MF3/MF3.plus
METAFORSA 3 MF3-14.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs28
General
Max CAN devices4 (can be extended with the license) 99 (for Metaforsa 3.plus)
Max CAN bus length800 m (twisted pair CAT5e)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x90x58 mm


Einleitung

Das METAFORSA SMART HOUSE Installationshandbuch beschreibt das Verfahren für die Installation, die Montage, den Betrieb und die Einstellung des Systems. Bei der Arbeit mit dem System müssen Sie alle in diesem Handbuch aufgeführten Anforderungen strikt einhalten. Die Nichtbeachtung kann zu Schäden am Gerät, dessen Ausfall, Stromschlag, Feuer und anderen Folgen führen. Der Hersteller behält sich das Recht vor, ohne vorherige Ankündigung Änderungen an diesem Handbuch vorzunehmen. Dieses Handbuch ist ein wesentlicher Bestandteil des Systems und verbleibt beim Endkunden.

Merkmale

  • 10 universelle Ausgänge werden unterstützt:
    • Lichter
    • NC/NO Heizungsventile
    • Jalousien
    • 1- oder 2-polige Schieber
    • 1- oder 2-polige Ventile
    • NC/NO Schlösser
    • Gebläsekonvektoren
  • 4 Dimmausgänge
  • 28 Eingänge, die unterstützen:
    • Tasten
    • LED-Tasten
    • Schalter
    • Reed-Schalter
    • Lecksensoren
    • Bewegungsmelder
    • Temperatursensoren
    • LED-Streifen
    • 3-4-5-Kanal-RGB-Leisten
    • WS2812B-Streifen
    • RS485-Geräte (nur für Metaforsa 3.plus)
  • Erweiterungsanschluss
  • Relais mit AgSnO2-Kontakten, ausgelegt für 80A 20ms Einschaltstromstoß
  • Cloud-Anbindung und Steuerung aller Haussysteme
  • Sprachsteuerung (Siri, Alexa, Google Home)

Sicherheitsanforderungen

ACHTUNG! Alle Arbeiten im Zusammenhang mit der Installation, dem Anschluss, der Einrichtung, der Wartung und der Unterstützung müssen von qualifiziertem Personal mit ausreichenden Kenntnissen und Erfahrungen im Umgang mit elektrischen Geräten durchgeführt werden.

Um das Risiko eines Brandes, eines elektrischen Schlages, einer Beschädigung des Systems und/oder von Personenschäden zu vermeiden, müssen die Installation und der Zusammenbau des Systems in Übereinstimmung mit den unten aufgeführten Anweisungen durchgeführt werden:


  • Alle Anschlussarbeiten müssen im stromlosen Zustand durchgeführt werden;
  • geeignete Werkzeuge und persönlichen Schutz gegen elektrischen Schlag verwenden;
  • Verwenden Sie keine beschädigten Kabel, Drähte und Steckverbinder;
  • Vermeiden Sie das Knicken von Kabeln und Drähten;
  • Kabel und Drähte nicht durch übermäßige Kraftanwendung einklemmen oder knicken. Andernfalls können die Innenleiter der Kabel und Drähte abisoliert oder gebrochen werden;
  • Verwenden Sie zum Anschließen keine Steckdose mit schlechten Kontakten;
  • Überschreiten Sie nicht die in diesem Handbuch angegebenen Grenzwerte für die Lastparameter;
  • Der Abschnitt der Versorgungsleiter unterliegt den Spezifikationen für die Stromdichtegrenze, den Isolierungstyp und das Drahtmaterial. Leichte Abschnitte können zu Kabelüberhitzung und Feuer führen.


Bei Arbeiten am System nach der Spannungsversorgung NIEMALS:

  • Stecker anschließen/abziehen;
  • Module und Sensoren öffnen.

Systemkonfiguration und Zweck

Zweck des Systems

METAFORSA SMART HOUSE ist eine fertige Lösung für die Automatisierung von Wohn- und Geschäftsräumen sowie Hotelkomplexen, die die am meisten gewünschten Funktionen von Smart House beinhaltet.


