Metaforsa2 MF-14

Revision as of 08:08, 4 March 2024 by Support (talk | contribs) (Created page with "====Conexión de la válvula unipolar de suministro de agua/gas====")
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF-14
Metaforsa2.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs24
Number of digital inputs4
General
Max CAN devices50
Max CAN bus length800 m (twisted pair 5 cat)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


Introducción

El Manual de Instalación de METAFORSA SMART HOUSE describe el procedimiento para su instalación, montaje, funcionamiento y configuración. Mientras trabaja con el sistema, debe cumplir estrictamente con todos los requisitos establecidos en este manual. El incumplimiento puede provocar daños al dispositivo, fallos, descargas eléctricas, incendios y otras consecuencias. El fabricante se reserva el derecho de realizar cambios en este manual sin previo aviso. Este manual es una parte integral del sistema y permanecerá en manos del cliente final.

Características

  • 10 salidas universales compatibles:
    • Luces
    • Válvulas de calefacción NC/NO
    • Persianas
    • Puertas de 1 o 2 polos
    • Válvulas de 1 o 2 polos
    • Cerraduras NC/NO
    • Unidades fancoil
  • 4 salidas de atenuación
  • 24 entradas discretas que soportan:
    • Botones
    • Interruptores
    • interruptores de láminas
    • sensores de fugas
    • detectores de movimiento
  • 4 entradas digitales para hasta 8 sensores de temperatura
  • Puerto de extensión
  • Relés con contactos AgSnO2 clasificados para corriente de entrada de 80 A y 20 ms
  • Conexión a la nube y control de todos los sistemas de la casa.
  • Control por voz (Siri, Alexa, Google Home)
  • El motor de complementos permite ampliar las posibilidades del sistema (por ejemplo, integración con luces Satel, Philips Hue, IKEA)
  • Seguridad contra intrusiones no autorizadas garantizada con cifrado RSA/AES256
  • Notificaciones push del sistema en su teléfono (también es posible recibirlas a través de mensajeros de Telegram y Viber)
  • Historial (se almacenan los datos del medidor durante 1 año)
  • Plug and play (posibilidad de ampliación del sistema rápida y fácil de usar)
  • Actualizaciones periódicas del sistema
  • Gran base de datos de scripts constantemente actualizada para satisfacer todas sus necesidades
  • Copias de seguridad diarias automáticas vía nube con posibilidad de restaurar la configuración inicial
  • API abierta (que permite integrar Larnitech a otros sistemas)
  • Interfaz web LT SETUP interactiva y fácil de usar disponible para configuración avanzada
  • Conecta y reproduce
  • Es un kit de sistema Smart Home completamente listo para instalar.

Requisitos de seguridad

'¡PRECAUCIÓN! Todos los trabajos relacionados con la instalación, conexión, configuración, servicio y soporte deben ser realizados por personal calificado con suficientes habilidades y experiencia en el trabajo con equipos eléctricos.

Para evitar el riesgo de incendio, descarga eléctrica, daños al sistema y/o lesiones personales, la instalación y el montaje del sistema deben realizarse de acuerdo con las instrucciones que se enumeran a continuación:


  • todos los trabajos de conexión deben realizarse sin energía eléctrica;
  • utilizar herramientas adecuadas y protección personal contra descargas eléctricas;
  • no utilice cables, alambres ni conectores dañados;
  • evitar el plegado de cables y alambres;
  • No pellizque ni doble los cables aplicando fuerza excesiva. De lo contrario, los conductores internos del cable y los alambres podrían pelarse o romperse;
  • no utilice una toma de corriente con malos contactos para realizar la conexión;
  • no exceda el límite de parámetros de carga especificados en este manual;
  • La sección de los cables de los conductores de alimentación está sujeta a las especificaciones de límite de densidad de corriente, tipo de aislamiento y material del cable. La sección ligera puede provocar un sobrecalentamiento del cable y un incendio.


