Name |
type and variety |
description |
default value
|
temperature-sensors |
list |
list of valve temperature sensors (for automation) |
-
|
automation |
string |
name of current automation mode |
-
|
valve |
string (addr) |
addr of valve |
-
|
valve-heating |
string (addr) |
addr of heating valve |
-
|
valve-cooling |
string (addr) |
addr of cooling valve |
-
|
temperature-lag |
number |
hysteresis range on either side from set-point temperature Set in automation tag. The decimal symbol is dot. |
0.5
|
undefined-behavior |
0-250/on/off/last |
fancoil position in case of sensors readings absence (off – 0; on – 250) |
last
|
P0 |
0-100 |
minimal power for turning on fan |
last
|
mode |
heat/cool |
heat/cool mode |
heat
|
alg |
string |
eco/fast/boost alg |
-
|
heat-carrier |
string (addr) |
temperature sensor of heat carrier |
-
|
limit-fan |
number(0-250) |
max power |
-
|
ctrl-change1 |
number(0-250) |
min level of power change (one time per “ctrl-ticks” attr) if defined |
5
|
ctrl-change2 |
number(0-250) |
min level of power change |
-
|
ctrl-ticks |
number(0-3825) |
power change by "ctrl-change1" timeout |
-
|