| {{Infobox module | | {{Infobox module |
| | name = MFC-14 | | | name = MFC-14 |
| | image = Metaforsa2-Cloud.png | | | image = Metaforsa2-Cloud.png |
| + | | maxcandev = 50 |
| + | | canbuslength = 800 m (twisted pair 5 cat) |
| + | | maxcancurrent = 500 mA |
| | outCount = 10 | | | outCount = 10 |
| | dimmOut = 4 | | | dimmOut = 4 |
− | | peakl = 16A | + | | peakl = 16 A |
− | | peakdl = 0.5A (110W at 220V) | + | | peakdl = 0.5 A (110 W at 220 V) |
| | dt = MOSFET | | | dt = MOSFET |
| | inDisc = 24 | | | inDisc = 24 |
Line 12: |
Line 18: |
| | dim = 9U, 156x110x58 mm | | | dim = 9U, 156x110x58 mm |
| }} | | }} |
− | ==Introduction== | + | ==Introduction== <!--T:1--> |
| | | |
| | | |
| + | <!--T:2--> |
| METAFORSA SMART HOUSE Installation Manual describes the procedure for its installation, assembly, operation and setting. While working with the system, you must strictly comply with all the requirements set out in this manual. Failure to comply may result in damage to the device, its failure, electric shock, fire and other fallout. The manufacturer reserves the right to make changes to this manual without prior notice. This manual is an integral part of the system and shall remain with the end-use customer. | | METAFORSA SMART HOUSE Installation Manual describes the procedure for its installation, assembly, operation and setting. While working with the system, you must strictly comply with all the requirements set out in this manual. Failure to comply may result in damage to the device, its failure, electric shock, fire and other fallout. The manufacturer reserves the right to make changes to this manual without prior notice. This manual is an integral part of the system and shall remain with the end-use customer. |
| | | |
− | ==Features== | + | <!--T:2.1--> |
| + | <youtube>IC_-C7zVTPc</youtube> |
| + | |
| + | ==Features== <!--T:3--> |
| | | |
| | | |
| + | <!--T:4--> |
| *10 universal outputs support: | | *10 universal outputs support: |
− | **Lights | + | **Light |
− | **NC/NO heating valves | + | ** NC/NO heating valves |
| **Blinds | | **Blinds |
| **1 or 2-pole gates | | **1 or 2-pole gates |
− | **1 or 2-pole valves | + | ** 1 or 2-pole valves |
| **NC/NO locks | | **NC/NO locks |
| **Fan coil units | | **Fan coil units |
Line 42: |
Line 53: |
| *Voice control (Siri, Alexa, Google Home) | | *Voice control (Siri, Alexa, Google Home) |
| | | |
− | ==Safety requirements== | + | ==Safety requirements== <!--T:5--> |
| | | |
| | | |
| + | <!--T:6--> |
| <div class="caution">'''CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.''' | | <div class="caution">'''CAUTION! All work related to the installation, connection, setting up, service and support must be carried out by qualified personnel with sufficient skills and experience in working with electrical equipment.''' |
| </div> | | </div> |
Line 50: |
Line 62: |
| | | |
| | | |
| + | <!--T:7--> |
| *all connection works must be carried out without power; | | *all connection works must be carried out without power; |
| *use appropriate tools and personal protection against electric shock; | | *use appropriate tools and personal protection against electric shock; |
Line 60: |
Line 73: |
| | | |
| | | |
| + | <!--T:8--> |
| When working with the system after voltage supply '''NEVER''': | | When working with the system after voltage supply '''NEVER''': |
| *make connection/disconnection of connectors; | | *make connection/disconnection of connectors; |
| *open modules and sensors. | | *open modules and sensors. |
| | | |
− | ==System configuration and purpose== | + | == System configuration and purpose== <!--T:9--> |
| | | |
− | ===Purpose of the system=== | + | ===Purpose of the system=== <!--T:10--> |
| | | |
| | | |
| + | <!--T:11--> |
| METAFORSA SMART HOUSE is a ready-made solution for automation of residential and commercial premises, hotel complexes which includes the most highly desired features of Smart House. | | METAFORSA SMART HOUSE is a ready-made solution for automation of residential and commercial premises, hotel complexes which includes the most highly desired features of Smart House. |
| | | |
| | | |
| + | <!--T:12--> |
| The device has 10 control channels, 4 dimming channels, 24 incoming sensor channels, and a digital sensors’ connection port. | | The device has 10 control channels, 4 dimming channels, 24 incoming sensor channels, and a digital sensors’ connection port. |
| | | |
| | | |
| + | <!--T:13--> |
| {| class="wikitable" | | {| class="wikitable" |
| |- | | |- |
− | ! Universal outputs can be used to control: !! Universal inputs allow you to connect: | + | ! Universal outputs can be used to control:!!Universal inputs allow you to connect: |
| |- | | |- |
− | | Lighting || Buttons/switching units | + | |Lighting||Buttons/switching units |
| |- | | |- |
− | | Socket connectors || Magnetic reed switches | + | | Socket connectors||Magnetic reed switches |
| |- | | |- |
− | | Underfloor heating || Magnetic reed switches | + | |Underfloor heating|| Magnetic reed switches |
| |- | | |- |
− | | Curtain/gate actuators || Leakage sensors | + | | Curtain/gate actuators ||Leakage sensors |
| |- | | |- |
− | | Water supply/heating valves || | + | |Water supply/heating valves|| |
| |} | | |} |
| | | |
| | | |
| | | |
| + | <!--T:14--> |
| Digital sensors connection port | | Digital sensors connection port |
| | | |
| | | |
