Metaforsa2 MF-14

Revision as of 09:35, 11 March 2024 by Support (talk | contribs) (Created page with "===Připojení pohonů===")
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF-14
Metaforsa2.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs24
Number of digital inputs4
General
Max CAN devices50
Max CAN bus length800 m (twisted pair 5 cat)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


Úvod

Návod k instalaci METAFORSA SMART HOUSE popisuje postup jeho instalace, montáže, provozu a nastavení. Při práci se systémem musíte přísně dodržovat všechny požadavky uvedené v tomto návodu. Nedodržení může mít za následek poškození zařízení, jeho poruchu, úraz elektrickým proudem, požár a další spad. Výrobce si vyhrazuje právo provádět změny v tomto návodu bez předchozího upozornění. Tato příručka je nedílnou součástí systému a zůstane u konečného zákazníka.

Vlastnosti

  • Podpora 10 univerzálních výstupů:
    • Světla
    • ventily topení NC/NO
    • Žaluzie
    • 1 nebo 2-pólové brány
    • 1 nebo 2-pólové ventily
    • NC/NO zámky
    • Fan coil jednotky
  • 4 výstupy stmívání
  • 24 diskrétních vstupů, které podporují:
    • Tlačítka
    • Spínače
    • jazýčkové spínače
    • senzory úniku
    • detektory pohybu
  • 4 digitální vstupy až pro 8 teplotních čidel
  • Prodlužovací port
  • Relé s kontakty AgSnO2 dimenzované na zapínací proud 80A 20ms
  • Cloudové připojení a ovládání všech systémů domu
  • Hlasové ovládání (Siri, Alexa, Google Home)
  • Plugins engine umožňuje rozšíření možností systému (např. integrace se Satel, Philips Hue, IKEA lights)
  • Bezpečnost proti neoprávněnému vniknutí zajištěna pomocí šifrování RSA/AES256
  • Push oznámení ze systému na vašem telefonu (možné také přijímat prostřednictvím telegramů a zpráv Viber)
  • Historie (ukládají se data měřiče za 1 rok)
  • Plug and play (možnost rychlého a uživatelsky přívětivého rozšíření systému)
  • Pravidelné aktualizace systému
  • Velká neustále aktualizovaná databáze skriptů, aby vyhovovala všem vašim potřebám
  • Automatické denní zálohy přes cloud s možností obnovení výchozí konfigurace
  • Otevřené API (které umožňuje integraci Larnitechu do jiných systémů)
  • Interaktivní a uživatelsky přívětivé webové rozhraní LT SETUP pro pokročilou konfiguraci
  • Zapoj a hraj
  • Jedná se o kompletní sadu systému Smart Home připravenou k instalaci

Bezpečnostní požadavky

POZOR! Veškeré práce související s instalací, připojením, nastavením, servisem a podporou musí provádět kvalifikovaný personál s dostatečnými dovednostmi a zkušenostmi v práci s elektrickým zařízením.

Aby se zabránilo riziku požáru, úrazu elektrickým proudem, poškození systému a/nebo zranění osob, musí být instalace a montáž systému provedena v souladu s níže uvedenými pokyny:


  • všechny spojovací práce musí být provedeny bez napájení;
  • používejte vhodné nástroje a osobní ochranu proti úrazu elektrickým proudem;
  • nepoužívejte poškozené kabely, vodiče a konektory;
  • vyhněte se skládání kabelů a drátů;
  • nepřiskřípněte ani nezlomte kabely a vodiče nadměrnou silou. Jinak mohou být vnitřní vodiče kabelu a vodičů odizolovány nebo zlomeny;
  • nepoužívejte k připojení zásuvku se špatnými kontakty;
  • nepřekračujte limit parametrů zatížení uvedený v tomto návodu;
  • část vodičů napájecích vodičů podléhá specifikacím pro omezení proudové hustoty, typ izolace a materiál vodiče. Světelná část může způsobit přehřátí kabelu a požár.


Při práci se systémem po napájení NIKDY:

  • proveďte připojení/odpojení konektorů;
  • otevřené moduly a senzory.

Konfigurace systému a účel

Účel systému

METAFORSA SMART HOUSE je hotové řešení pro automatizaci obytných a komerčních prostor, hotelových komplexů, které zahrnuje ty nejžádanější vlastnosti Smart House.


Zařízení má 10 řídicích kanálů, 4 kanály stmívání, 24 vstupních senzorových kanálů a port pro připojení digitálních senzorů.


Univerzální výstupy lze použít k ovládání: Univerzální vstupy umožňují připojení:
Osvětlení Tlačítka/spínací jednotky
Zásuvkové konektory Magnetické jazýčkové spínače
Podlahové vytápění Pohybové senzory
Pohony záclon/brán Senzory úniku
Ventily pro přívod vody/topení


Port pro připojení digitálních senzorů


Port pro připojení digitálních senzorů umožňuje připojení různých digitálních senzorů, jako jsou teplotní senzory, okolní světlo, vlhkost a další.


