Translations:Fancoil/9/en
Jump to navigation
Jump to search
Byte number | Bit number | Description |
---|---|---|
0 | 0 1 2 3 4-7 |
On/Off Cooling/Heating Fan On/Off Boost On/Off Integration algorithm (slow,medium,fast,boost) |
1-2 | 8-23 | T set (<-100 - no automation) |
3-4 | 24-39 | T cur (<-100 - no automation or undefined all T sensors) |
5 | 40-43 44-47 |
Current automation time interval index Current automation index |
6 | 48-55 | Current fan level (0-250) |
7 | 56 57 58 59 60 61 62 63 |
Error: Has undefined T sensor(s) Error: Has no any defined T sensor Error: valve state is undefined Error: reverse valve is on Error: heat transfer sensor is undefined or has bad level Error: low power for accessing setpoint Error: fan state is undef Reserved |