| + | <!--T:15--> |
| The digital sensors connection port allows you to connect a variety of digital sensors, such as temperature sensors, ambient light, humidity and other. | | The digital sensors connection port allows you to connect a variety of digital sensors, such as temperature sensors, ambient light, humidity and other. |
| | | |
| | | |
| + | <!--T:16--> |
| Expansion port | | Expansion port |
| | | |
| | | |
| + | <!--T:17--> |
| The expansion port allows you to upgrade the system by connecting auxiliary equipment, such as the control module for LED lighting, dimming, metering devices and other elements. | | The expansion port allows you to upgrade the system by connecting auxiliary equipment, such as the control module for LED lighting, dimming, metering devices and other elements. |
| The package, which is completely ready-to-install, includes the basic hardware and software. | | The package, which is completely ready-to-install, includes the basic hardware and software. |
| | | |
− | ===Package contents=== | + | === Package contents=== <!--T:18--> |
| | | |
| | | |
| + | <!--T:19--> |
| The package comes standard with: | | The package comes standard with: |
| {| class="wikitable" | | {| class="wikitable" |
| |- | | |- |
− | | Mainframe METAFORSA MFC-14.А || 1 pc | + | | Mainframe METAFORSA MFC-14.А||1 pc |
| |- | | |- |
− | | Power supply unit MEANWELL DR-15-12 || 1 pc | + | |Power supply unit MEANWELL DR-15-12||1 pc |
| |- | | |- |
− | | Motion sensor CW-MSD || 3 pcs | + | | Motion sensor CW-MSD||3 pcs |
| |- | | |- |
− | | Leakage sensor FW-WL.A || 2 pcs | + | |Leakage sensor FW-WL.A||2 pcs |
| |- | | |- |
− | | Temperature-sensitive element FW-TS.A || 4 pcs | + | |Temperature-sensitive element FW-TS.A||4 pcs |
| |- | | |- |
− | | Magnetic reed switch (window/door position sensor) || 4 pcs | + | |Magnetic reed switch (window/door position sensor)||4 pcs |
| |- | | |- |
− | | Ethernet-cable noise filter || 1 pc | + | |Ethernet-cable noise filter||1 pc |
| |- | | |- |
− | | Power supply cord || 1 pc | + | | Power supply cord||1 pc |
| |- | | |- |
− | | Manual || 1 pc | + | |Manual||1 pc |
| |} | | |} |
| | | |
− | ===Basic technical specifications of the System=== | + | ===Basic technical specifications of the System=== <!--T:20--> |
| {| class="wikitable" | | {| class="wikitable" |
− | |+ style="text-align:left;" | Table1 | + | |+ style="text-align:left;" |Table1 |
| + | |- |
| + | !Specification!!Meaning |
| |- | | |- |
− | !Specification !! Meaning
| + | | colspan="2" |'''Output ports''' |
| |- | | |- |
− | |colspan="2"|'''Output ports''' | + | |Number of switched channels||10 |
| |- | | |- |
− | | Number of switched channels || 10 | + | |Number of dimming channels|| 4 |
| |- | | |- |
− | | Number of dimming channels || 4 | + | |Commutation voltage||0-250 V AC/DC |
| |- | | |- |
− | | Commutation voltage || 0-250 V AC/DC | + | |Peak load (one channel) ||16A |
| |- | | |- |
− | | Peak load (one channel) || 16A | + | |Peak load (device)||160A |
| |- | | |- |
− | | Peak load (device) || 160A | + | |Max load per dimming channel||0.5A (110W at 220V) |
| |- | | |- |
− | | Max load per dimming channel || 0.5A (110W at 220V) | + | | Max load per PWM outputs||50mA |
| |- | | |- |
− | | Dimmer type || MOSFET | + | |Dimmer type ||MOSFET |
| |- | | |- |
− | | Dimming type || trailing edge | + | |Dimmer load type ||R,C |
| |- | | |- |
− | | Power supply cable connection type || connector | + | |Dimming type|| trailing edge |
| + | |- |
| + | |Power supply cable connection type ||connector |
| |- | | |- |
| |Permissible section of power supply cable to connect in socket:<br>single-conductor cable<br>multiple-conductor cable<br>tipped multiple-conductor cable||<br>0.5 … 4mm2<br>0.5 … 4mm2<br>0.5 … 2.5mm2 | | |Permissible section of power supply cable to connect in socket:<br>single-conductor cable<br>multiple-conductor cable<br>tipped multiple-conductor cable||<br>0.5 … 4mm2<br>0.5 … 4mm2<br>0.5 … 2.5mm2 |
| |- | | |- |
− | |colspan="2"|'''Input ports''' | + | | colspan="2" |'''Input ports''' |
| |- | | |- |
− | |Number of discrete inputs || 24 | + | |Number of discrete inputs||24 |
| |- | | |- |
− | |Number of digital inputs || 4 | + | |Number of digital inputs ||4 |
| |- | | |- |
− | |Current maximum rating on the direct-current voltage connectors || 50mA | + | |Current maximum rating on the direct-current voltage connectors||50mA |
| |- | | |- |
− | |colspan="2"|'''Other''' | + | | colspan="2" |'''Other''' |
| |- | | |- |
− | |Operating ambient temperature || 0 … +45°С | + | |Operating ambient temperature||0 … +45°С |
| |- | | |- |
− | |Storage/transportation temperature || -20 … +60°С | + | |Storage/transportation temperature||-20 … +60°С |
| |- | | |- |
− | |Permissible humidity || 0 … 95% (non-condensing) | + | |Permissible humidity||0 … 95% (non-condensing) |
| |- | | |- |
− | |Supply voltage || 11.5 … 27.5 V DC | + | |Supply voltage||11.5 … 27.5 V DC |
| |- | | |- |
− | |Maximum demand || 1А | + | |Maximum demand||1А |
| |- | | |- |
− | |Available interfaces || Ethernet, CAN, OneWire | + | |Available interfaces||Ethernet, CAN, OneWire |
| |- | | |- |
− | |Bus type || CAN (4-wire) | + | | Bus type||CAN (4-wire) |
| |- | | |- |
− | |CAN (4-wire) || 800 m* (twisted pair 5 cat) | + | |CAN (4-wire)||800 m* (twisted pair 5 cat) |
| |- | | |- |
− | |CAN wire type || FTP Cat 5E | + | | CAN wire type||FTP Cat 5E |
