{| class="wikitable"
|+ text-align="left"|'''Table2'''
|-
!Connector!!Contact!! style="width:300px" |Assignment
|-
|1, 3<br>[[File:mf10l.jpg|80px|frameless]] ||L1-2 L3-4|| Phase conductor connection for C1-C8 channels load switching
|-
|2, 4<br>[[File:mf10out.jpg|80px|frameless]] ||C1-4 C5-8|| Load application (light lamps, thermal actuators, etc.)
|-
|5<br>[[File:mf10out2.jpg|80px|frameless]] || С9 L5 С10|| Connection of curtain/jalousie/shutter actuators, valve, lamps, gate controllers, etc.: С9, С10 — outputs for load application L5 — connection of group phase supply wire
|-
| colspan="2"| 6<br>Device status indicators || The module status indicators are described in '''table 3'''
|-
|7<br>[[File:mf10power.jpg|80px|frameless]] ||+12V GND|| +12V — module power supply by an external 12 V power supply GND — common
|-
|8<br>[[File:Rj45.jpg|80px|frameless]] ||RJ45|| Connector for LAN connectivity
|-
|9-12<br>[[File:mf10in.jpg|80px|frameless]] ||+12V In1 … In16 GND||Controlling devices connection (buttons, magnetic reed switches, motion or leakage sensors): +12V — sensor power output +12 V In1 … In16 — logic inputs (0-12 V) GND — common
|-
|13<br>[[File:mf10ow.jpg|80px|frameless]] ||OneWire|| Digital sensors connection (temperature) VCC — sensors power supply output +5V OW1-OW4 — OneWire data buses GND — common
|-
|14<br>[[File:Can.jpg|80px|frameless]] ||VCC<br>GND<br>L<br>H|| External modules connection for CAN-bus VСС — 12V output for external devices power supply GND — common L — CAN-L data bus H — CAN-H data bus
|}