Al trabajar con el sistema después del suministro de voltaje NUNCA:

  • realizar conexión/desconexión de conectores;
  • abrir módulos y sensores.

Configuración y propósito del sistema

Propósito del sistema

METAFORSA SMART HOUSE es una solución lista para usar para la automatización de locales residenciales, comerciales y complejos hoteleros que incluye las características más deseadas de Smart House.


El dispositivo tiene 10 canales de control, 4 canales de atenuación, 24 canales de sensores entrantes y un puerto de conexión de sensores digitales.


Las salidas universales se pueden utilizar para controlar: Las entradas universales le permiten conectar:
Iluminación Botones/unidades de conmutación
Conectores hembra Interruptores de láminas magnéticos
Calefacción por suelo radiante Sensores de movimiento
Actuadores de cortinas/portones Sensores de fugas
Válvulas de suministro de agua/calefacción


Puerto de conexión de sensores digitales


El puerto de conexión de sensores digitales le permite conectar una variedad de sensores digitales, como sensores de temperatura, luz ambiental, humedad y otros.


Puerto de expansión


El puerto de expansión le permite actualizar el sistema conectando equipos auxiliares, como el módulo de control para iluminación LED, atenuación, dispositivos de medición y otros elementos. El paquete, que está completamente listo para instalar, incluye el hardware y el software básicos.

Contenido del paquete

El paquete viene de serie con:

Unidad central METAFORSA MF-14.А 1 PC
Unidad de fuente de alimentación MEANWELL DR-15-12 1 PC
Sensor de movimiento CW-MSD 3 piezas
Sensor de fugas FW-WL.A 2 piezas
Elemento sensible a la temperatura FW-TS.A 4 piezas
Interruptor de láminas magnético (sensor de posición de ventana/puerta) 4 piezas
Filtro de ruido del cable Ethernet 1 PC
Cable de alimentación 1 PC

Especificaciones técnicas básicas del Sistema

Las especificaciones y características básicas del módulo METAFORSA MF-14.A se muestran en la tabla 1

Tabla 1
Especificación Significado
Puertos de salida
Número de canales conmutados 10
Número de grupos conmutados 10
Número de canales de regulación 4
Tensión de conmutación 0-250 V CA/CC
Carga máxima (un canal) 16A
Carga máxima (dispositivo) 160A
Carga máxima por canal de regulación 0,5 A (110 W a 220 V)
Tipo de atenuador MOSFET
Tipo de carga de atenuador R,C
Tipo de atenuación borde de salida
Tipo de conexión del cable de alimentación conector
Sección permitida del cable de alimentación a conectar en la toma de corriente:
cable monoconductor
cable multiconductor
cable multiconductor con punta

0,5 … 4mm2
0,5 … 4mm2
0,5 … 2,5 mm2
Puertos de entrada
Número de entradas discretas 24
Número de entradas digitales 4
Clasificación máxima actual de los conectores de tensión de corriente continua 50mA
Otro
Temperatura ambiente de funcionamiento 0 … +45°С
Temperatura de almacenamiento/transporte -20 … +60°С
Humedad permitida 0 … 95% (sin condensación)
Fuente de alimentación 12 … 27,5 V CC
24 V, 0,75 A Recomendado
Máxima demanda 0.5А
Interfaces disponibles Ethernet, CAN, OneWire
Tipo de autobús CAN (4 hilos)
CAN (4 hilos) 800 m* (par trenzado 5 cat)
Tipo de cable CAN FTP Gato 5E
Tipo de conexión CAN conector
Longitud máxima de la línea digital 30 metros
Tipo de cable de línea digital UTP/FTP Categoría 5E
Longitud máxima de LAN 100 metros
Tipo de cable LAN UTP/FTP Categoría 5E
Tipo de conexión LAN Conector RJ-45
Especificaciones dimensionales 9U, 156x110x58mm
Material de la carcasa Plástico ABS
Carcasa IP40
Tipo de instalación del equipo Carril DIN (EN 60715)
Peso 400 gramos

* – se requiere la instalación de unidades de suministro de energía adicionales para líneas largas; La longitud máxima de la línea puede verse reducida por varios factores de interferencia.