| |- | | |- |
− | |CAN connection type || connector | + | | CAN connection type||connector |
| |- | | |- |
− | |Digital line maximum length || 30 m | + | |Digital line maximum length || 30 m |
| |- | | |- |
− | |Digital line wirde type || UTP/FTP Cat 5E | + | | Digital line wirde type||UTP/FTP Cat 5E |
| |- | | |- |
− | |Digital line connection type || Connector RJ-12 | + | |Digital line connection type||Connector RJ-12 |
| |- | | |- |
− | |LAN maximum length || 100 m | + | |LAN maximum length||100 m |
| |- | | |- |
− | |LAN wire type || UTP/FTP Cat 5E | + | |LAN wire type||UTP/FTP Cat 5E |
| |- | | |- |
− | |LAN connection type || Connector RJ-45 | + | |LAN connection type ||Connector RJ-45 |
| |- | | |- |
− | |Dimensional specifications || 9U, 156x110x58 mm | + | |Dimensional specifications||9U, 156x110x58 mm |
| |- | | |- |
− | |Shell material || ABS plastic | + | |Shell material||ABS plastic |
| |- | | |- |
− | |Casing || IP40 | + | |Casing||IP40 |
| |- | | |- |
− | |Equipment installation type || DIN-rail (EN 60715) | + | |Equipment installation type||DIN-rail (EN 60715) |
| |- | | |- |
− | |Weight || 300 g | + | |Weight ||300 g |
| |} | | |} |
| <nowiki>*</nowiki> – installing additional power supply units is required for long lines; the maximum length of the line may be reduced by various interference factors | | <nowiki>*</nowiki> – installing additional power supply units is required for long lines; the maximum length of the line may be reduced by various interference factors |
| | | |
− | ===General structure of the System=== | + | ===General structure of the System === <!--T:21--> |
| | | |
| | | |
| + | <!--T:22--> |
| Module general view is shown in '''fig. 1''' | | Module general view is shown in '''fig. 1''' |
| | | |
| | | |
| + | <!--T:23--> |
| [[File:Mfc14.ch.png|700px|frameless|left|Fig. 1 Module general view]] | | [[File:Mfc14.ch.png|700px|frameless|left|Fig. 1 Module general view]] |
| <br> | | <br> |
| {| class="wikitable" style="clear:left;" | | {| class="wikitable" style="clear:left;" |
| |- | | |- |
− | |1 || — connector for load application and power supply | + | |1||— connector for load application |
| |- | | |- |
− | |2 || — connector for dimming-lamps application | + | |2||— connector for dimming-lamps application |
| |- | | |- |
− | |3 || — power connector | + | |3||— power connector |
| |- | | |- |
− | |4 || — Ethernet network connector | + | |4||— Ethernet network connector |
| |- | | |- |
− | |5-6 || — connectors for digital sensors and buttons/switching units | + | |5-6||— connectors for digital sensors and buttons/switching units |
| |- | | |- |
− | |7 || — OneWire interface connector (for digital sensors) | + | |7||— OneWire interface connector (for digital sensors) |
| |- | | |- |
− | |8 || — connector for expansion module. | + | |8||— connector for expansion module. |
| |} | | |} |
| | | |
| | | |
| + | <!--T:24--> |
| '''Overview of the METAFORSA device external connectors:''' | | '''Overview of the METAFORSA device external connectors:''' |
| At the top of the casing ('''fig. 1''') there is: | | At the top of the casing ('''fig. 1''') there is: |
| | | |
| | | |
| + | <!--T:25--> |
| *connector (1) — Devices connection; | | *connector (1) — Devices connection; |
| *connector (2) — Dimming lamps connection; | | *connector (2) — Dimming lamps connection; |
| | | |
| | | |
| + | <!--T:26--> |
| At the bottom of the casing ('''fig. 1''') there is: | | At the bottom of the casing ('''fig. 1''') there is: |
| | | |
| | | |
| + | <!--T:27--> |
| *connector (3) — module power supply connection; | | *connector (3) — module power supply connection; |
| *connector (4) — Ethernet network connection; | | *connector (4) — Ethernet network connection; |
Line 256: |
Line 288: |
| | | |
| | | |
| + | <!--T:28--> |
| {| class="wikitable" | | {| class="wikitable" |
− | |+ text-align="left"|'''Table2''' | + | |+ text-align="left" |'''Table2''' |
| |- | | |- |
− | !Connector!!Contact!!Assignment | + | !Connector!!Contact !!Assignment |
| |- | | |- |
− | |[[File:Out.png|80px|frameless]] ||1-10|| Load application (light lamps, thermal actuators, etc.) | + | |[[File:Out.png|80px|frameless]]||1-10 ||Load application (light lamps, thermal actuators, etc.) |
| |- | | |- |
− | |[[File:Dimm.png|80px|frameless]] ||D1-4, L, N|| Load application (dimming lamps) | + | |[[File:Dimm.png|80px|frameless]]||D1-4, L, N||Load application (dimming lamps) |
| |- | | |- |
− | | colspan="2"| Device status indicators || The module status indicators are described in '''table 3''' | + | | colspan="2" |Device status indicators||The module status indicators are described in '''table 3''' |
| |- | | |- |
− | |[[File:24vconn.png|80px|frameless]] ||+24V<br>GND|| +24V — module power supply by an external 24 V power supply GND — common | + | |[[File:24vconn.png|80px|frameless]]||+24V<br>GND|| +24V — module power supply by an external 24 V power supply GND — common |
| |- | | |- |
− | |[[File:Rj45.jpg|80px|frameless]] ||RJ45|| Connector for LAN connectivity | + | |[[File:Rj45.jpg|80px|frameless]]||RJ45|| Connector for LAN connectivity |
| |- | | |- |
− | |[[File:Inputs.png|80px|frameless]] ||In1-12, In13-24 GND|| Controlling devices connection (buttons, magnetic reed switches, motion or leakage sensors): +12V — sensor power output +12 V<br>In1 … In24 — logic inputs (0-12 V)<br>GND — common | + | |[[File:Inputs.png|80px|frameless]]||In1-12, In13-24 GND||Controlling devices connection (buttons, magnetic reed switches, motion or leakage sensors): +12V — sensor power output +12 V<br>In1 … In24 — logic inputs (0-12 V)<br>GND — common |
