==5-CHANNEL EXTENSION MODULE== <!--T:2-->
 
  −
==5-CHANNEL EXTENSION MODULE==
   
Has 5 outputs for connecting loads and 12 inputs for connecting
 
Has 5 outputs for connecting loads and 12 inputs for connecting
 
various sensors/buttons.
 
various sensors/buttons.
   −
==Features==
+
==Features== <!--T:3-->
    +
<!--T:4-->
 
*5 universal outputs support:
 
*5 universal outputs support:
 
**Lights
 
**Lights
Line 35: Line 38:  
**Leak sensors
 
**Leak sensors
 
**Motion detectors
 
**Motion detectors
*4 digital inputs for up to 8 temperature sensors
      +
<!--T:5-->
 
<div class="caution">
 
<div class="caution">
 
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.
 
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.
Line 53: Line 56:  
</div>
 
</div>
   −
==Overview==
+
==Overview== <!--T:6-->
 
[[File:HT05B VIEW.png|500px]]
 
[[File:HT05B VIEW.png|500px]]
   −
==Example of connection==
+
==Example of connection== <!--T:7-->
 
[[File:HT05B EXA.png|500px]]
 
[[File:HT05B EXA.png|500px]]
   −
==Module dimensions==
+
==Module dimensions== <!--T:8-->
 
[[File:HT05B DIMM.png|500px]]
 
[[File:HT05B DIMM.png|500px]]
   −
==Module parameters==
+
==Module parameters== <!--T:9-->
    +
<!--T:10-->
 
{{ Mp
 
{{ Mp
 
| outqty          = 5
 
| outqty          = 5
 
| discinqty      = 12
 
| discinqty      = 12
| digitinqty      = 4
   
| involtage      = 0-250V
 
| involtage      = 0-250V
 
| currtype        = AC/DC
 
| currtype        = AC/DC
Line 82: Line 85:  
}}
 
}}
   −
==Connectivity recommendations==
+
==Connectivity recommendations== <!--T:11-->
    +
<!--T:12-->
 
In order to protect the actuator and loads connected to it, installing a circuit breaker is recommended.
 
In order to protect the actuator and loads connected to it, installing a circuit breaker is recommended.
 
The nominal value of the circuit breaker should be calculated based on the maximum total load of connected
 
The nominal value of the circuit breaker should be calculated based on the maximum total load of connected
Line 91: Line 95:  
for each load.
 
for each load.
   −
==Connection of actuators==
+
==Connection of actuators== <!--T:13-->
    +
<!--T:14-->
 
<div class="caution"> Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.
 
<div class="caution"> Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.
 
If free (unused) channels remain in a given group after a curtain/jalousie/shutter actuator with low-voltage control or gate actuator has been connected to it, these channels need to be left unused. (Do not connect other devices to them!) </div>
 
If free (unused) channels remain in a given group after a curtain/jalousie/shutter actuator with low-voltage control or gate actuator has been connected to it, these channels need to be left unused. (Do not connect other devices to them!) </div>
   −
===Connection of the lights/electric contactor/heating thermal actuator===
+
===Connection of the lights/electric contactor/heating thermal actuator=== <!--T:15-->
    +
<!--T:16-->
 
[[File:lamps.png|200px]]<br>
 
[[File:lamps.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 105: Line 111:       −
===Connection of high load device===
+
===Connection of high load device=== <!--T:17-->
    +
<!--T:18-->
 
{| class="wikitable" style="width:800px";
 
{| class="wikitable" style="width:800px";
 
|-
 
|-
Line 115: Line 122:  
|}
 
|}
   −
===Connection of curtain/jalousie/shutter actuator with 220V force control===
+
===Connection of curtain/jalousie/shutter actuator with 220V force control=== <!--T:19-->
    +
<!--T:20-->
 
[[File:Pjalousie.png|200px]]<br>
 
[[File:Pjalousie.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 123: Line 131:  
</syntaxhighlight>
 
</syntaxhighlight>
   −
===Connection of curtain/jalousie/shutter actuator with low-voltage control===
+
===Connection of curtain/jalousie/shutter actuator with low-voltage control=== <!--T:21-->
    +
<!--T:22-->
 
[[File:Ljalousie.png|200px]]<br>
 
[[File:Ljalousie.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 131: Line 140:  
</syntaxhighlight>
 