Das Gerät verfügt über 10 Steuerkanäle, 4 Dimmkanäle und 28 Eingangskanäle.


Universalausgänge können verwendet werden zur Steuerung von: ! Mit den Universaleingängen können Sie anschließen:
Beleuchtung Taster/LED-Taster/Schalteinheiten
Steckdosenleisten Magnetische Reed-Schalter
Fußbodenheizung Leckagesensoren
Vorhang Bewegungsmelder
Torantriebe Temperatursensoren
Wasserversorgung LED-Streifen/3-4-5-Kanal-RGB-Streifen/WS2812B-Streifen
Heizungsventile RS485-Geräte*

* - Nur für Metaforsa 3.plus


Erweiterungsanschluss


Die Erweiterungsschnittstelle ermöglicht es Ihnen, das System durch den Anschluss von Zusatzgeräten zu erweitern, wie z. B. das Steuermodul für LED-Beleuchtung, Dimmer, Messgeräte und andere Elemente. Das komplett einbaufertige Paket enthält die grundlegende Hardware und Software.

Paketinhalt

Das Paket wird standardmäßig geliefert:

Großrechner METAFORSA 3/3.plus 1 Stück
Netzgerät MEANWELL DR-15-12 1 St.
Bewegungssensor CW-MSD 3 Stück
Leckagesensor FW-WL.B 2 St.
Temperatursensorelement FW-TS 4 Stück
Magnetischer Reedschalter (Fenster-/Türpositionssensor) 4 Stück
Ethernet-Kabel-Rauschfilter 1 Stück
Netzkabel 1 St.

Grundlegende technische Daten des Systems

Die grundlegenden Spezifikationen und Merkmale des Moduls METAFORSA 3/3.plus sind in Tabelle 1 aufgeführt

Tabelle 1
Spezifikation Bedeutung
Ausgabeports
Anzahl der geschalteten Kanäle 10
Anzahl der geschalteten Gruppen 10
Anzahl Dimmkanäle 4
Kommutierungsspannung 0-250 V AC/DC
Spitzenlast (ein Kanal) 16A
Spitzenlast (Gerät) 160A
Maximale Last pro Dimmkanal 0,5A (110W bei 220V)
Dimmertyp MOSFET
Dimmerlasttyp R,C
Dimmart Hinterkante
Anschlussart des Stromversorgungskabels Verbinder
Zulässiger Querschnitt des Stromversorgungskabels zum Anschluss an die Steckdose:
Einleiterkabel
Mehrleiterkabel
Mehrleiterkabel mit Spitze

0,5 … 4mm2
0,5 … 4mm2
0,5 … 2,5 mm2
Eingabeports
Anzahl der diskreten Eingänge 28
Maximal zulässiger Strom an den Gleichspannungsanschlüssen: 5 mA*
Sonstiges
Betriebsumgebungstemperatur 0 ... +45°С
Lager-/Transporttemperatur -10 ... +50°С
Zulässige Luftfeuchtigkeit 0 … 95 % (nicht kondensierend)
Stromversorgung 11,5 … 27,5 V DC
24 V, 0,75 A Empfohlen
Maximale Nachfrage 0,5À
Verfügbare Schnittstellen Ethernet, CAN
Bustyp CAN (4-Draht)
CAN (4-Draht) 800 m** (Twisted Pair CAT5e)
CAN-Kabeltyp FTP Cat 5E
CAN-Verbindungstyp Verbinder
Maximale Länge der digitalen Leitung 30 m
Digitaler Leitungstyp UTP/FTP Cat 5E
Maximale LAN-Länge 100 m
LAN-Kabeltyp UTP/FTP Cat 5E
LAN-Verbindungstyp Anschluss RJ-45
Anzahl RS485-Ports 1***
Datenübertragungsgeschwindigkeit 1200-115200 b/s***
Maßangaben 9 HE, 156 x 90 x 58 mm
Schalenmaterial Abs
Gehäuse IP40
Geräteinstallationstyp DIN-Schiene (EN 60715)
Gewicht 400 g