| |- | | |- |
− | |[[File:OW.png|80px|frameless]] ||OneWire|| Digital sensors connection (temperature)<br>VCC — sensors power supply output +5V<br>OW1-OW4 — OneWire data buses<br>GND — common | + | |[[File:OW.png|80px|frameless]]||OneWire ||Digital sensors connection (temperature)<br>VCC — sensors power supply output +5V<br>OW1-OW4 — OneWire data buses<br>GND — common |
| |- | | |- |
− | |[[File:Can.jpg|80px|frameless]] ||VCC<br>GND<br>L<br>H|| External modules connection for CAN-bus<br>VСС — 12V output for external devices power supply<br>GND — common<br>L — CAN-L data bus<br>H — CAN-H data bus | + | |[[File:Can.jpg|80px|frameless]]||VCC<br>GND<br>L<br>H||External modules connection for CAN-bus<br>VСС — 12V output for external devices power supply<br>GND — common<br>L — CAN-L data bus<br>H — CAN-H data bus |
| |} | | |} |
| | | |
| + | <!--T:29--> |
| {{Indicationmf}} | | {{Indicationmf}} |
| | | |
− | ===System installation and assembly=== | + | ===System installation and assembly=== <!--T:30--> |
| Before connecting the system, you must: | | Before connecting the system, you must: |
| | | |
| | | |
| + | <!--T:31--> |
| *site the sensor and actuators (if not pre-installed), set the sensors and actuators; | | *site the sensor and actuators (if not pre-installed), set the sensors and actuators; |
| *site the module and power supply. | | *site the module and power supply. |
| | | |
| | | |
| + | <!--T:32--> |
| '''Note: The module must be installed near the power supply voltage source.''' | | '''Note: The module must be installed near the power supply voltage source.''' |
| | | |
| | | |
| + | <!--T:33--> |
| <div class="cautoin">CAUTION! | | <div class="cautoin">CAUTION! |
| AC power voltage must be provided to the system input through the circuit breaker assembly. It should be installed close to the power supply.</div> | | AC power voltage must be provided to the system input through the circuit breaker assembly. It should be installed close to the power supply.</div> |
Line 297: |
Line 334: |
| | | |
| | | |
| + | <!--T:34--> |
| Typical diagram of METAFORSA MFC-14.A module connection is shown in '''fig. 3.''' | | Typical diagram of METAFORSA MFC-14.A module connection is shown in '''fig. 3.''' |
| <div style="clear: both">[[File:Mfc14chcon.png|700px|Fig. 3]]</div> | | <div style="clear: both">[[File:Mfc14chcon.png|700px|Fig. 3]]</div> |
| | | |
| | | |
| + | ===Connection of the actuators=== <!--T:35--> |
| | | |
− | ===Connection of the actuators===
| |
| | | |
| + | ====Connection of the lights/electric contactor/heating thermal actuator==== <!--T:36--> |
| | | |
− | | + | <!--T:37--> |
− | ====Connection of the lights/electric contactor/heating thermal actuator====
| + | {| class="wikitable" style="width:800px" ; |
− | | |
− | {| class="wikitable" style="width:800px"; | |
| |- | | |- |
− | |[[File:lamps.png|350px|lamp]]<br>'''Fig. 4'''|| style="margin:20px"|Such actuators as light, electric contactor, heating thermal actuator should be switched on any of the outputs 1 – 10, the neutral wire and the ground wire should be connected directly to the switchboard. The example of connection is shown in '''Fig.4'''. | + | |[[File:lamps.png|350px|lamp]]<br>'''Fig. 4'''|| style="margin:20px" |Such actuators as light, electric contactor, heating thermal actuator should be switched on any of the outputs 1 – 10, the neutral wire and the ground wire should be connected directly to the switchboard. The example of connection is shown in '''Fig.4'''. |
| |} | | |} |
| | | |
| | | |
| + | ====Connection of high load device==== <!--T:38--> |
| | | |
− | ====Connection of high load device====
| + | <!--T:39--> |
− | | + | {| class="wikitable" style="width:800px" ; |
− | {| class="wikitable" style="width:800px"; | |
| |- | | |- |
− | |[[File:Contactor.png|350px|Contactor]]|| style="margin:20px"|Recomended contactors: | + | |[[File:Contactor.png|350px|Contactor]]|| style="margin:20px" |Recomended contactors: |
| *ABB ESB series | | *ABB ESB series |
| *Schneider Acti 9 iCT series | | *Schneider Acti 9 iCT series |
Line 326: |
Line 363: |
| | | |
| | | |
| + | ====Connection of single-pole water/gas supply valve==== <!--T:40--> |
| | | |
− | ====Connection of single-pole water/gas supply valve====
| + | <!--T:41--> |
− | | + | {| class="wikitable" style="width:800px" ; |
− | {| class="wikitable" style="width:800px"; | |
| |- | | |- |
− | |colspan="2" style="background-color:#dededf" |'''Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.''' | + | | colspan="2" style="background-color:#dededf" |'''Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.''' |
| |- | | |- |
− | |[[File:1pvalve.png|350px|valve]]<br>'''Fig. 5'''|| style="margin:20px"|The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in '''Fig.5'''. | + | |[[File:1pvalve.png|350px|valve]]<br>'''Fig. 5'''|| style="margin:20px" | The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in '''Fig.5'''. |
| |} | | |} |
| | | |
| | | |
| + | ====Connection of double-pole water/gas supply valve==== <!--T:42--> |
| | | |
− | ====Connection of double-pole water/gas supply valve====
| + | <!--T:43--> |