</syntaxhighlight>
   −
===Connection of single-pole gate actuator===
+
===Connection of single-pole gate actuator=== <!--T:23-->
    +
<!--T:24-->
 
[[File:1pgate.png|200px]]<br>
 
[[File:1pgate.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 139: Line 149:  
</syntaxhighlight>
 
</syntaxhighlight>
   −
===Connection of double-pole gate actuator===
+
===Connection of double-pole gate actuator=== <!--T:25-->
    +
<!--T:26-->
 
[[File:2pgate.png|200px]]<br>
 
[[File:2pgate.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 149: Line 160:       −
===Connection of single-pole water/gas supply valve===
+
===Connection of single-pole water/gas supply valve=== <!--T:27-->
    +
<!--T:28-->
 
[[File:1pvalve.png|200px]]<br>
 
[[File:1pvalve.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 157: Line 169:  
</syntaxhighlight>
 
</syntaxhighlight>
   −
===Connection of double-pole water/gas supply valve===
+
===Connection of double-pole water/gas supply valve=== <!--T:29-->
    +
<!--T:30-->
 
[[File:2pvalve.png|200px]]<br>
 
[[File:2pvalve.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 165: Line 178:  
</syntaxhighlight>
 
</syntaxhighlight>
   −
===Connection of fancoil control unit===
+
===Connection of fancoil control unit=== <!--T:31-->
    +
<!--T:32-->
 
[[File:fancoil.png|200px]]<br>
 
[[File:fancoil.png|200px]]<br>
 
Sample HW for this configuration
 
Sample HW for this configuration
Line 174: Line 188:       −
==Indication of module operation==
+
==Indication of module operation== <!--T:33-->
    +
<!--T:34-->
 
{{Indicationold}}
 
{{Indicationold}}
   −
==Module installation and connection procedure==
+
==Module installation and connection procedure== <!--T:35-->
    +
<!--T:36-->
 
#Connect the outputs.
 
#Connect the outputs.
 
#Connect the inputs.
 
#Connect the inputs.
Line 187: Line 203:  
#Check all equipment for proper operation.
 
#Check all equipment for proper operation.
   −
==Module shut-off and deinstallation procedure==
+
==Module shut-off and deinstallation procedure== <!--T:37-->
    +
<!--T:38-->
 
#Disconnect the power from the load
 
#Disconnect the power from the load
 
#Disconnect the CAN connector.
 
#Disconnect the CAN connector.
Line 194: Line 211:  
#Disconnect the outputs.
 
#Disconnect the outputs.
   −
==HW Settings==
+
==HW Settings== <!--T:39-->
    +
<!--T:40-->
 
{| class="wikitable"
 
{| class="wikitable"
 
|-
 
|-
 
!Name!!Type, range!!SUBID!!Default!!Description
 
!Name!!Type, range!!SUBID!!Default!!Description
 
|-
 
|-
|runtime||integer 0-100||1-7||15||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
+
|runtime||integer 0-100||1-5||15||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); Example: runtime=15
 
|-
 
|-
 
|runtimeopen||integer 0-60000||Blinds subId||-||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
 
|runtimeopen||integer 0-60000||Blinds subId||-||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
Line 206: Line 224:  
|runtimeclose||integer 0-60000||Blinds subId||-||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
 
|runtimeclose||integer 0-60000||Blinds subId||-||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
 
|-
 
|-
|hold||integer 0-10000||1-7||500||hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
+
|hold||integer 0-10000||1-5||500||hold is the bridging time in miliseconds, is used for gate and jalousie (by default hold is the same as runtime), lock; Example: hold=3500
 
|-
 
|-
|def||string 'ON'||1-7||'OFF'||def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
+
|def||string 'ON'||1-5||'OFF'||def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
 
|-
 
|-
|stop||Char ‘R’||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
+
|stop||Char ‘R’||1-5||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
 
|-
 
|-
|out||char[7]||98||'LLLLLLL'||Each char is responsible for the type of a particular channel
+
|out||char[5]||98||'LLLLL'||Each char is responsible for the type of a particular channel
 
*'L'-Lamp;
 
*'L'-Lamp;
 
*'M'-Lamp Inverse;
 
