Metaforsa 3/3.plus

Revision as of 14:06, 4 April 2024 by Support (talk | contribs) (Created page with "Los sensores de movimiento deben conectarse a cualquier entrada libre in1-in28; en estas condiciones su alimentación está conectada a los puntos de contacto de +5V y GND del...")
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF3/MF3.plus
METAFORSA 3 MF3-14.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs28
General
Max CAN devices4 (can be extended with the license) 99 (for Metaforsa 3.plus)
Max CAN bus length800 m (twisted pair CAT5e)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x90x58 mm


Introducción

El Manual de Instalación de METAFORSA SMART HOUSE describe el procedimiento para su instalación, montaje, funcionamiento y configuración. Mientras trabaja con el sistema, debe cumplir estrictamente con todos los requisitos establecidos en este manual. El incumplimiento puede provocar daños al dispositivo, fallos, descargas eléctricas, incendios y otras consecuencias. El fabricante se reserva el derecho de realizar cambios en este manual sin previo aviso. Este manual es una parte integral del sistema y permanecerá en manos del cliente final.

Características

  • Soporta 10 salidas universales:
    • Luces
    • Válvulas de calefacción NC/NO
    • Persianas
    • Puertas de 1 ó 2 polos
    • Válvulas de 1 ó 2 polos
    • Cerraduras NC/NO
    • Ventiladores
  • 4 salidas de regulación
  • 28 entradas compatibles:
    • Botones
    • Botones LED
    • Interruptores
    • Interruptores de láminas
    • Sensores de fugas
    • Detectores de movimiento
    • Sensores de temperatura
    • Tiras LED
    • Tiras RGB de 3-4-5 canales
    • TirasWS2812B
    • Dispositivos RS485 (sólo para Metaforsa 3.plus)
  • Puerto de extensión
  • Relés con contactos de AgSnO2 con corriente de irrupción de 80A 20ms
  • Conexión a la nube y control de todos los sistemas de la casa
  • Control por voz (Siri, Alexa, Google Home)

Requisitos de seguridad

'¡PRECAUCIÓN! Todos los trabajos relacionados con la instalación, conexión, configuración, servicio y soporte deben ser realizados por personal calificado con suficientes habilidades y experiencia en el trabajo con equipos eléctricos.

Para evitar el riesgo de incendio, descarga eléctrica, daños al sistema y/o lesiones personales, la instalación y el montaje del sistema deben realizarse de acuerdo con las instrucciones que se enumeran a continuación:


  • todos los trabajos de conexión deben realizarse sin corriente eléctrica;
  • utilizar herramientas adecuadas y protección personal contra descargas eléctricas;
  • no utilizar cables, alambres y conectores dañados;
  • evite doblar los cables y alambres;
  • no pellizque ni retuerza los cables y alambres aplicando una fuerza excesiva. De lo contrario, los conductores internos de los cables y alambres podrían pelarse o romperse;
  • No utilice tomas de corriente con contactos deficientes;
  • no exceda el límite de los parámetros de carga especificados en este manual;
  • la sección de cable de los conductores de alimentación está sujeta a las especificaciones de límite de densidad de corriente, tipo de aislamiento y material del cable. Una sección ligera puede provocar el sobrecalentamiento e incendio del cable.


Al trabajar con el sistema después del suministro de voltaje NUNCA:

  • realizar conexión/desconexión de conectores;
  • abrir módulos y sensores.

Configuración y propósito del sistema

Propósito del sistema

METAFORSA SMART HOUSE es una solución lista para usar para la automatización de locales residenciales, comerciales y complejos hoteleros que incluye las características más deseadas de Smart House.


El dispositivo tiene 10 canales de control, 4 canales de regulación y 28 canales de entrada qty.