− | | + | {| class="wikitable" style="width:800px" ; |
− | {| class="wikitable" style="width:800px"; | |
| |- | | |- |
− | |colspan="2" style="background-color:#dededf" |'''Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.''' | + | | colspan="2" style="background-color:#dededf" |'''Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.''' |
| |- | | |- |
− | |[[File:2pvalve.png|350px|valve]]<br>'''Fig. 6'''|| style="margin:20px"|Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in '''Fig.6'''. | + | |[[File:2pvalve.png|350px|valve]]<br>'''Fig. 6'''|| style="margin:20px" |Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in '''Fig.6'''. |
| |} | | |} |
| | | |
| | | |
| + | ==== Connection of single-pole gate actuator==== <!--T:44--> |
| | | |
− | ====Connection of single-pole gate actuator====
| + | <!--T:45--> |
− | | |
| {{ConExC | | {{ConExC |
| |Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire. | | |Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire. |
Line 357: |
Line 394: |
| | | |
| | | |
| + | ====Connection of double-pole gate actuator==== <!--T:46--> |
| | | |
− | ====Connection of double-pole gate actuator====
| + | <!--T:47--> |
− | | |
| {{ConExC | | {{ConExC |
| |Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. | | |Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. |
Line 366: |
Line 403: |
| | | |
| | | |
| + | ====Connection of curtain/jalousie/shutter actuator with 220V force control==== <!--T:48--> |
| | | |
− | ====Connection of curtain/jalousie/shutter actuator with 220V force control====
| + | <!--T:49--> |
− | | |
| {{ConExC | | {{ConExC |
| |Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. | | |Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. |
Line 375: |
Line 412: |
| | | |
| | | |
| + | ====Connection of curtain/jalousie/shutter actuator with low-voltage control ==== <!--T:50--> |
| | | |
− | ====Connection of curtain/jalousie/shutter actuator with low-voltage control====
| + | <!--T:51--> |
− | | |
| {{ConExC | | {{ConExC |
| |Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. | | |Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire. |
Line 383: |
Line 420: |
| }} | | }} |
| | | |
− | ===Connection of sensing elements/switches/buttons=== | + | ===Connection of sensing elements/switches/buttons=== <!--T:52--> |
| | | |
− | ====Connection of motion sensors==== | + | ====Connection of motion sensors==== <!--T:53--> |
| | | |
| + | <!--T:54--> |
| The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in '''Fig.11'''. | | The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in '''Fig.11'''. |
| | | |
| + | <!--T:55--> |
| [[File:msConn.png|300px|ms]] | | [[File:msConn.png|300px|ms]] |
| <br> | | <br> |
Line 394: |
Line 433: |
| | | |
| | | |
− | ====Connection of FW-WL.A leakage sensors==== | + | ====Connection of FW-WL.A leakage sensors ==== <!--T:56--> |
| | | |
| + | <!--T:57--> |
| FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in '''fig. 12'''. | | FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in '''fig. 12'''. |
− | {| style="width"700px" | + | {| style="width" 700px" |
| |- style="tezt-align:center;" | | |- style="tezt-align:center;" |
| |[[File:Leak1.png|300px|center]]<br>'''Fig12'''||[[File:Leak2.png|300px|center]]<br>'''Fig13''' | | |[[File:Leak1.png|300px|center]]<br>'''Fig12'''||[[File:Leak2.png|300px|center]]<br>'''Fig13''' |
| |} | | |} |
| | | |
| + | <!--T:58--> |
| Configuration and connection of the FW-WL.A sensor | | Configuration and connection of the FW-WL.A sensor |
| 1. Terminals: | | 1. Terminals: |
Line 409: |
Line 450: |
| 2. Sensor preset switch (optionally): | | 2. Sensor preset switch (optionally): |
| :1 — sensor sensitivity (ON – high, OFF – low); | | :1 — sensor sensitivity (ON – high, OFF – low); |
− | :2 — indicator colour setting (ON – blue, OFF – green). | + | : 2 — indicator colour setting (ON – blue, OFF – green). |
| 3. LED status indicator. | | 3. LED status indicator. |
| | | |
− | ====Connection of buttons/switches/magnetic reed switches==== | + | ====Connection of buttons/switches/magnetic reed switches ==== <!--T:59--> |
| | | |
− | Buttons and reed switches are connected to any free input in1-in16, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in '''Fig. 14-16'''. | + | <!--T:60--> |
− | {| style="width"700px" | + | Buttons and reed switches are connected to any free input in1-in24, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in '''Fig. 14-15'''. |
| + | {| style="width" 700px" |
| |- style="tezt-align:center;" | | |- style="tezt-align:center;" |
− | |[[File:Buttons.png|300px|center]]<br>'''Fig14''' connection of buttons/switching units || [[File:Reed-sv.png|300px|center]]<br>'''Fig15''' connection of the magnetic reed switches (window/door position sensors) | + | |[[File:Buttons.png|300px|center]]<br>'''Fig14''' connection of buttons/switching units||[[File:Reed-sv.png|300px|center]]<br>'''Fig15''' connection of the magnetic reed switches (window/door position sensors) |
| |} | | |} |
| | | |
| + | ====Connection of digital sensors==== <!--T:61--> |
| | | |
− | ====Connection of digital sensors====
| + | <!--T:62--> |
− | | |
| The OW adapter ('''Fig. 16a''') is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel ('''Fig. 16b'''). The connected sensors are detected automatically and do not require any original setting. | | The OW adapter ('''Fig. 16a''') is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel ('''Fig. 16b'''). The connected sensors are detected automatically and do not require any original setting. |