Estructura general del Sistema

La vista general del módulo se muestra en 'fig. 1


700px|sin marco|izquierda|Fig. 1 Vista general del módulo

1 — conector para aplicación de carga
2 — conector para aplicación de lámparas con atenuación
3 - conector de alimentación
4 — Conector de red Ethernet
5-6 — conectores para sensores digitales y botones/unidades de conmutación
7 — Conector de interfaz OneWire (para sensores digitales)
8 — conector para módulo de expansión.


Descripción general de los conectores externos del dispositivo METAFORSA: En la parte superior de la carcasa (fig. 1) se encuentra:


  • conector (1) — Conexión de dispositivos;
  • conector (2) — Conexión de lámparas atenuadoras;


En la parte inferior de la carcasa (fig. 1) se encuentra:


  • conector (3) — conexión de alimentación del módulo;
  • conector (4) — Conexión de red Ethernet;
  • conectores (5-6): cuatro conectores de seis puntos para la conexión de sensores digitales: movimiento, fugas, sensores de interruptor de láminas y *sensores de botón/unidad de conmutación;
  • conector (7) — Conexión del bus de sensores digitales OneWire;
  • conector (8) — conexión del módulo de expansión.

La configuración física y la asignación del punto de contacto de cada conector se muestran en la tabla 2.


Tabla2
Conector Contacto Asignación
80px|sin marco 1-10 Aplicación de carga (lámparas de luz, actuadores térmicos, etc.)
80px|sin marco D1-4, L, N Aplicación de carga (lámparas atenuantes)
Indicadores de estado del dispositivo Los indicadores de estado del módulo se describen en la tabla 3
80px|sin marco +24V
GND
+24 V: fuente de alimentación del módulo mediante una fuente de alimentación externa de 24 V GND: común
80px|sin marco RJ45 Conector para conectividad LAN
80px|sin marco In1-12, In13-24 GND Conexión de dispositivos de control (botones, interruptores de láminas magnéticos, sensores de movimiento o fugas): +12 V — salida de alimentación del sensor +12 V
In1 … In24 — entradas lógicas (0-12 V)
GND — común
80px|sin marco OneWire Conexión de sensores digitales (temperatura)
VCC: salida de alimentación de los sensores +5 V
OW1-OW4: buses de datos OneWire
GND: común
80px|sin marco VCC
GND
L
H
Conexión de módulos externos para CAN-bus
VСС — Salida de 24 V para fuente de alimentación de dispositivos externos
GND — común
L — Bus de datos CAN-L
H — Bus de datos CAN-H
Table3
Indicator Status Description
Power   Power
  Power not available
Activity   Data communication
  Data communication not available
Error   No errors
  Communication error
   Module overheat
    Dimmer outputs module overload
     Absence of power on dimmers, if in configuration

Instalación y montaje del sistema

Antes de conectar el sistema, debe:


  • coloque el sensor y los actuadores (si no están preinstalados), configure los sensores y actuadores;
  • ubique el módulo y la fuente de alimentación.


Nota: El módulo debe instalarse cerca de la fuente de tensión de alimentación.


¡PRECAUCIÓN! Se debe proporcionar voltaje de alimentación de CA a la entrada del sistema a través del conjunto del disyuntor. Debe instalarse cerca de la fuente de alimentación.
  1. La potencia del conjunto del disyuntor debe cumplir con la capacidad de carga;
  2. No se puede conectar nada más que los conductores de fase al módulo, el cable neutro se conecta por separado.


El esquema típico de conexión del módulo METAFORSA MF-14.A se muestra en la fig. 3.


