HW settings

Name Type, range SUBID Default Description
dm char[9] 98 'RGBRGBRGB' Each char is responsible for the type of a particular channel, RGB takes 3 channels
  • 'RGB' – Use like RGB lamp
  • 'L' – LED Function, dimmable LED lamps
  • 'G' – Use like halogen dimer-lamp
  • 'Y' – Linear Function of dimming
  • 'F' – Fancoil
  • 'S' – Lamp
  • 'M' – Inverse lamp
  • 'V' – Valve
  • 'W' – Inverse valve
  • 'K' – Lock
  • 'N' – Inverse lock
  • 'H' – Valve heating
  • 'J' – Inverse valve heating
  • '-' – Channel disabled

Example: dm='LLLRGBLLL'

f integer 0-1000 98 500 Frequency of rgb LED

Example:hw="f=800"

def integer 0-250 1-5 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 1-5 0 Minimum dimming level, example: min=10
max integer 0-100 1-5 100 Maximum dimming level, example max=95
force integer 0-100 1-5 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 1-9 5 Runtime is the speed of changing the brightness(measured in miliseconds for dimmer and in seconds for RGB). Example: runtime=5000