GATEWAY
This module is used to connect two additional CAN networks to the system. It also converts Ethernet into CAN bus and vice versa.
CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.To avoid the risk of fire, electric shock, damage to the system and/or personal injury, the system installation and assembly must be performed in accordance with the instructions listed below:
all connectivity work must be carried out with the power turned OFF;
use appropriate tools and personal protection against electric shock;
do not use damaged cables, wires and connectors;
avoid folding the cables and wires;
do not apply excessive force to the wires by kinking or pressing them too hard: the inner conductors of the cables and wires may get stripped or damaged;
do not use the power socket with poor contacts to connect;
do not exceed the load limit parameters specified in the manual;
the supply conductors wire section is subject to the specifications for current density limit, insulation type and wire material. Light section can result in cable overheating and fire.
When the power is on, NEVER:
connect/disconnect the connectors;
open modules and sensors.
Downloads
DWG file
Module view
Indicators
Ethernet
Power supply
CAN1
CAN2
Module dimensions
Connectors
Сonnection example
Module parameters
Parameter name
Value
Type of connection
CAN, Ethernet
Input/output interfaces
Ethernet, 2xCAN
Data speed
10/100Mb/s
Max CAN deviсes
100(50 per CAN)
CAN bus topology
BUS
Number of CAN ports
2
Power supply
11.5 … 27.5 V DC
24V, 2.5A Recommended
Max own current (24V)
60mA
Max CAN bus length
800 m* (twisted pair 5 cat)
Max current per CAN bus
700mA
Case material
ABS
Protection
IP40
Equipment installation type
DIN-rail (EN 60715)
Temperature range
-10 … +50°C
Size
2U, 35x95x58 mm
Weight
65 g
* – installing additional power supply units is required for long lines; the maximum length of the line may be reduced by various interference factors
Indication of module operation.