Byte number Bit number Description
0 0
3
4-7
On/Off
Autostate
Mode:
0 – fan
1 – cool
2 – dry
3 – heat
4 – auto
1-2 8-23 Temperature setpoint
3 24-27








28-31







Horizontal vanes:
0 – left
1 – left-center
2 – center
3 – center-right
4 – right
5 – sides (low angle)
6 – sides (high angle)
7 – from sides to center
Vertical vanes:
0 – auto
1 – top
2 – top-center
3 – center
4 – center-bottom
5 – bottom
6 – swing
4 32-35







Fan:
0 – auto
1 – 1st speed
2 – 2nd speed
3 – 3rd speed
4 – 4th speed
5 – 5th speed
6 – silent mode
5-6 40-55 Current temperature
7 56-63 Flags
8 64-71 Errors