Translations:Vent/10/en

Revision as of 15:01, 24 January 2022 by FuzzyBot (talk | contribs) (Importing a new version from external source)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Byte number Bit number Description
0 0
1
3
4-7
On/Off
Fan On/Off
Boost On/Off
Integration algorithm (slow,medium,fast,boost)
1-2 8-23 CO2 setpoint (<-100 - no automation)
3-4 24-39 CO2 current (<-100 - no automation or undefined all CO2 sensors)
5 40-43
44-47
Current automation time interval index
Current automation index
6 48-55 Current fan level (0-250)
7 56
57
61
62
63
Error: Has undefined CO2 sensor(s)
Error: Has no any defined CO2 sensor
Error: low power for accessing setpoint
Error: fan state is undef
Reserved