Changes

6,719 bytes added ,  13:20, 6 January 2022
Created page with "DW-BC03"
<languages/>
{{RevisionChanger | hasA = 1 | hasB = 1 | hasC = 1}}
{{Infobox module
| name = DW-BC03.C
| image = DW-BC03C.png
| outCount = 3
| dimmOut =
| peakl = 5A
| peakdl =
| dt =
| inDisc =
| inDigit =
| voltage = 11.5...27.5 V DC
| dim = 4U, 69x110x58 mm
}}

==3-CHANNEL MODULE FOR BLINDS MOTOR CONTROL==

This module provides control of curtains, projector screens, valves or other electrical motors.

==Features==
*Supported load types:
**curtains with force/low-current control
**1 / 2 pole valves
*Overcurrent protection
*Built-in current sensor

<div class="caution">
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.
To avoid the risk of fire, electric shock, damage to the system and/or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:
*all connectivity work must be carried out with the power turned OFF;
*use appropriate tools and personal protection against electric shock;
*do not use damaged cables, wires and connectors;
*avoid folding the cables and wires;
*do not apply excessive force to the wires by kinking or pressing them too hard: the inner conductors of the cables and wires may get stripped or damaged;
*do not use the power socket with poor contacts to connect;
*do not exceed the load limit parameters specified in the manual;
*the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.
When the power is on, NEVER:
*connect/disconnect the connectors;
*open modules and sensors.
</div>

==Overview==

[[File:BC03C VIEW.png|500px]]

==Connection of curtain/jalousie/shutter actuators==

[[File:BC03C EXA.png|500px]]

==Module dimensions==

[[File:BC03C DIM.png|500px]]

==Internal layout==

[[File:BC03C IL.png|500px]]


==Module parameters==

{{ Mp
| outqty = 3
| involtage = 0-250 V AC/DC
| currtype = AC/DC
| maxperch = 5A
| power = 11.5 … 27.5 V DC from CAN
| maxcur24v = 55 mA
| bustype = CAN (4-wire)
| instalation = DIN-rail (EN 60715)
| sccab = 0.5 … 4
| mccab = 0.5 … 4
| tmccab = 0.5 … 2.5
| case = ABS
| protection = IP40
| temprange = -10 … +50 °C
| size = 4U, 69x110x58 mm
| weight = 85 g
}}

==Indication of module operation==
===Bootloader===
{{indication| textBBB= Waiting for bootloader command}}
===Firmware===
{{indicationfw
|err1 = 1
|err2 = 1
|err3 = 1
}}

==Module installation and connection procedure==
#Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
#Connect the CAN connector.
#Connect the channels.
#Configure the module using LT setup.
#Apply power to the load.
#Check all equipment for proper operation.

==Module shut-off and deinstallation procedure==
#Disconnect the power from the load.
#Disconnect the channels.
#Disconnect the CAN connector.
#Remove the module from the DIN rail, releasing the latch at the bottom of the module base.

==HW settings==
{|class="wikitable"
|-
!Name!!Type, range!!SUBID!!Default!!Description
|-
|runtime||integer 0-100||1-6||15||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
|-
|runtimeopen||integer 0-60000||Blinds subId||–||Runtimeopen is the open time in miliseconds, is used for blinds; Example: runtimeopen=15000
|-
|runtimeclose||integer 0-60000||Blinds subId||–||Runtimeclose is the close time in miliseconds, is used for blinds; Example: runtimeclose=15000
|-
|hold||integer 0-10000||1-6||500||hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
|-
|current||integer 0;1||1;3;5||1||
0 – Disable current sensor.
1 – Use current sensor to detect blinds movement.
|-
|out_l_protect_on||integer||1;3;5;98||1000||Overload protection threshold (mA). (Setting to 98 subId applies to all three current sensors.)
|-
|def||string 'ON'||1-6||'OFF'||Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
|-
|stop||Char 'R'||1-5||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is 'r' or 'R' then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., 'd' ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop='r'
|-
|out||char[6]||98||'PPP'||Each char is responsible for the type of a particular channel
*'L'-Lamp;
*'M'-Lamp Inverse;
*'J'-Heating NO, valve-heating, normally open;
*'H'-Heating NC, valve-heating, normally closed;
*'B'-Blinds (2 pole), jalousie/curtains;
*'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
*'G'-Gate (2 pole), 2 pole gate;
*'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
*'X'-Gate (1 pole /short press), 1 pole gate;
*'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
*'V'-Valve (2 pole), 2 pole valve;
*'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
*'R'-Valve (1 pole), 1 pole valve,;
*'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
*'K'-Lock (short press);
*'N'-Lock (short press) Inverse;
*'P'-Blinds (2 pole);
*'O'-Blinds Inverse (2 pole), invert open-close;
*'-'-none, nothing is connected.
Example: dm='BGV'
|}
<syntaxhighlight lang="xml" line>
<item addr="449:1" cfgid="46" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4069"/>
<item addr="449:3" cfgid="46" name="Gate" sub-type="120" type="gate" uniq_id="4077" hw="runtime=55"/>
<item addr="449:5" cfgid="46" name="Valve" type="valve" uniq_id="4078"/>
<item addr="449:30" cfgid="46" name="Current" system="yes" type="current-sensor" uniq_id="4072"/>
<item addr="449:31" cfgid="46" name="Current" system="yes" type="current-sensor" uniq_id="4073"/>
<item addr="449:32" cfgid="46" name="Current" system="yes" type="current-sensor" uniq_id="4074"/>
<item addr="449:97" cfgid="46" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4075"/>
<item addr="449:98" cfgid="46" hw="out='BGV'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4076"/>
</syntaxhighlight>