EIB

Revision as of 15:10, 15 January 2022 by Rusanov (talk | contribs) (Marked this version for translation)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Other languages:
English • ‎русский

Switch-press-release (Recommended)

For correct operation, it is required that the button, when pressed, should send 1, and when released, 0 This kind of configuration can be used for double, triple clicks and dimming

Button configuration in ETS:


 

 

Configuration in EIB plugin:


 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/0 data len 1: 01  - Button pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/0 data len 1: 00  - Button released
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/2 data len 1: 01  - Feedback sent

Switch-one-phys-btn

Each press of the button sends 1 byte of data (alternately 0 or 1). To start / stop dimming, the button sends 9/8 or 1/0 to the dimming group address.

Button configuration in ETS:


 
Or:
 

 

Configuration in EIB plugin:


 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/3 destination 5/0/0 data len 1: 01 - Button pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 5/0/1 data len 1: 01 - Feedback sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/3 destination 5/0/0 data len 1: 00 - Button pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 5/0/1 data len 1: 00  - Feedback sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/3 destination 5/0/2 data len 1: 09 - Dimming UP started
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/3 destination 5/0/2 data len 1: 08 - Dimming UP finished
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/3 destination 5/0/2 data len 1: 01 - Dimming DOWN started
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/3 destination 5/0/2 data len 1: 00 - Dimming DOWN finished

Switch-two-phys-btn

This type of configuration is used if you have physically 2 buttons on a panel, one of which always sends the command on (1) and the second off (0). In this case, 2 buttons are created in the Larnitech system, each of which can be used independently. Most of the panels do not allow independent use of the feedback LEDs, therefore, if the keys are used independently, the indication may not work correctly.

Button configuration in ETS:


 

 

Configuration in EIB plugin:


 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/2 data len 1: 01 - Button 1 pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/3 data len 1: 01  - Feedback 2 sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/0 data len 1: 01  - Feedback sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/2 data len 1: 00 - Button 2 pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/3 data len 1: 00  - Feedback 2 sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/0 data len 1: 00  - Feedback sent

Switch-long-press

Works the same as Switch-two-phys-btn, the difference is that dimming is added.

Button configuration in ETS:


 

 

 

Configuration in EIB plugin:


 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/2 data len 1: 01  - Button 1 pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/3 data len 1: 01 - Feedback 2 sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/0 data len 1: 01 - Feedback sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/2 data len 1: 00  - Button 2 pressed
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/3 data len 1: 00 - Feedback 2 sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 2/0/0 data len 1: 00 - Feedback sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/1 data len 1: 01 - Button 1 dimming started
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/1 data len 1: 00 - Button 1 dimming finished
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/1 data len 1: 09 - Button 2 dimming started
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 2/0/1 data len 1: 08 - Button 2 dimming finished

Temperature Sensor

Creates a temperature sensor in the Larnitech system.

Sensor configuration in ETS:


 

 

Configuration in EIB plugin:


 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/1/5 data len 3: 00 0c c4  - Received temperature from the sensor

Thermostat

The plugin ensures temperature setpoint synchronization between a thermostat and valve-heating element in the Larnitech system

Thermostat configuration in ETS:


 

 

 

Configuration in EIB plugin:


 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 4/0/2 data len 3: 00 0c 4c - Setpoint sent to the thermostat
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0c 4c - Setpoint received from the thermostat

Climate Control

Heat/Cool Setpoint - Must be selected if the thermostat panel has only 1 address for two setpoints. In this case, depending on the selected mode in the climate control, the following values will be taken:

  • If climate control is in heating mode, Heat/Cool setpoint will be accepted as the heating setpoint. Likewise within the Cooling mode, Heat/Cool setpoint will be accepted as the cooling setpoint.
  • If the climate control is in the Heating/Cooling mode, it will use add/subtract delta and set 2 setpoints (Heat and cool). For example setpoint 25 will be transformed to 23-27.

Thermostat configuration in ETS:


 

 

 

 

 

 

Configuration in EIB plugin:


 

 

 


LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/3/1 data len 1: 00 - Turn OFF
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0d 46 - Setpoint received
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/3/1 data len 1: 01 - Turn ON
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0d 46 - Setpoint received
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 4/0/2 data len 3: 00 0c e2 - Setpoint sent to the thermostat
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0c e2 - Setpoint received

Air Conditioner

In case the device does can't send mode with the DPT 20.105 data type, but simply sends [1,2,3,4,0…], you can set your own correspondence of values to the mode

Configuration in ETS:


 

 

 

 

 

 

 

 


Configuration in EIB plugin:


 

 

LOG:

From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/3/1 data len 1: 00 - Turn OFF
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0d 46 - Setpoint received
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/3/1 data len 1: 01 - Turn ON
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0d 46 - Setpoint received
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/2/0 data len 2: 00 04 - Mode changed to Heating
From EIB (BAOS, chID 0, seq_cntr 0) => source 15/15/255 destination 4/0/2 data len 3: 00 0c e2 - Setpoint sent
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/0/1 data len 3: 00 0c e2 - Setpoint received
From EIB (BAOS, chID 0, seq_cntr 0) => source 1/1/1 destination 4/4/0 data len 2: 00 03 - Sending FAN speed