Line 563: |
Line 563: |
| *provjeriti integritet CAN vodova, napajanje napona na modulima. | | *provjeriti integritet CAN vodova, napajanje napona na modulima. |
| | | |
− | ==HW Settings== | + | ==HW postavke== |
| {| class="wikitable" | | {| class="wikitable" |
| |- | | |- |
− | !Name!!Type, range!!SUBID!!Default!!Description | + | !Ime!!Vrsta, opseg!!SUBID!!Podrazumevano!!Opis |
| |- | | |- |
− | |runtime||integer 0-100 || 1-10 || 15 ||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); | + | |runtime||integer 0-100 || 1-10 || 15 ||vrijeme rada je vrijeme otvaranja/zatvaranja u sekundama, koristi se za žaluziju, kapiju, ventil (2 polni); |
− | <br>Example: runtime=15 | + | <br>Primjer: runtime=15 |
| |- | | |- |
− | |runtimeopen||integer 0-60000||Blinds subId || ||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000 | + | |runtimeopen||integer 0-60000||Blinds subId || ||Runtimeopen je otvoreno vrijeme u milisekundama, koristi se za roletne; primjer: runtimeopen=15000 |
| |- | | |- |
− | |runtimeclose||integer 0-60000||Blinds subId|| ||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000 | + | |runtimeclose||integer 0-60000||Blinds subId|| ||Runtimeclose je vrijeme zatvaranja u milisekundama, koristi se za roletne; primjer: runtimeclose=15000 |
| |- | | |- |
− | |hold||integer 0-10000||1-10||500||hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500 | + | |hold||integer 0-10000||1-10||500||hold je vrijeme premošćavanja u milisekundama, koristi se za kapiju i žaluziju (podrazumevano zadržavanje je isto kao vrijeme izvođenja za žaluziju i vrata), zaključavanje; primjer: hold=3500 |
| |- | | |- |
− | |def||string 'ON'||1-10||'OFF'||def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON' | + | |def||string 'ON'||1-10||'OFF'||def je status elementa postavljen nakon ponovnog pokretanja, koristi se za lampu, grijanje, ventil (1 pol); primjer: def='ON' |
| |- | | |- |
− | |stop||Char ‘R’||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’ | + | |stop||Char ‘R’||1-7||–||(za 2-polna kapija i roletne) Ako se deklariše tada komandom Stop tokom kretanja, pojavljuje se isti impuls kao i na početku pokreta. Pol, na kojem se formiraju stop-impuli, definiran je parametrom Stop vrijednost. Ako je 'r' ili 'R' tada se stop-impuls proizvodi na suprotnom od pola start-impulsa. Ako se unese bilo koja druga vrijednost (npr. 'd'), tada je stop-impuls na istom polu. Ako je Runtime prošlo nakon početka pokreta, tada se stop-impuls ne formira. primjer: stop=’r’ |
| |- | | |- |
− | |out||char[10]||98||'LLLLHHHHP-'||Each char is responsible for the type of a particular channel | + | |out||char[10]||98||'LLLLHHHHP-'||Svaki znak je odgovoran za tip određenog kanala |
| *'L'-Lamp; | | *'L'-Lamp; |
| *'M'-Lamp Inverse; | | *'M'-Lamp Inverse; |
− | *'J'-Heating NO, valve-heating, normally open; | + | *'J'-grijanje NE, ventil za grijanje, normalno otvoren; |
− | *'H'-Heating NC, valve-heating, normally closed; | + | *'H'-grijanje NC, ventil za grijanje, normalno zatvoren; |
− | *'B'-Blinds (2 pole), jalousie/curtains; | + | *'B'-Roletne (2 pol), žaluzine/zavjese; |
− | *'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close; | + | *'C'-Rolete Inverse (2 polne), žaluzije/zavjese, invertno otvaranje-zatvaranje; |
− | *'G'-Gate (2 pole), 2 pole gate; | + | *'G'-kapija (2-polna), 2-polna kapija; |
− | *'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close; | + | *'D'-Gate (2-polna) Inverzna, 2-polna kapija, invertna otvaranje-zatvaranje; |
− | *'X'-Gate (1 pole /short press), 1 pole gate; | + | *'X'-Gate (1 pol /kratki pritisak), 1 pole kapija; |
− | *'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close; | + | *'Z'-kapija (1 pol) Inverzna, 1-polna kapija, invertno otvaranje-zatvaranje; |
− | *'V'-Valve (2 pole), 2 pole valve; | + | *'V'-ventil (2-polni), 2-polni ventil; |
− | *'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close; | + | *'W'-ventil (2-polni) Inverzni, 2-polni ventil, obrnuti otvaranje-zatvaranje; |
− | *'R'-Valve (1 pole), 1 pole valve,; | + | *'R'-ventil (1-polni), 1-polni ventil,; |
− | *'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close; | + | *'S'-ventil (1 polni) Inverzni, 1-polni ventil, obrnuti otvaranje-zatvaranje; |
− | *'K'-Lock (short press); | + | *'K'-Lock (kratak pritisak); |
− | *'N'-Lock (short press) Inverse; | + | *'N'-Lock (kratki pritisak) Inverse; |
− | *'P'-Blinds (2 pole); | + | *'P' roletne (2 polne); |
− | *'O'-Blinds Inverse (2 pole), invert open-close; | + | *'O'-Blinds Inverse (2 pol), invertno otvaranje-zatvaranje; |
− | *'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control; | + | *'F'-FanCoil. Grupa1 (Lamp Toggle). Za kontrolu brzine ventilatora; |
