==HW settings==
{|class="wikitable"
|-
!Name!!Type, range!!SUBID!!Default!!Description
|-
|io||char[6]||98||'HHHLLL'||Each char is responsible for the type of a particular channel
*1-3 channels
**'H' – Contact
**'K' – Inverted contact
**'L' – Backlit button
**'M' – Inverted backlit button
*4-6 channels
**'L'-Lamp
**'M'-Lamp Inverse;
**'J'-Heating NO, valve-heating, normally open;
**'H'-Heating NC, valve-heating, normally closed;
**'B'-Blinds, jalousie/curtains(2 pole);
**'C'-Blinds Inverse, jalousie/curtains, invert open-close(2 pole);
**'G'-Gate (2 pole), 2 pole gate;
**'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
**'X'-Gate (1 pole /short press), 1 pole gate;
**'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
**'V'-Valve (2 pole), 2 pole valve,;
**'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
**'R'-Valve (1 pole), 1 pole valve;
**'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
**'K'-Lock (short press);
**'N'-Lock (short press) Inverse;
**'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
**'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
**'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
**'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
**'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
**'-'-none, nothing is connected.
Example:
<syntaxhighlight lang="xml" line>
hw="io='KKKLLL'"
</syntaxhighlight>
|}