Rozšiřující port


Rozšiřující port umožňuje upgradovat systém připojením pomocných zařízení, jako je řídicí modul pro LED osvětlení, stmívání, měřicí zařízení a další prvky. Balíček, který je zcela připraven k instalaci, obsahuje základní hardware a software.

Obsah balení

Balíček je standardně dodáván s:

Sálový rám METAFORSA MF-14.А 1 ks
Napájecí zdroj MEANWELL DR-15-12 1 ks
Pohybový senzor CW-MSD 3 ks
Snímač úniku FW-WL.A 2 ks
Teplotně citlivý prvek FW-TS.A 4 ks
Magnetický jazýčkový spínač (snímač polohy okna/dveře) 4 ks
Filtr šumu ethernetového kabelu 1 ks
Napájecí kabel 1 ks

Základní technické specifikace systému

Základní specifikace a vlastnosti modulu METAFORSA MF-14.A jsou uvedeny v tabulce 1

Table1
Specifikace Význam
Výstupní porty
Počet přepínaných kanálů 10
Počet přepínaných skupin 10
Počet kanálů stmívání 4
Komutační napětí 0-250 V AC/DC
Špičkové zatížení (jeden kanál) 16A
Špičkové zatížení (zařízení) 160A
Maximální zatížení na kanál stmívání 0,5A (110W při 220V)
Typ stmívače MOSFET
Typ zátěže stmívače R,C
Typ stmívání odtoková hrana
Typ připojení napájecího kabelu konektor
Přípustný průřez napájecího kabelu pro připojení do zásuvky:
jednovodičový kabel
vícežilový kabel
špičkový vícevodičový kabel

0,5 … 4 mm2
0,5 … 4 mm2
0,5 … 2,5 mm2
Vstupní porty
Počet diskrétních vstupů 24
Počet digitálních vstupů 4
Maximální proud na konektorech stejnosměrného napětí 50 mA
Jiné
Provozní okolní teplota 0 … +45°С
Skladovací/přepravní teplota -20 … +60°С
Přípustná vlhkost 0 … 95 % (bez kondenzace)
Napájení 12 … 27,5 V DC
24 V, 0,75 A Doporučeno
Maximální poptávka 0,5A
Dostupná rozhraní Ethernet, CAN, OneWire
Typ autobusu CAN (4vodičový)
CAN (4vodičový) 800 m* (kroucený pár 5 koček)
Typ drátu CAN FTP Cat 5E
Typ připojení CAN konektor
Maximální délka digitální linky 30 m
Typ drátu digitální linky UTP/FTP Cat 5E
Maximální délka LAN 100 m
Typ drátu LAN UTP/FTP Cat 5E
Typ připojení LAN Konektor RJ-45
Rozměrové specifikace 9U, 156x110x58 mm
Materiál pláště ABS plast
Pouzdro IP40
Typ instalace zařízení DIN lišta (EN 60715)
Hmotnost 400 g

* – pro dlouhé linky je nutná instalace dalších napájecích jednotek; maximální délka vedení může být snížena různými rušivými faktory

Obecná struktura systému

Celkový pohled na modul je znázorněn na Obr. 1


 


1 — konektor pro aplikaci zátěže
2 — konektor pro aplikaci stmívacích světel
3 - napájecí konektor
4 — Ethernetový síťový konektor
5-6 — konektory pro digitální snímače a tlačítka/spínací jednotky
7 — Konektor rozhraní OneWire (pro digitální senzory)
8 — konektor pro rozšiřující modul.


Přehled externích konektorů zařízení METAFORSA: V horní části krytu (obr. 1) je:


  • konektor (1) — Připojení zařízení;
  • konektor (2) — připojení stmívacích světel;


Ve spodní části pouzdra (obr. 1) je:


  • konektor (3) — připojení napájení modulu;
  • konektor (4) — připojení k síti Ethernet;
  • konektory (5-6) — čtyři šestibodové konektory pro připojení digitálních senzorů – pohyb, netěsnost, senzory jazýčkového spínače a * senzory tlačítka/spínací jednotky;
  • konektor (7) — připojení sběrnice digitálních snímačů OneWire;
  • konektor (8) — připojení rozšiřujícího modulu.

Fyzická konfigurace a přiřazení kontaktních bodů každého konektoru jsou uvedeny v tabulce 2.


Tabulka2
Konektor Kontakt Zadání
  1-10 Aplikace zatížení (světelné lampy, termopohony atd.)
  D1-4, L, N Aplikace zátěže (stmívání lamp)
Indikátory stavu zařízení Indikátory stavu modulu jsou popsány v tabulce 3
  +24V
GND
+24V — napájení modulu externím 24V zdrojem GND — společné
  RJ45 Konektor pro připojení k LAN
  In1-12, In13-24 GND Připojení ovládacích zařízení (tlačítka, magnetické jazýčkové spínače, snímače pohybu nebo úniku): +12V — výstupní výkon snímače +12 V
In1 … In24 — logické vstupy (0-12 V)
GND — společné
  OneWire Připojení digitálních senzorů (teplota)
VCC — výstup napájení senzorů +5V
OW1-OW4 — datové sběrnice OneWire
GND — společné
  VCC
GND
L
H
Připojení externích modulů pro sběrnici CAN
VСС — 24V výstup pro napájení externích zařízení
GND — společné
L — datová sběrnice CAN-L
H — datová sběrnice CAN-H
Table3
Indicator Status Description
Power   Power
  Power not available
Activity   Data communication
  Data communication not available
Error   No errors
  Communication error
   Module overheat
    Dimmer outputs module overload
     Absence of power on dimmers, if in configuration

Instalace a montáž systému

Před připojením systému musíte:


  • umístěte senzor a akční členy (pokud nejsou předem nainstalovány), nastavte senzory a akční členy;
  • Umístěte modul a napájecí zdroj.


