DW-HC10

Other languages:
Revision:
/B
/C


DW-HC10.C
DW-HC10C.png
Output ports
Number of switched channels10
Peak load0.5A
Input ports
Number of digital inputs12
Other
Supply voltage11.5...27.5 V DC
Dimentions4U, 69x110x58 mm


10-CHANNEL HEATING CONTROLLER

The device is designed for controlling heating devices (radiators, floor heating, fan coil units, etc.). The device is equipped with 12 input channels for connection of temperature sensors (FW-FT or FW-TS).

Features

  • 10 outputs for NO/NC/PWM valves
  • 12 inputs for digital/analogue temperature sensors (FW-FT, FW-TS, NTC)
  • Can to use temperature data from other modules
  • 10 independed heating zones with weekly shedule
  • Up to 20 heating profiles
  • Built-in real time clock

CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment. To avoid the risk of fire, electric shock, damage to the system and/or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:

  • all connectivity work must be carried out with the power turned OFF;
  • use appropriate tools and personal protection against electric shock;
  • do not use damaged cables, wires and connectors;
  • avoid folding the cables and wires;
  • do not apply excessive force to the wires by kinking or pressing them too hard: the inner conductors of the cables and wires may get stripped or damaged;
  • do not use the power socket with poor contacts to connect;
  • do not exceed the load limit parameters specified in the manual;
  • the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.

When the power is on, NEVER:

  • connect/disconnect the connectors;
  • open modules and sensors.

Overview

 

Example of connection

 

Module dimensions

 

Module parameters

Parameter name Value
Input channels qty 12
Input/output channels qty
0-10 input port quantity
Buttons
LED Buttons
Number of sensor inputs
Number of dry contact inputs
RS485 ports qty
RS232 ports qty
UART ports qty
M-BUS port quantity
Pulse inputs quantity
DALI ports qty
DALI-line voltage supply
Peak current of DALI-line power supply
Peak current in DALI-line
Maximum DALI devices quantity
Dimming channels qty
Output channels qty 10
0-10 output port quantity
Analog output channels qty
Output
Digital line maximum length
Discrete input channels qty
Digital input channels qty
Speakers
Max power output audio channel
Camera
IR lighting
Card reader
Connection type
Protocols
Backlight voltage
Load type NO / NC / PWM (0.4Hz)
Dimmer load type
Supported sensors DS18B20 / NTC (7-15kOhm)
Input voltage 20-250V
Current type AC/DC
Adjustment type
Max load
Min load
Max load per channel 0.5A(110W at 220V)
Max load per group
Max load per device 1A(220W at 220V)
Control parameters
Angle of vision IR °
Angle of motion °
Temperature measuring range °C
Humidity measuring range
Dimmer type
Dimming type
Voltage that may be applied to the input channels 20-250V
Max output switching voltage
Max output switching current
Power supply 11.5 … 27.5 V DC from CAN
Max current(24V) 110 mA
Max current(13V)
Max detection distance
Max IR distance
Max BT distance
Max current
Relay
Data transfer speed
Permissible section of power supply cable to connect in socket:
Sensors VCC output
Sensors max VCC current
R1-R2 inputs max current
Push-button/reed switches line recommended length
Temperature sensor line max length
Sensor cable length
Sensors line max length 30m
Bus type CAN (4-wire)
Compatible with
Output voltage
Output current
Equipment installation type DIN rail (EN 60715)
Mounting
Max cabel lenght
Case material ABS
Protection IP40
Temperature range -10 … +50 °C
Size 4U, 69x110x58 mm
Weight 140 g
* -
** -
*** -
1 -
2 -
3 -


Connection of high load device

  Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.

Input connector pinout

 


Example of sensors connection

 

Indication of module operation

Bootloader

Indicator Status Description
 
  Device in bootloader
 
   Downloading firmware
   Flashing firmware

Firmware

Indicator Status Description
 
     Network configuration
     Identification
  Operational mode
  Operational mode
 

Error
  Lost connection to server
   Overheat
    Overload
     No AC power
      RTC error
 

Activity
  CAN activity
  OW activity
  RS-485 activity
  Ethernet activity


Module installation and connection procedure

  • Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
  • Connect the CAN connector.
  • Connect the input/output channels.
  • Configure the module using LT setup.
  • Apply power to the load.
  • Check all equipment for proper operation.

Module shut-off and deinstallation procedure

  • Disconnect the power from the load.
  • Disconnect the input/output channels.
  • Disconnect the CAN connector.
  • Remove the module from the DIN rail, releasing the latch at the bottom of the module base.

HW settings

Name Type, range SUBID Default Description
def string 1-10 'OFF' Def is the element status is set after restart, is used for lamp, heating, valve(1 pole);

Set 'last' saved state of the element in case of a power reset. The element save his state after stay unchanged for 10 minutes. Example: def='ON' def='last'

offset integer -39 – 39 31-42 0 It is the sensor values offset; Example: offset='-1.2'
mode string 98 'AС' Output operatoin mode:
  • 'AС' – 220V AC
  • 'DC' – DC current
out char[10] 98 'HHHHHHHHHH' Each char is responsible for the type of a particular channel
  • 'D'- PWM output (frequency 0.4Hz);
  • 'С'- Fancoil dimmer;
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='BGLKMVX'

in char[12] 98 '++++++++++++' Each char is responsible for the type of a particular channel
  • 'D'-DS18B20 digital sensor;
  • 'R'-Analogue temperature sensor;
  • '+'-Autodetection;
  • '-'Not used;

Example: out='+DR+R–R+RD+'

r int 31-42 '10000' Analogue temperature sensor`s resistance on 25 °C.

Example: r='8000'

 1<item addr="348:1" cfgid="43" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4097" hw="runtime=45"/>
 2<item addr="348:3" auto-period="600" cfgid="43" name="Lamp" type="lamp" uniq_id="4098" hw="def='ON'"/>
 3<item addr="348:4" cfgid="43" name="Gate" sub-type="120" type="gate" uniq_id="4099" hw="runtime=30"/>
 4<item addr="348:6" cfgid="43" name="Lock" type="lamp" uniq_id="4100" hw="hold=5000"/>
 5<item addr="348:7" cfgid="43" name="Radiator" type="valve-heating" uniq_id="4029" hw="def='ON'">
 6    <automation name="Eco" temperature-level="16" uniq_id="4030"/>
 7    <automation name="Comfort" temperature-level="22" uniq_id="4031"/>
 8    <automation name="Hot" temperature-level="25" uniq_id="4032"/>
 9</item>
10<item addr="348:8" cfgid="43" name="Radiator" type="valve-heating" uniq_id="4033" hw="def='OFF'">
11    <automation name="Eco" temperature-level="16" uniq_id="4034"/>
12    <automation name="Comfort" temperature-level="22" uniq_id="4035"/>
13    <automation name="Hot" temperature-level="25" uniq_id="4036"/>
14</item>
15<item addr="348:31" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4089" hw="offset=10"/>
16<item addr="348:32" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4090" hw="offset=-15"/>
17<item addr="348:33" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4091"/>
18<item addr="348:34" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4092" hw="offset=5"/>
19<item addr="348:35" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4093"/>
20<item addr="348:36" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4094"/>
21<item addr="348:37" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4095"/>
22<item addr="348:38" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4096"/>
23<item addr="348:39" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4097"/>
24<item addr="348:40" cfgid="43" name="Temperature" type="temperature-sensor" uniq_id="4098"/>
25<item addr="348:97" cfgid="43" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4041"/>
26<item addr="348:98" cfgid="43" hw="out='B-LG-KHJ--'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4042"/>