Translations:Fancoil/3/en

From Larnitech wiki page
Jump to navigation Jump to search
Name type and variety description default value
temperature-sensors list list of valve temperature sensors (for automation) -
automation string name of current automation mode -
valve string (addr) addr of valve -
valve-heating string (addr) addr of heating valve -
valve-cooling string (addr) addr of cooling valve -
temperature-lag number hysteresis range on either side from set-point temperature Set in automation tag. The decimal symbol is dot. 0.5
undefined-behavior 0-250/on/off/last fancoil position in case of sensors readings absence (off – 0; on – 250) last
P0 0-100 minimal power for turning on fan last
mode heat/cool heat/cool mode heat
alg string eco/fast/boost alg -
heat-carrier string (addr) temperature sensor of heat carrier -
limit-fan number(0-250) max power -
ctrl-change1 number(0-250) min level of power change (one time per “ctrl-ticks” attr) if defined 5
ctrl-change2 number(0-250) min level of power change -
ctrl-ticks number(0-3825) power change by "ctrl-change1" timeout -