==WATER LEAKAGE PROTECTION MODULE==
The module supports the connection of 2 valves of water supply
shutoff and 4 leakage sensors (up to 16 FW-WL.B/EW-WL.B ).
==Features==
*Supports 1p/2p valves
*Valve feedback reed switch
*Support up to 16 leakage sensors
*Sensor detection and diagnostics
*Sensor sensitivity adjustment
<div class="caution">
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.
To avoid the risk of fire, electric shock, damage to the system and/or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:
*all connectivity work must be carried out with the power turned OFF;
*use appropriate tools and personal protection against electric shock;
*do not use damaged cables, wires and connectors;
*avoid folding the cables and wires;
*do not apply excessive force to the wires by kinking or pressing them too hard: the inner conductors of the cables and wires may get stripped or damaged;
*do not use the power socket with poor contacts to connect;
*do not exceed the load limit parameters specified in the manual;
*the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.
When the power is on, NEVER:
*connect/disconnect the connectors;
*open modules and sensors.
</div>
==Overview==
[[File:WL02C VIEW.png|500px]]
<br>
<br>
[[File:WL02C VIEW2.png|300px]]
==Example of connection==
[[File:WL02C EXA.png|500px]]
==Module dimensions==
[[File:WL02C DIM.png|500px]]
==Internal layout==
[[File:WL02C IL.png|500px]]
==Module parameters==
{{ Mp
| outqty = 4
| siqty = 4 FW-WL.A/EW-WL.A<br>16 FW-WL.B/EW-WL.B (4 per input)
| dcqty = 2
| involtage = 0-250 V AC/DC
| currtype = AC/DC
| maxperch = 5A
| power = 11.5 … 27.5 V DC from CAN
| maxcur24v = 60 mA
| sensvccout = 8..12 V
| sensmaxvcccur = 70 mA
| rinmaxcur = 3 mA
| smaxlen = 30m
| bustype = CAN (4-wire)
| instalation = DIN-rail (EN 60715)
| case = ABS
| protection = IP40
| temprange = -10 … +50 °C
| size = 4U, 69x110x58 mm
| weight = 100 g
}}
==Indication of module operation==
===Bootloader===
{{indication| textBBB= Waiting for bootloader command}}
===Firmware===
{{indicationfw
|err1 = 1
|err2 = 1
|err3 = 1
}}
==Module installation and connection procedure==
#Install the module in the switchboard on the DIN rail and fix it with the special latch on the module base.
#Connect the CAN connector.
#Connect the channels.
#Configure the module using LT setup.
#Apply power to the load.
#Check all equipment for proper operation.
==Module shut-off and deinstallation procedure==
#Disconnect the power from the load.
#Disconnect the channels.
#Disconnect the CAN connector.
#Remove the module from the DIN rail, releasing the latch at the bottom of the module base.
==HW settings==
{|class="wikitable"
|-
!Name!!Type, range!!SUBID!!Default!!Description
|-
|runtime||integer 0-100||1-4||15||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
|-
|runtimeopen||integer 0-60000||Blinds subId||-||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
|-
|runtimeclose||integer 0-60000||Blinds subId||-||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
|-
|hold||integer 0-10000||1-4||500||hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
|-
|def||string 'ON'||1-4||'OFF'||Def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
|-
|out||char[4]||98||'V-V-'||Each char is responsible for the type of a particular channel
*'L'-Lamp;
*'M'-Lamp Inverse;
*'J'-Heating NO, valve-heating, normally open;
*'H'-Heating NC, valve-heating, normally closed;
*'B'-Blinds (2 pole), jalousie/curtains;
*'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
*'G'-Gate (2 pole), 2 pole gate;
*'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
*'X'-Gate (1 pole /short press), 1 pole gate;
*'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
*'V'-Valve (2 pole), 2 pole valve;
*'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
*'R'-Valve (1 pole), 1 pole valve,;
*'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
*'K'-Lock (short press);
*'N'-Lock (short press) Inverse;
*'P'-Blinds (2 pole);
*'O'-Blinds Inverse (2 pole), invert open-close;
*'-'-none, nothing is connected.
Example: out='V-V-'
|-
|leak||char[4]||98||'LLLL'||Each char is responsible for the type of a particular channel
*'L'-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
*'N'-Third party leakage sensor;
*'S' – Leak, on-the-floor (FW-WL.B) leakage sensor
*'-'-none
|-
|in||char[2]||98||'KK'||Each char is responsible for the type of a particular channel
*'K' – Contact;
*'H' – Inverted contact;
*'-' – none;
Example: in='HHKK'
|}
<syntaxhighlight lang="xml" line>
<item addr="500:1" cfgid="53" hw="runtime=30" name="Valve" type="valve" uniq_id="4105"/>
<item addr="500:3" cfgid="53" name="Jalousie" sub-type="120" type="jalousie" uniq_id="4117"/>
<item addr="500:11" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4107"/>
<item addr="500:12" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4108"/>
<item addr="500:13" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4109"/>
<item addr="500:14" cfgid="53" name="Leak" type="leak-sensor" uniq_id="4110"/>
<item addr="500:21" cfgid="53" name="Door" type="door-sensor" uniq_id="4111"/>
<item addr="500:22" cfgid="53" name="Door" type="door-sensor" uniq_id="4112"/>
<item addr="500:23" cfgid="53" name="Door" type="door-sensor" uniq_id="4113"/>
<item addr="500:24" cfgid="53" name="Door" type="door-sensor" uniq_id="4114"/>
<item addr="500:97" cfgid="53" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4115"/>
<item addr="500:98" cfgid="53" hw="leak='NNLL' in='HHKK' out='V-B-'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="4116"/>
</syntaxhighlight>