− | *'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control; | + | *'E'-FanCoil. Group2 (Lamp Toggle). Za kontrolu brzine ventilatora; |
− | *'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control; | + | *'Q'-FanCoil. Grupa 3 (Prebacivanje lampe). Za kontrolu brzine ventilatora; |
− | *'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control; | + | *'U'-FanCoil. Grupa 4 (Prebacivanje lampe). Za kontrolu brzine ventilatora; |
− | *'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control; | + | *'I'-FanCoil. Grupa 5 (Prebacivanje lampe). Za kontrolu brzine ventilatora; |
− | *'-'-none, nothing is connected. | + | *'-'-ništa, ništa nije povezano. |
− | Example: out='LLB-G-V-W-'
| + | primjer: out='LLB-G-V-W-' |
| |- | | |- |
− | |dm||char[4]||98||‘LLLL’||Each char is responsible for the type of a particular channel | + | |dm||char[4]||98||‘LLLL’||Svaki znak je odgovoran za tip određenog kanala |
− | *‘g’ – use like halogen dimer-lamp | + | *‘g’ – koristiti kao halogena dimer lampa |
− | *‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec) | + | *‘s’ – Soft Switch, lampa, kada se napajanje uključuje/isključuje glatko (500msec) |
− | *‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately | + | *‘k’ – Prekidač, lampa, kada se napajanje uključi/isključi odmah |
− | *‘l’ – LED Function, dimmable LED lamps | + | *‘l’ – LED funkcija, LED lampe koje se mogu prigušiti |
− | *‘v’ – linear Function of dimming | + | *‘v’ – linearna funkcija zatamnjivanja |
− | *‘-‘ – Channel disabled | + | *‘-‘ – Kanal onemogućen |
− | *‘+’ – Regular channel | + | *‘+’ – Redovni kanal |
− | Example: dm=’skl-‘
| + | primjer: dm=’skl-‘ |
| |- | | |- |
− | |def||integer 0-250||11-14||100||The default brightness level in case of a power reset (1..250). Example: def=250 | + | |def||integer 0-250||11-14||100||Podrazumevani nivo osvetljenosti u slučaju resetovanja napajanja (1..250). primjer: def=250 |
| |- | | |- |
− | |min||integer 0-100||11-14||0||Minimum dimming level, example: min=10 | + | |min||integer 0-100||11-14||0||Minimalni nivo zatamnjenja, primjer: min=10 |
| |- | | |- |
− | |max||integer 0-100||11-14||100||Maximum dimming level, example max=95 | + | |max||integer 0-100||11-14||100||Maksimalni nivo zatamnjenja, primer max=95 |
| |- | | |- |
− | |start||integer 0-100||11-14||0||The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60 | + | |start||integer 0-100||11-14||0||Funkcija Start se koristi za lampe kojima nedostaje minimalni napon za uključivanje. Ako je podešena vrijednost niža od početne vrijednosti, lampa se uključuje na početnu vrijednost i njima se svjetlo prigušuje do postavljenog nivoa. primjer: start=60 |
| |- | | |- |
− | |force||integer 0-100||11-14||10||Time duration of the starting value (measured in milliseconds). Example: force=20 | + | |force||integer 0-100||11-14||10||Vremensko trajanje početne vrijednosti (mjereno u milisekundama). primjer: force=20 |
| |- | | |- |
− | |runtime||integer 0-60000||11-14||1000||Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000 | + | |runtime||integer 0-60000||11-14||1000||Vrijeme rada je brzina promjene svjetline sa 'min' na 'max' (mjereno u milisekundama). primjer: runtime=1000 |
| |- | | |- |
− | |offset||integer (+/- 0…39)||39-46||'0'||sensor values offset; For example, offset is -3.8 : | + | |offset||integer (+/- 0…39)||39-46||'0'|| pomak vrijednosti senzora; Na primjer, pomak je -3,8: |
− | Example: hw="offset='-3.8'"
| + | primjer: hw="offset='-3.8'" |
| |- | | |- |
− | |in||char[24]||98||'BBBBBBBBBBBBMMMLLLKKKKKK'||Each char is responsible for the type of a particular channel | + | |in||char[24]||98||'BBBBBBBBBBBBMMMLLLKKKKKK'||Svaki znak je odgovoran za tip određenog kanala |
− | *'B'-Button; | + | *'B'-dugme; |
| *'C'-nButton; | | *'C'-nButton; |
| *'S'-Switch; | | *'S'-Switch; |
− | *'K'-Contact; | + | *'K'-Kontakt; |
− | *'H'-nContact; | + | *'H'-nKontakt; |
− | *‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor | + | *‘L’-curenje, ugrađeni pod (EW-WL) ili podni (FW-WL) senzor curenja |
− | *‘N’-Third party leakage sensor; | + | *‘N’-Senzor curenja treće strane; |
− | *'M'-Motion, motion sensor; | + | *'M'-Motion, senzor pokreta; |
− | *'V'-nMotion, motion sensor; | + | *'V'-nMotion, senzor pokreta; |
− | *'-'-none | + | *'-'-ništa |
− | Example: in='MMMMMMMMMMMMLLLLLLLLLLLL'
| + | Primjer: in='MMMMMMMMMMMMLLLLLLLLLLLLLL' |
− | 12 motion sensors and 12 leak-sensors; | + | 12 senzora pokreta i 12 senzora curenja; |
| in='BBBBBBBBSSSSSSBBBBSSSSSS' | | in='BBBBBBBBSSSSSSBBBBSSSSSS' |
− | 12 buttons; 12 switches. | + | 12 dugmadi; 12 prekidača. |
| |} | | |} |
| | | |