! Las salidas universales se pueden utilizar para controlar: !! Las entradas universales le permiten conectar: |- | Iluminación || Botones/botones LED/unidades de conmutación |- | Conectores hembra || Interruptores de láminas magnéticos |- | Calefacción por suelo radiante || Sensores de fugas |- | Cortina || detectores de movimiento |- | Actuadores de puerta || Sensores de temperatura |- | Abastecimiento de agua || Tiras LED/tiras RGB de 3-4-5 canales/tiras WS2812B |- | Válvulas de calefacción || Dispositivos RS485* |} * – Sólo para Metaforsa 3.plus


Puerto de expansión


El puerto de expansión le permite actualizar el sistema conectando equipos auxiliares, como el módulo de control para iluminación LED, atenuación, dispositivos de medición y otros elementos. El paquete, que está completamente listo para instalar, incluye el hardware y el software básicos.

Contenido del paquete

El paquete viene de serie con:

Unidad central METAFORSA 3/3.plus 1 PC
Unidad de fuente de alimentación MEANWELL DR-15-12 1 PC
Sensor de movimiento CW-MSD 3 piezas
Sensor de fugas FW-WL.B 2 piezas
Elemento sensible a la temperatura FW-TS 4 piezas
Interruptor de láminas magnético (sensor de posición de ventana/puerta) 4 piezas
Filtro de ruido del cable Ethernet 1 PC
Cable de alimentación 1 PC

Especificaciones técnicas básicas del Sistema

Las especificaciones y características básicas del módulo METAFORSA 3/3.plus se muestran en la tabla 1{| class="wikitable" |+ text-align="left"|Tabla 1 |- !Especificación !! Significado |- |colspan="2"|Puertos de salida |- | Número de canales conmutados || 10 |- | Número de grupos conmutados|| 10 |- | Número de canales de regulación || 4 |- | Tensión de conmutación || 0-250 V CA/CC |- | Carga máxima (un canal) || 16A |- | Carga máxima (dispositivo) || 160A |- | Carga máxima por canal de regulación || 0,5 A (110 W a 220 V) |- | Tipo de atenuador || MOSFET |- | Tipo de carga de atenuador || R,C |- | Tipo de atenuación || borde de salida |- | Tipo de conexión del cable de alimentación || conector |- |Sección permitida del cable de alimentación a conectar en la toma de corriente:
cable monoconductor
cable multiconductor
cable multiconductor con punta||
0,5 … 4mm2
0,5 … 4mm2
0,5 … 2,5 mm2 |- |colspan="2"|Puertos de entrada |- |Número de entradas discretas || 28 |- |Clasificación máxima actual de los conectores de tensión de corriente continua || 5 mA* |- |colspan="2"|Otro |- |Temperatura ambiente de funcionamiento || 0 … +45°С |- |Temperatura de almacenamiento/transporte || -10 … +50°С |- |Humedad permitida || 0 … 95% (sin condensación) |- |Fuente de alimentación || 11,5 … 27,5 V CC
24 V, 0,75 A Recomendado |- |Máxima demanda || 0.5А |- |Interfaces disponibles || Ethernet, puede |- |Tipo de autobús || CAN (4 hilos) |- |CAN (4 hilos) || 800 m** (par trenzado CAT5e) |- |Tipo de cable CAN || FTP Gato 5E |- |Tipo de conexión CAN || Conector |- |Longitud máxima de la línea digital || 30 metros |- |Tipo de cable de línea digital || UTP/FTP Categoría 5E |- |Longitud máxima de LAN || 100 metros |- |Tipo de cable LAN || UTP/FTP Categoría 5E |- |Tipo de conexión LAN || Conector RJ-45 |- |Cantidad de puertos RS485 || 1*** |- |Velocidad de transferencia de datos || 1200-115200 b/s*** |- |Especificaciones dimensionales || 9U, 156x90x58mm |- |Material de la carcasa || abdominales |- |Carcasa || IP40 |- |Tipo de instalación del equipo || Carril DIN (EN 60715) |- |Peso || 400 gramos |} *: los canales de salida solo deben conectarse utilizando un amplificador que utilice una señal PWM de 5 V de la salida IO como entrada.

** – se requiere la instalación de unidades de suministro de energía adicionales para líneas largas; La longitud máxima de la línea puede verse reducida por varios factores de interferencia.