Poznámka: Modul musí být instalován v blízkosti zdroje napájecího napětí.


POZOR! Střídavé napájecí napětí musí být přivedeno na vstup systému přes sestavu jističe. Měl by být instalován v blízkosti napájecího zdroje.
  1. Výkon sestavy jističe musí odpovídat nosnosti;
  2. K modulu nelze připojit nic jiného než fázové vodiče, nulový vodič se připojuje samostatně.


Typické schéma zapojení modulu METAFORSA MF-14.A je znázorněno na obr. 3.

 


Připojení pohonů

Connection of the lights/electric contactor/heating thermal actuator

 
Fig. 4
Such actuators as light, electric contactor, heating thermal actuator should be switched on any of the outputs 1 – 10, the neutral wire and the ground wire should be connected directly to the switchboard. The example of connection is shown in Fig.4.


Connection of high load device

  Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.


Connection of single-pole water/gas supply valve

Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 5
The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.5.


Connection of double-pole water/gas supply valve

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Connection of single-pole gate actuator

Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors

The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11.

 
Fig. 11


Connection of FW-WL.A leakage sensors

FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12.

 

Fig12
 

Fig13

Configuration and connection of the FW-WL.A sensor 1. Terminals:

+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.

2. Sensor preset switch (optionally):

1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).

3. LED status indicator.

Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in24, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-15.

 

Fig14 connection of buttons/switching units
 

Fig15 connection of the magnetic reed switches (window/door position sensors)

Connection of digital sensors

The OW adapter (Fig. 16a) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b). The connected sensors are detected automatically and do not require any original setting.

 

Fig16 a
 

Fig16 b

Configuration and connection of the OW adapter

Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 17.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSBBBBSSSSSS' 12 buttons; 12 switches.

 1<item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> 
 2<item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> 
 3    <automation name="Eco" temperature-level="16" uniq_id="3781"/> 
 4    <automation name="Comfort" temperature-level="22" uniq_id="3782"/> 
 5    <automation name="Hot" temperature-level="25" uniq_id="3783"/> 
 6</item> 
 7<item addr="339:3" cfgid="40" hw="runtime=9" name="Jalousie" sub-type="120" type="jalousie" uniq_id="32"/> 
 8<item addr="339:5" cfgid="40" hw="runtime=13" name="Gate" sub-type="120" type="gate" uniq_id="3784"/> 
 9<item addr="339:7" cfgid="40" hw="hold=4600" name="Gate" sub-type="120" type="gate" uniq_id="3785"/> 
10<item addr="339:8" cfgid="40" hw="runtime=10" name="Valve" type="valve" uniq_id="3786"/> 
11<item addr="339:11" cfgid="40" name="Motion" type="motion-sensor" uniq_id="17"/> 
12<item addr="339:12" cfgid="40" name="Motion" type="motion-sensor" uniq_id="18"/> 
13<item addr="339:13" cfgid="40" name="Motion" type="motion-sensor" uniq_id="19"/> 
14<item addr="339:16" cfgid="40" name="Leak" type="leak-sensor" uniq_id="21"/> 
15<item addr="339:17" cfgid="40" name="Leak" type="leak-sensor" uniq_id="41"/> 
16<item addr="339:19" cfgid="40" name="Switch" type="switch" uniq_id="22"/> 
17<item addr="339:20" cfgid="40" name="Switch" type="switch" uniq_id="23"/> 
18<item addr="339:21" cfgid="40" name="Switch" type="switch" uniq_id="24"/> 
19<item addr="339:22" cfgid="40" name="Switch" type="switch" uniq_id="25"/> 
20<item addr="339:23" cfgid="40" name="Door" type="door-sensor" uniq_id="26"/>
21<item addr="339:24" cfgid="40" name="Door" type="door-sensor" uniq_id="27"/> 
22<item addr="339:25" cfgid="40" name="Door" type="door-sensor" uniq_id="28"/> 
23<item addr="339:26" cfgid="40" name="Door" type="door-sensor" uniq_id="29"/> 
24<item addr="339:30" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3772"/> 
25<item addr="339:31" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3773"/> 
26<item addr="339:32" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3774"/> 
27<item addr="339:33" cfgid="40" hw="offset='-10.8'" name="Temperature" type="temperature-sensor" uniq_id="3775"/> 
28<item addr="339:34" cfgid="40" hw="offset='25.1'" name="Temperature" type="temperature-sensor" uniq_id="3776"/> 
29<item addr="339:35" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3777"/> 
30<item addr="339:36" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3778"/> 
31<item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/>