* – Ausgangskanäle sollten nur mit einem Verstärker verbunden werden, der das 5-V-PWM-Signal vom IO-Ausgang als Eingang verwendet

** – bei langen Leitungen ist die Installation zusätzlicher Netzteile erforderlich; Die maximale Länge der Leitung kann durch verschiedene Störfaktoren reduziert werden

*** – Nur für Metaforsa 3.plus

Allgemeine Struktur des Systems

Die Gesamtansicht des Moduls ist in Abb. 1 dargestellt.


 


1 — Anschluss für Lastaufbringung
2 — Steckverbinder für Dimmlampenanwendungen
3 - Stecker
4 — Ethernet-Netzwerkanschluss
5-6 — Anschlüsse für universelle Ein-/Ausgabekanäle
7 — Anschluss für Erweiterungsmodul.


'Übersicht über die externen METAFORSA-Geräteanschlüsse: Oben auf dem Gehäuse (Abb. 1) befindet sich:


  • Anschluss (1) – Geräteverbindung;
  • Anschluss (2) – Anschluss zum Dimmen von Lampen;


Auf der Unterseite des Gehäuses (Abb. 1) befindet sich:


  • Anschluss (3) – Anschluss für die Stromversorgung des Moduls;
  • Anschluss (4) – Ethernet-Netzwerkverbindung;
  • Anschlüsse (5-6) – universelle Eingangs-/Ausgangskanalverbindung – Tasten, Reed-Schalter, LED-Tasten, Lecksensoren, Bewegungssensoren, Temperatursensoren, LED-Streifen, 3-4-5-Kanal-RGB-Streifen, WS2812B-Streifen, RS485-Geräte ( Nur für Metaforsa 3.plus);
  • Anschluss (7) – Erweiterungsmodulanschluss.

Die physische Konfiguration und die Kontaktpunktzuordnung jedes Steckverbinders sind in „Tabelle 2“ dargestellt.

Tabelle 2
Stecker Kontakt Belegung
  1-10 Lastanwendung (Lichtlampen, thermische Aktuatoren usw.)
  D1-4, L, N Lastanwendung (Dimmen von Lampen)
Gerätestatusanzeigen Die Modulstatusanzeigen sind in „Tabelle 3“ beschrieben.
  +24V
GND
+24V – Stromversorgung des Moduls über eine externe 24-V-Stromversorgung. GND – Masse
  RJ45 Anschluss für LAN-Konnektivität
  In1-14, In15-28 GND Anschluss von Steuergeräten (Tasten, LED-Tasten, magnetische Reed-Schalter, Bewegungsmelder, Leckagesensoren, Temperatursensoren usw.):
In1 … In28 – Logikeingänge
GND – gemeinsam
  VCC
GND
L
H
Anschluss externer Module für CAN-Bus
VСС – 24-V-Ausgang für die Stromversorgung externer Geräte
GND – gemeinsam
L – CAN-L-Datenbus
H – CAN-H-Datenbus
Table3
Indicator Status Description
Power   Power
  Power not available
Activity   Data communication
  Data communication not available
Error   No errors
  Communication error
   Module overheat
    Dimmer outputs module overload
     Absence of power on dimmers, if in configuration

Systeminstallation und Montage

Bevor Sie das System anschließen, müssen Sie:


  • Platzieren Sie den Sensor und die Aktoren (falls nicht vorinstalliert), stellen Sie die Sensoren und Aktoren ein;
  • Platzieren Sie das Modul und die Stromversorgung.


Hinweis: Das Modul muss in der Nähe der Spannungsquelle der Stromversorgung installiert werden.