| | | |
− | {| style="width"700px" | + | <!--T:63--> |
| + | {| style="width" 700px" |
| |- style="tezt-align:center;" | | |- style="tezt-align:center;" |
| |[[File:Ow1Conn.png|300px|center]]<br>'''Fig16 a'''||[[File:Ow2Conn.png|300px|center]]<br>'''Fig16 b''' | | |[[File:Ow1Conn.png|300px|center]]<br>'''Fig16 a'''||[[File:Ow2Conn.png|300px|center]]<br>'''Fig16 b''' |
Line 432: |
Line 475: |
| <div style="width:700px; background-rgb:#dededf">'''Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction. '''</div> | | <div style="width:700px; background-rgb:#dededf">'''Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction. '''</div> |
| | | |
− | ===Connection of RGB and LED.=== | + | ===Connection of RGB and LED. === <!--T:64--> |
| | | |
| + | <!--T:65--> |
| MFC has new function – switching inputs to LED outputs (in15-in18; in21-in24). | | MFC has new function – switching inputs to LED outputs (in15-in18; in21-in24). |
| [[File:MFC RGB CONNECT.png|700px]] | | [[File:MFC RGB CONNECT.png|700px]] |
| | | |
| + | <!--T:66--> |
| HW example for this configuration:<br> | | HW example for this configuration:<br> |
− | <syntaxhighlight lang="xml" line>hw="in='--------------RRRR--RRRR' rgb='RGBLLLLL'"</syntaxhighlight> | + | <syntaxhighlight lang="xml" line="">hw="in='--------------RRRR--RRRR' rgb='RGBLLLLL'"</syntaxhighlight> |
| | | |
| | | |
− | ===Connection of auxiliary equipment.=== | + | ===Connection of auxiliary equipment.=== <!--T:67--> |
| | | |
| + | <!--T:68--> |
| Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in '''Table 4.''' The example of connection is shown in '''Fig. 17'''. | | Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in '''Table 4.''' The example of connection is shown in '''Fig. 17'''. |
| | | |
| + | <!--T:69--> |
| {| class="wikitable" style="width:700px" | | {| class="wikitable" style="width:700px" |
| |- | | |- |
| |[[File:Canex.png|700px]] | | |[[File:Canex.png|700px]] |
| |- | | |- |
− | |style="background-color:#dededf"|'''Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.''' | + | | style="background-color:#dededf" |'''Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.''' |
| |} | | |} |
| | | |
− | ===Module installation and connection procedure=== | + | ===Module installation and connection procedure=== <!--T:70--> |
− | <div style="width:700px; background-color:#dededf">''' | + | <div style="width:700px; background-color:#dededf"> |
− | ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.'''</div> | + | ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.</div> |
| | | |
− | #Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base. | + | <!--T:71--> |
| + | # Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base. |
| #Fasten the supply unit on the left side of the module. | | #Fasten the supply unit on the left side of the module. |
− | #Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module. | + | # Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module. |
| #Connect the connectors (5), (6). | | #Connect the connectors (5), (6). |
| #Connect the connectors (1), (2). | | #Connect the connectors (1), (2). |
Line 465: |
Line 513: |
| #Wait until the module is loaded, then configure it in accordance with the '''System Setup Instructions.''' | | #Wait until the module is loaded, then configure it in accordance with the '''System Setup Instructions.''' |
| #Apply power to the connectors (1), (2). | | #Apply power to the connectors (1), (2). |
− | #Check all equipment for proper operation. | + | # Check all equipment for proper operation. |
| | | |
− | ===METAFORSA module shut-off and deinstallation procedure=== | + | ===METAFORSA module shut-off and deinstallation procedure=== <!--T:72--> |
| | | |
− | #De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit. | + | <!--T:73--> |
| + | # De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit. |
| #Disconnect the load power supply connectors (1), (2). | | #Disconnect the load power supply connectors (1), (2). |
| #Disconnect the connector (3). | | #Disconnect the connector (3). |
Line 475: |
Line 524: |
| #Remove the module from the DIN-rail, releasing the latch at the bottom of the module base. | | #Remove the module from the DIN-rail, releasing the latch at the bottom of the module base. |
| | | |
− | ==Hardware setup== | + | ==Hardware setup== <!--T:74--> |
| | | |
| + | <!--T:75--> |
| To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in [https://itunes.apple.com/us/app/larnitech/id1108457530?mt=8 App Store] and [https://play.google.com/store/apps/details?id=com.larnitech Play Market]. After installation, follow the '''System Setup Instructions'''. | | To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in [https://itunes.apple.com/us/app/larnitech/id1108457530?mt=8 App Store] and [https://play.google.com/store/apps/details?id=com.larnitech Play Market]. After installation, follow the '''System Setup Instructions'''. |
| | | |
− | ==Fault diagnostics and handling== | + | ==Fault diagnostics and handling== <!--T:76--> |
| | | |
| + | <!--T:77--> |
| The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [http://www.larnitech.com/support/] or [support@larnitech.com]. | | The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [http://www.larnitech.com/support/] or [support@larnitech.com]. |
