отдельно.


Типовая схема подключения модуля METAFORSA MFC-14.A показана на рис. 3

 


Подключение реле

Подключение освещения/электрического контактора/термореле отопления

 
Fig. 4
Такие реле, как освещение, электрический контактор, термореле отопления должны быть подключены к любому из выходов 1-10, а нейтральный провод и заземление должны быть подключены непосредственно к распределительному щиту. Пример подключения показан на рис. 4.


Подключение устройства с высокой нагрузкой

  Рекомендуемые контакторы:
  • ABB серии ESB
  • Schneider Acti 9 серии iCT
  • Hager серии ESC.


Подключение однополюсного клапана подачи воды/газа

Внимание: перед подачей питания на нагружаемые элементы системы убедитесь в правильности конфигурации выходов модуля METAFORSA. Неправильная конфигурация или неправильное подключение могут привести к отказу модуля и/или выходу из строя подключенного к нему оборудования, и даже к возгоранию.
 
Fig. 5
Однополюсный клапан подачи воды/газа подключается к любому из выходов 1–10, нейтральный провод и заземление подключаются непосредственно к распределительному щиту. Пример подключения показан на рис. 5.


Подключение двухполюсного клапана подачи воды/газа

Внимание: перед подачей питания на клапан необходимо убедиться в правильности конфигурации выходов модуля METAFORSA. Неправильная конфигурация может вызвать подачу напряжения одновременно на оба канала клапана, что может привести к отказу модуля и/или к выходу из строя подключенного к нему оборудования, и даже к возгоранию.
 
Fig. 6
Для подключения двухполюсного клапана подачи воды/газа используются два смежных контакта (например, 3 и 4), а нейтральный провод и заземление подключаются непосредственно к распределительному щиту. Пример подключения показан на рис. 6.


Подключение однополюсного привода ворот

Внимание: перед подачей питания на модуль необходимо правильно настроить доступ к контактам в приложении. Неправильно настроенные контакты могут привести к выходу модуля из строя и/или к отказу подключенного к нему оборудования, и даже к возгоранию.

 
Fig. 7
Для подключения однополюсных контроллеров приводов ворот используется любой контакт (например, 3). Пример подключения показан на рис. 7.


Подключение двухполюсного привода ворот

Внимание! Перед подачей питания на модуль необходимо правильно настроить выходы в приложении. Неправильно настроенные контакты могут привести к одновременной подаче питания на оба канала, что может привести к выходу модуля из строя и/или отказу подключенного к нему оборудования, и даже к возгоранию.

 
Fig. 8
Для подключения двухполюсного однополюсных контроллера привода ворот используются два смежных контакта (например, 3 и 4). Пример подключения показан на рис. 8.


Подключение реле штор/жалюзи/ставней с регулировкой усилия 220 В

Внимание! Перед подачей питания на модуль необходимо правильно настроить выходы в приложении. Неправильно настроенные контакты могут привести к одновременной подаче питания на оба канала, что может привести к выходу модуля из строя и/или отказу подключенного к нему оборудования, и даже к возгоранию.

 
Fig. 9
Для подключения реле штор/жалюзи/ставней используются два смежных контакта (например, 3 и 4), а нейтральный провод и заземление подключаются непосредственно к распределительному щиту. Пример подключения показан на рис. 9


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors

The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11.

 
Fig. 11


Connection of FW-WL.A leakage sensors

FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12.

 

Fig12
 

Fig13

Configuration and connection of the FW-WL.A sensor 1. Terminals:

+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.

2. Sensor preset switch (optionally):

1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).

3. LED status indicator.

Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in16, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-16.

 

Fig14 connection of buttons/switching units
 

Fig15 connection of the magnetic reed switches (window/door position sensors)


Connection of digital sensors

The OW adapter (Fig. 16a) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b). The connected sensors are detected automatically and do not require any original setting.

 

Fig16 a
 

Fig16 b

Configuration and connection of the OW adapter

Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Connection of RGB and LED.

MFC has new function – switching inputs to LED outputs (in15-in18; in21-in24).  

HW example for this configuration:

1hw="in='--------------RRRR--RRRR' rgb='RGBLLLLL'"


Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 17.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.


HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • 'R' (avaliable on in15-in18; in21-in24) LED outputs
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSRRRRSSRRRR' 8 buttons; 8 switches and 8 LED channels.

rgb char[8] 98 'RGBLRGBL' Each char is responsible for the type of a particular channel selected as 'R' in inputs
  • RGB – rgb lamp (avaliable only on in15-in17; in21-in23)
  • L – dimmer-lamp (avaliable only on in15-in18; in21-in24)

Example: hw="in='BBBBBBBBSSSSSSRRRRSSRRRR' rgb='RGBLLLLL'"

 1<item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> 
 2<item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> 
 3    <automation name="Eco" temperature-level="16" uniq_id="3781"/> 
 4    <automation name="Comfort" temperature-level="22" uniq_id="3782"/> 
 5    <automation name="Hot" temperature-level="25" uniq_id="3783"/> 
 6</item> 
 7<item addr="339:3" cfgid="40" hw="runtime=9" name="Jalousie" sub-type="120" type="jalousie" uniq_id="32"/> 
 8<item addr="339:5" cfgid="40" hw="runtime=13" name="Gate" sub-type="120" type="gate" uniq_id="3784"/> 
 9<item addr="339:7" cfgid="40" hw="hold=4600" name="Gate" sub-type="120" type="gate" uniq_id="3785"/> 
10<item addr="339:8" cfgid="40" hw="runtime=10" name="Valve" type="valve" uniq_id="3786"/> 
11<item addr="339:11" cfgid="40" name="Motion" type="motion-sensor" uniq_id="17"/> 
12<item addr="339:12" cfgid="40" name="Motion" type="motion-sensor" uniq_id="18"/> 
13<item addr="339:13" cfgid="40" name="Motion" type="motion-sensor" uniq_id="19"/> 
14<item addr="339:16" cfgid="40" name="Leak" type="leak-sensor" uniq_id="21"/> 
15<item addr="339:17" cfgid="40" name="Leak" type="leak-sensor" uniq_id="41"/> 
16<item addr="339:19" cfgid="40" name="Switch" type="switch" uniq_id="22"/> 
17<item addr="339:20" cfgid="40" name="Switch" type="switch" uniq_id="23"/> 
18<item addr="339:21" cfgid="40" name="Switch" type="switch" uniq_id="24"/> 
19<item addr="339:22" cfgid="40" name="Switch" type="switch" uniq_id="25"/> 
20<item addr="339:23" cfgid="40" name="Door" type="door-sensor" uniq_id="26"/>
21<item addr="339:24" cfgid="40" name="Door" type="door-sensor" uniq_id="27"/> 
22<item addr="339:25" cfgid="40" name="Door" type="door-sensor" uniq_id="28"/> 
23<item addr="339:26" cfgid="40" name="Door" type="door-sensor" uniq_id="29"/> 
24<item addr="339:30" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3772"/> 
25<item addr="339:31" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3773"/> 
26<item addr="339:32" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3774"/> 
27<item addr="339:33" cfgid="40" hw="offset='-10.8'" name="Temperature" type="temperature-sensor" uniq_id="3775"/> 
28<item addr="339:34" cfgid="40" hw="offset='25.1'" name="Temperature" type="temperature-sensor" uniq_id="3776"/> 
29<item addr="339:35" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3777"/> 
30<item addr="339:36" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3778"/> 
31<item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/>