ACHTUNG! Der Systemeingang muss über die Schutzschalterbaugruppe mit Wechselspannung versorgt werden. Es sollte in der Nähe der Stromversorgung installiert werden.
  1. Die Leistung der Leistungsschalterbaugruppe muss der Belastbarkeit entsprechen;
  2. An das Modul können nur die Phasenleiter angeschlossen werden, der Neutralleiter wird separat angeschlossen.


Ein typisches Diagramm der Modulverbindung METAFORSA 3/3.plus ist in Abb. dargestellt. 3.

 


Anschluss der Aktoren

Anschluss der Beleuchtung/elektrischer Schütz/Heizungs-Thermoaktor

 
Abb. 4'
Stellantriebe wie Licht, elektrische Schütze, thermische Stellantriebe für Heizungen sollten an einen der Ausgänge 1 – 10 geschaltet werden, der Neutralleiter und der Erdungsdraht sollten direkt an die Schalttafel angeschlossen werden. Das Anschlussbeispiel ist in Abb. 4 dargestellt.


Anschluss eines Hochlastgeräts

  Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.


Connection of single-pole water/gas supply valve

Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 5
The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.5.


Connection of double-pole water/gas supply valve

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Connection of single-pole gate actuator

Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors/leakage sensors

The motion sensors/leakage sensors should be connected to any free input in1-in28; in these conditions their power is connected to the contact points of +5V and GND of the relevant group. The example of connection is shown in Fig.11.

 
Fig. 11 connection of motion sensors/leakage sensors


Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 12-13.

 

Fig. 12 connection of buttons/switching units
 

Fig. 13 connection of the magnetic reed switches (window/door position sensors)

Connection of temperature sensors

Temperature sensors are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 14.

 

Fig. 14 connection of temperature sensors

RGB connection scheme

CAUTION! Output channels should only be connected using amplifier which uses 5V PWM signal from IO output as input

 

Fig. 15 RGB connection

WS2812B connection scheme

 

Fig. 16 WS2812B connection

RS485 connection scheme

CAUTION! RS485 connection is only available for Metaforsa 3.plus and only occurs on 21 channel

 

Fig. 17 RS485 connection

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 18.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

io char[28] 98 io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • '0' - led-dimmer
  • '1' - halogen-dimmer
  • '2' - linear-dimmer
  • '3'..'6' - RGB-3..6 channels
  • 'z' - WS2812B -string
  • 'e' - led-button inverse
  • 'd' - led-button
  • 'c' - button inverse
  • 'b' - button
  • 's' - switch
  • 'k' - contact inverse
  • 'h' - contact
  • 'l' - leak
  • 'n' - Neptun
  • 'v' - motion inverse
  • 'm' - motion
  • 'r' - thermo-resistor
  • 't' - DALLAS
  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK'

Only for Metaforsa 3.plus
cfg string 98 9600/8N1 cfg='SPEED/BPS', where
  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"
[Protocol] string 98 Protocol setting is described by protocol parameter. The following

protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"
echo on; off 98 'off' For settings check out and testing echo parameter can be used. Module

echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"
 1		<item addr="349:1" auto-period="600" cfgid="197" name="Lamp 1" type="lamp"/>
 2		<item addr="349:2" auto-period="600" cfgid="197" name="Lamp 2" type="lamp"/>
 3		<item addr="349:3" auto-period="600" cfgid="197" name="Lamp 3" type="lamp"/>
 4		<item addr="349:4" auto-period="600" cfgid="197" name="Lamp 4" type="lamp"/>
 5		<item addr="349:5" auto-period="600" cfgid="197" name="Lamp 5" type="lamp"/>
 6		<item addr="349:6" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
 7			<automation name="Eco" temperature-level="16"/>
 8			<automation name="Comfort" temperature-level="22"/>
 9			<automation name="Hot" temperature-level="25"/>
10		</item>
11		<item addr="349:7" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
12			<automation name="Eco" temperature-level="16"/>
13			<automation name="Comfort" temperature-level="22"/>
14			<automation name="Hot" temperature-level="25"/>
15		</item>
16		<item addr="349:8" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
17			<automation name="Eco" temperature-level="16"/>
18			<automation name="Comfort" temperature-level="22"/>
19			<automation name="Hot" temperature-level="25"/>
20		</item>
21		<item addr="349:9" cfgid="197" name="Jalousie" sub-type="120" type="jalousie"/>
22		<item addr="349:11" auto-period="600" cfgid="197" name="Dimmer 1" type="dimmer-lamp"/>
23		<item addr="349:12" auto-period="600" cfgid="197" name="Dimmer 2" type="dimmer-lamp"/>
24		<item addr="349:13" auto-period="600" cfgid="197" name="Dimmer 3" type="dimmer-lamp"/>
25		<item addr="349:14" auto-period="600" cfgid="197" name="Dimmer 4" type="dimmer-lamp"/>
26		<item addr="349:16" cfgid="197" name="Door 1" type="door-sensor"/>
27		<item addr="349:17" cfgid="197" name="Door 2" type="door-sensor"/>
28		<item addr="349:18" cfgid="197" name="Door 3" type="door-sensor"/>
29		<item addr="349:19" cfgid="197" name="Door 4" type="door-sensor"/>
30		<item addr="349:20" cfgid="197" name="Door 5" type="door-sensor"/>
31		<item addr="349:21" cfgid="197" name="Door 6" type="door-sensor"/>
32		<item addr="349:22" cfgid="197" name="Door 7" type="door-sensor"/>
33		<item addr="349:23" cfgid="197" name="Door 8" type="door-sensor"/>
34		<item addr="349:24" cfgid="197" name="Door 9" type="door-sensor"/>
35		<item addr="349:25" cfgid="197" name="Door 10" type="door-sensor"/>
36		<item addr="349:26" cfgid="197" name="Door 11" type="door-sensor"/>
37		<item addr="349:27" cfgid="197" name="Door 12" type="door-sensor"/>
38		<item addr="349:28" cfgid="197" name="Door 13" type="door-sensor"/>
39		<item addr="349:29" cfgid="197" name="Door 14" type="door-sensor"/>
40		<item addr="349:30" cfgid="197" name="Door 15" type="door-sensor"/>
41		<item addr="349:31" cfgid="197" name="Door 16" type="door-sensor"/>
42		<item addr="349:32" cfgid="197" name="Door 17" type="door-sensor"/>
43		<item addr="349:33" cfgid="197" name="Door 18" type="door-sensor"/>
44		<item addr="349:34" cfgid="197" name="Door 19" type="door-sensor"/>
45		<item addr="349:35" cfgid="197" name="Door 20" type="door-sensor"/>
46		<item addr="349:36" cfgid="197" name="Door 21" type="door-sensor"/>
47		<item addr="349:37" cfgid="197" name="Door 22" type="door-sensor"/>
48		<item addr="349:38" cfgid="197" name="Door 23" type="door-sensor"/>
49		<item addr="349:39" cfgid="197" name="Door 24" type="door-sensor"/>
50		<item addr="349:40" cfgid="197" name="Door 24" type="door-sensor"/>
51		<item addr="349:41" cfgid="197" name="Door 25" type="door-sensor"/>
52		<item addr="349:43" cfgid="197" name="IR receiver" type="ir-receiver"/>
53		<item addr="349:44" cfgid="197" name="RS485" type="com-port"/>
54		<item addr="349:90" cfgid="197" name="Current" system="yes" type="current-sensor"/>
55		<item addr="349:95" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
56		<item addr="349:96" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
57		<item addr="349:97" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
58		<item addr="349:98" cfgid="197" hw="out='LLLLLHHHB-' dm='LLLL' io='KKKKKKKKKKKKKKKKKKKKUKKKKKK-'" logic-ver="19" name="Temperature" sn="2533726919" system="yes" type="temperature-sensor"/>
59		<item addr="349:100" cfgid="197" name="RS232" type="com-port"/>