| There are also some tips in the FAQ section at our website [http://www.larnitech.com/faq/]. | | There are also some tips in the FAQ section at our website [http://www.larnitech.com/faq/]. |
| | | |
− | ===The actuators do not operate:=== | + | ===The actuators do not operate: === <!--T:78--> |
| | | |
| + | <!--T:79--> |
| *ensure the outputs are properly configured in the application (see '''System Setup Instructions'''); | | *ensure the outputs are properly configured in the application (see '''System Setup Instructions'''); |
| *check the connection is correct in accordance with '''table 2 and''' paragraph 3.6; | | *check the connection is correct in accordance with '''table 2 and''' paragraph 3.6; |
Line 491: |
Line 543: |
| *verify the operability of the connected equipment. | | *verify the operability of the connected equipment. |
| | | |
− | ===The module is off, indication absent:=== | + | ===The module is off, indication absent:=== <!--T:80--> |
| | | |
| + | <!--T:81--> |
| *check the connection to 24V supply unit as shown in '''table 2''' (contacts pin assignment); | | *check the connection to 24V supply unit as shown in '''table 2''' (contacts pin assignment); |
| *check the connection of the supply unit to 220V power mains, the indicator should be ON. | | *check the connection of the supply unit to 220V power mains, the indicator should be ON. |
| | | |
− | ===Network connection fault:=== | + | ===Network connection fault:=== <!--T:82--> |
| | | |
| + | <!--T:83--> |
| *ensure the Ethernet cable is properly wired and connected to the connector; | | *ensure the Ethernet cable is properly wired and connected to the connector; |
| *ensure the LED status indicators are ON on the Ethernet connector; | | *ensure the LED status indicators are ON on the Ethernet connector; |
Line 503: |
Line 557: |
| *METAFORSA module and the device you are connecting from are in the same network. | | *METAFORSA module and the device you are connecting from are in the same network. |
| | | |
| + | <!--T:84--> |
| hold integer 0-10000 1-10 by default hold is the same as runtime | | hold integer 0-10000 1-10 by default hold is the same as runtime |
| hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500 | | hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500 |
| | | |
| | | |
− | ===The sensors do not operate:=== | + | ===The sensors do not operate:=== <!--T:85--> |
| | | |
− | *ensure the inputs are properly configured in the application ('''System Setup Instructions'''); | + | <!--T:86--> |
| + | * ensure the inputs are properly configured in the application ('''System Setup Instructions'''); |
| *check the connection is correct in accordance with '''table 2''' and paragraph 3.7; | | *check the connection is correct in accordance with '''table 2''' and paragraph 3.7; |
| *ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – '''table 3'''; | | *ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – '''table 3'''; |
| *check the power supply availability on the sensors; | | *check the power supply availability on the sensors; |
− | *check the integrity of lines laid to the sensors. | + | * check the integrity of lines laid to the sensors. |
| | | |
− | ===The auxiliary equipment does not operate:=== | + | ===The auxiliary equipment does not operate:=== <!--T:87--> |
− | *check the connection is correct in accordance with table 2 and paragraph 3.8-9; | + | * check the connection is correct in accordance with table 2 and paragraph 3.8-9; |
− | *ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3; | + | * ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3; |
| *check the integrity of the CAN lines, voltage supply on the modules. | | *check the integrity of the CAN lines, voltage supply on the modules. |
| | | |
| | | |
− | ==HW Settings== | + | == HW Settings== <!--T:88--> |
| {| class="wikitable" | | {| class="wikitable" |
| |- | | |- |
− | !Name!!Type, range!!SUBID!!Default!!Description | + | !Name!!Type, range!!SUBID!!Default!! Description |
| |- | | |- |
− | |runtime||integer 0-100 || 1-10 || 15 ||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); | + | |runtime ||integer 0-100||1-10||15||runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole); |
| <br>Example: runtime=15 | | <br>Example: runtime=15 |
| |- | | |- |
− | |runtimeopen||integer 0-60000||Blinds subId || ||Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000 | + | |runtimeopen|| integer 0-60000||Blinds subId|| || Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000 |
| |- | | |- |
| |runtimeclose||integer 0-60000||Blinds subId|| ||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000 | | |runtimeclose||integer 0-60000||Blinds subId|| ||Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000 |
| |- | | |- |
− | |hold||integer 0-10000||1-10||500||hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500 | + | |hold||integer 0-10000||1-10 || 500||hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500 |
| |- | | |- |
− | |def||string 'ON'||1-10||'OFF'||def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON' | + | | def||string 'ON'||1-10|| 'OFF' || def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON' |
| |- | | |- |
| |stop||Char ‘R’||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’ | | |stop||Char ‘R’||1-7||–||(for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’ |