Conexión de los actuadores

Conexión de las luces/contactor eléctrico/actuador térmico de calefacción

 
Fig. 4
Actuadores como la luz, el contactor eléctrico o el actuador térmico de calefacción deben conectarse en cualquiera de las salidas 1 a 10, el cable neutro y el cable de tierra deben conectarse directamente al tablero de distribución. El ejemplo de conexión se muestra en la Fig.4.


Conexión de dispositivo de alta carga

  Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.


Conexión de la válvula unipolar de suministro de agua/gas

Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 5
The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.5.


Connection of double-pole water/gas supply valve

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Connection of single-pole gate actuator

Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors

The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11.

 
Fig. 11


Connection of FW-WL.A leakage sensors

FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12.

 

Fig12
 

Fig13

Configuration and connection of the FW-WL.A sensor 1. Terminals:

+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.

2. Sensor preset switch (optionally):

1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).

3. LED status indicator.

Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in24, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-15.

 

Fig14 connection of buttons/switching units
 

Fig15 connection of the magnetic reed switches (window/door position sensors)

Connection of digital sensors

The OW adapter (Fig. 16a) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b). The connected sensors are detected automatically and do not require any original setting.

 

Fig16 a
 

Fig16 b

Configuration and connection of the OW adapter

Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 17.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSBBBBSSSSSS' 12 buttons; 12 switches.

 1<item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> 
 2<item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> 
 3    <automation name="Eco" temperature-level="16" uniq_id="3781"/> 
 4    <automation name="Comfort" temperature-level="22" uniq_id="3782"/> 
 5    <automation name="Hot" temperature-level="25" uniq_id="3783"/> 
 6</item> 
 7<item addr="339:3" cfgid="40" hw="runtime=9" name="Jalousie" sub-type="120" type="jalousie" uniq_id="32"/> 
 8<item addr="339:5" cfgid="40" hw="runtime=13" name="Gate" sub-type="120" type="gate" uniq_id="3784"/> 
 9<item addr="339:7" cfgid="40" hw="hold=4600" name="Gate" sub-type="120" type="gate" uniq_id="3785"/> 
10<item addr="339:8" cfgid="40" hw="runtime=10" name="Valve" type="valve" uniq_id="3786"/> 
11<item addr="339:11" cfgid="40" name="Motion" type="motion-sensor" uniq_id="17"/> 
12<item addr="339:12" cfgid="40" name="Motion" type="motion-sensor" uniq_id="18"/> 
13<item addr="339:13" cfgid="40" name="Motion" type="motion-sensor" uniq_id="19"/> 
14<item addr="339:16" cfgid="40" name="Leak" type="leak-sensor" uniq_id="21"/> 
15<item addr="339:17" cfgid="40" name="Leak" type="leak-sensor" uniq_id="41"/> 
16<item addr="339:19" cfgid="40" name="Switch" type="switch" uniq_id="22"/> 
17<item addr="339:20" cfgid="40" name="Switch" type="switch" uniq_id="23"/> 
18<item addr="339:21" cfgid="40" name="Switch" type="switch" uniq_id="24"/> 
19<item addr="339:22" cfgid="40" name="Switch" type="switch" uniq_id="25"/> 
20<item addr="339:23" cfgid="40" name="Door" type="door-sensor" uniq_id="26"/>
21<item addr="339:24" cfgid="40" name="Door" type="door-sensor" uniq_id="27"/> 
22<item addr="339:25" cfgid="40" name="Door" type="door-sensor" uniq_id="28"/> 
23<item addr="339:26" cfgid="40" name="Door" type="door-sensor" uniq_id="29"/> 
24<item addr="339:30" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3772"/> 
25<item addr="339:31" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3773"/> 
26<item addr="339:32" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3774"/> 
27<item addr="339:33" cfgid="40" hw="offset='-10.8'" name="Temperature" type="temperature-sensor" uniq_id="3775"/> 
28<item addr="339:34" cfgid="40" hw="offset='25.1'" name="Temperature" type="temperature-sensor" uniq_id="3776"/> 
29<item addr="339:35" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3777"/> 
30<item addr="339:36" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3778"/> 
31<item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/>