*'M'-Lamp Inverse;
Line 249: Line 267:  
*'N'-Third party leakage sensor;
 
*'N'-Third party leakage sensor;
 
*'M'-Motion, ​motion sensor;
 
*'M'-Motion, ​motion sensor;
 +
*'V'-Motion sensor (CW-MSD);
 
*'-'-none
 
*'-'-none
 
Example: in='KKKBBBLLLMMM'
 
Example: in='KKKBBBLLLMMM'
 
|}
 
|}
    +
<!--T:41-->
 
<syntaxhighlight lang="xml" line>
 
<syntaxhighlight lang="xml" line>
<item addr="479:1" auto-period="600" cfgid="42" name="Lamp" type="lamp" uniq_id="145" hw="def='ON'"/>
+
<item addr="331:1" auto-period="600" cfgid="41" name="Lamp" type="lamp" hw="def='ON'" uniq_id="189"/>
<item addr="479:2" cfgid="42" name="Radiator" type="valve-heating" uniq_id="146" hw="def='ON'">
+
<item addr="331:2" cfgid="41" name="Jalousie" sub-type="120" type="jalousie" hw="runtime=35" uniq_id="190"/>
  <automation name="Eco" temperature-level="16" uniq_id="147"/>
+
<item addr="331:4" cfgid="41" name="Valve" type="valve" hw="runtime=44" uniq_id="191"/>
  <automation name="Comfort" temperature-level="22" uniq_id="148"/>
+
<item addr="331:11" cfgid="41" name="Motion" type="motion-sensor" uniq_id="192"/>
  <automation name="Hot" temperature-level="25" uniq_id="149"/>
+
<item addr="331:12" cfgid="41" name="Leak" type="leak-sensor" uniq_id="193"/>
</item>
+
<item addr="331:13" cfgid="41" name="Leak" type="leak-sensor" uniq_id="194"/>
<item addr="479:3" cfgid="42" name="Gate" sub-type="120" type="gate" uniq_id="150" hw="runtime=25"/>
+
<item addr="331:14" cfgid="41" name="Switch" type="switch" uniq_id="195"/>
<item addr="479:5" cfgid="42" name="Jalousie" sub-type="120" type="jalousie" uniq_id="151" hw="runtime=50"/>
+
<item addr="331:15" cfgid="41" name="Switch" type="switch" uniq_id="196"/>
<item addr="479:7" cfgid="42" name="Valve" type="valve" uniq_id="152" hw="def='ON'"/>
+
<item addr="331:16" cfgid="41" name="Door" type="door-sensor" uniq_id="184"/>
<item addr="479:11" cfgid="42" name="Switch" type="switch" uniq_id="153"/>
+
<item addr="331:18" cfgid="41" name="Door" type="door-sensor" uniq_id="186"/>
<item addr="479:12" cfgid="42" name="Switch" type="switch" uniq_id="154"/>
+
<item addr="331:97" cfgid="41" name="Temperature" system="yes" type="temperature-sensor" uniq_id="187"/>
<item addr="479:13" cfgid="42" name="Door" type="door-sensor" uniq_id="133"/>
+
<item addr="331:98" cfgid="41" hw="out='LB-V-' in='MLNSB----H-K'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="188"/>
<item addr="479:14" cfgid="42" name="Door" type="door-sensor" uniq_id="134"/>
  −
<item addr="479:15" cfgid="42" name="Leak" type="leak-sensor" uniq_id="155"/>
  −
<item addr="479:16" cfgid="42" name="Leak" type="leak-sensor" uniq_id="156"/>
  −
<item addr="479:17" cfgid="42" name="Motion" type="motion-sensor" uniq_id="157"/>
  −
<item addr="479:18" cfgid="42" name="Door" type="door-sensor" uniq_id="138"/>
  −
<item addr="479:20" cfgid="42" name="Door" type="door-sensor" uniq_id="140"/>
  −
<item addr="479:21" cfgid="42" name="Motion" type="motion-sensor" uniq_id="158"/>
  −
<item addr="479:97" cfgid="42" name="Temperature" system="yes" type="temperature-sensor" uniq_id="143"/>
  −
<item addr="479:98" cfgid="42" hw="out='LHG-B-R' in='CSKHLNMK-KM-'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="144"/>
   
</syntaxhighlight>
 