| |- | | |- |
− | |out||char[10]||98||'LLLLHHHHP-'||Each char is responsible for the type of a particular channel | + | |out||char[10] || 98|| 'LLLLHHHHP-'||Each char is responsible for the type of a particular channel |
| *'L'-Lamp; | | *'L'-Lamp; |
| *'M'-Lamp Inverse; | | *'M'-Lamp Inverse; |
Line 549: |
Line 605: |
| *'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close; | | *'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close; |
| *'X'-Gate (1 pole /short press), 1 pole gate; | | *'X'-Gate (1 pole /short press), 1 pole gate; |
− | *'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close; | + | * 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close; |
| *'V'-Valve (2 pole), 2 pole valve; | | *'V'-Valve (2 pole), 2 pole valve; |
| *'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close; | | *'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close; |
| *'R'-Valve (1 pole), 1 pole valve,; | | *'R'-Valve (1 pole), 1 pole valve,; |
− | *'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close; | + | * 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close; |
− | *'K'-Lock (short press); | + | * 'K'-Lock (short press); |
| *'N'-Lock (short press) Inverse; | | *'N'-Lock (short press) Inverse; |
| *'P'-Blinds (2 pole); | | *'P'-Blinds (2 pole); |
| *'O'-Blinds Inverse (2 pole), invert open-close; | | *'O'-Blinds Inverse (2 pole), invert open-close; |
− | *'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control; | + | * 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control; |
| *'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control; | | *'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control; |
| *'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control; | | *'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control; |
Line 571: |
Line 627: |
| *‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately | | *‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately |
| *‘l’ – LED Function, dimmable LED lamps | | *‘l’ – LED Function, dimmable LED lamps |
− | *‘v’ – linear Function of dimming | + | * ‘v’ – linear Function of dimming |
| *‘-‘ – Channel disabled | | *‘-‘ – Channel disabled |
| *‘+’ – Regular channel | | *‘+’ – Regular channel |
| Example: dm=’skl-‘ | | Example: dm=’skl-‘ |
| |- | | |- |
− | |def||integer 0-250||11-14||100||The default brightness level in case of a power reset (1..250). Example: def=250 | + | |def||integer 0-250||11-14||100|| The default brightness level in case of a power reset (1..250). Example: def=250 |
| |- | | |- |
− | |min||integer 0-100||11-14||0||Minimum dimming level, example: min=10 | + | |min||integer 0-100 ||11-14||0||Minimum dimming level, example: min=10 |
| |- | | |- |
− | |max||integer 0-100||11-14||100||Maximum dimming level, example max=95 | + | |max||integer 0-100 ||11-14||100||Maximum dimming level, example max=95 |
| |- | | |- |
| |start||integer 0-100||11-14||0||The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60 | | |start||integer 0-100||11-14||0||The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60 |
Line 586: |
Line 642: |
| |force||integer 0-100||11-14||10||Time duration of the starting value (measured in milliseconds). Example: force=20 | | |force||integer 0-100||11-14||10||Time duration of the starting value (measured in milliseconds). Example: force=20 |
| |- | | |- |
− | |runtime||integer 0-60000||11-14||1000||Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000 | + | |runtime||integer 0-60000|| 11-14||1000 || Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000 |
| |- | | |- |
− | |offset||integer (+/- 0…39)||39-46||'0'||sensor values offset; For example, offset is -3.8 : | + | |offset||integer (+/- 0…39)||39-46 ||'0'||sensor values offset; For example, offset is -3.8 : |
| Example: hw="offset='-3.8'" | | Example: hw="offset='-3.8'" |
| |- | | |- |
− | |in||char[24]||98||'BBBBBBBBBBBBMMMLLLKKKKKK'||Each char is responsible for the type of a particular channel | + | |in|| char[24]||98||'BBBBBBBBBBBBMMMLLLKKKKKK'||Each char is responsible for the type of a particular channel |
| *'B'-Button; | | *'B'-Button; |
| *'C'-nButton; | | *'C'-nButton; |
| *'S'-Switch; | | *'S'-Switch; |
− | *'K'-Contact; | + | * 'K'-Contact; |
− | *'H'-nContact; | + | * 'H'-nContact; |
| *‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor | | *‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor |
| *‘N’-Third party leakage sensor; | | *‘N’-Third party leakage sensor; |
− | *'M'-Motion, motion sensor; | + | * 'M'-Motion, motion sensor; |
| *'V'-nMotion, motion sensor; | | *'V'-nMotion, motion sensor; |
| *'R' (avaliable on in15-in18; in21-in24) LED outputs | | *'R' (avaliable on in15-in18; in21-in24) LED outputs |
Line 615: |
Line 671: |
| |} | | |} |
| | | |
− | <syntaxhighlight lang="xml" line> | + | <!--T:89--> |
| + | <syntaxhighlight lang="xml" line=""> |
| <item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> | | <item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> |
| <item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> | | <item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> |
Line 648: |
Line 705: |
| <item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/> | | <item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/> |
| </syntaxhighlight> | | </syntaxhighlight> |