*** – Sólo para Metaforsa 3.plus

Estructura general del Sistema

La vista general del módulo se muestra en 'fig. 1


 


1 — conector para aplicación de carga
2 — conector para aplicación de lámparas con atenuación
3 - conector de alimentación
4 — Conector de red Ethernet
5-6 — conectores para canales de entrada/salida universales
7 — conector para módulo de expansión.


Descripción general de los conectores externos del dispositivo METAFORSA: En la parte superior de la carcasa (fig. 1) se encuentra:


  • conector (1) — Conexión de dispositivos;
  • conector (2) — Conexión de lámparas atenuadoras;


En la parte inferior de la carcasa (fig. 1) se encuentra:


  • conector (3) — conexión de alimentación del módulo;
  • conector (4) — Conexión de red Ethernet;
  • conectores (5-6): conexión universal de canales de entrada/salida: botones, interruptores de láminas, botones LED, sensores de fugas, sensores de movimiento, sensores de temperatura, tiras de LED, tiras RGB de 3-4-5 canales, tiras WS2812B, dispositivos RS485 ( Sólo para Metaforsa 3.plus);
  • conector (7) — conexión del módulo de expansión.

La configuración física y la asignación del punto de contacto de cada conector se muestran en la tabla 2.

Tabla 2
Conector Contacto Asignación
  1-10 Aplicación de carga (lámparas de luz, actuadores térmicos, etc.)
  D1-4, L, N Aplicación de carga (lámparas atenuantes)
Indicadores de estado del dispositivo Los indicadores de estado del módulo se describen en la tabla 3
  +24V
GND
+24 V: fuente de alimentación del módulo mediante una fuente de alimentación externa de 24 V GND: común
  RJ45 Conector para conectividad LAN
  In1-14, In15-28 GND Conexión de dispositivos de control (botones, botones LED, interruptores de láminas magnéticos, detectores de movimiento, sensores de fugas, sensores de temperatura, etc.):
In1 … In28 — entradas lógicas
GND — común
  VCC
GND
L
H
Conexión de módulos externos para CAN-bus
VСС — Salida de 24 V para fuente de alimentación de dispositivos externos
GND — común
L — Bus de datos CAN-L
H — Bus de datos CAN-H
Table3
Indicator Status Description
Power   Power
  Power not available
Activity   Data communication
  Data communication not available
Error   No errors
  Communication error
   Module overheat
    Dimmer outputs module overload
     Absence of power on dimmers, if in configuration

Instalación y montaje del sistema

Antes de conectar el sistema, debe:


  • coloque el sensor y los actuadores (si no están preinstalados), configure los sensores y actuadores;
  • ubique el módulo y la fuente de alimentación.


Nota: El módulo debe instalarse cerca de la fuente de tensión de alimentación.


¡PRECAUCIÓN! Se debe proporcionar voltaje de alimentación de CA a la entrada del sistema a través del conjunto del disyuntor. Debe instalarse cerca de la fuente de alimentación.
  1. La potencia del conjunto del disyuntor debe cumplir con la capacidad de carga;
  2. No se puede conectar nada más que los conductores de fase al módulo, el cable neutro se conecta por separado.


El esquema típico de conexión del módulo METAFORSA 3/3.plus se muestra en la fig. 3.

 


Conexión de los actuadores

Conexión de las luces/contactor eléctrico/actuador térmico de calefacción

 
Fig. 4
Actuadores como la luz, el contactor eléctrico o el actuador térmico de calefacción deben conectarse en cualquiera de las salidas 1 a 10, el cable neutro y el cable de tierra deben conectarse directamente al tablero de distribución. El ejemplo de conexión se muestra en la Fig.4.


Conexión de dispositivo de alta carga

  Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.


Conexión de la válvula unipolar de suministro de agua/gas

Precaución: Antes de aplicar energía a la carga, asegúrese de que la configuración de salida del módulo METAFORSA sea correcta. La configuración incorrecta o la conexión incorrecta pueden provocar la falla del módulo y/o falla del equipo conectado al mismo, e incluso un incendio.
 
Fig. 5
La válvula unipolar de suministro de agua/gas se conecta a cualquiera de las salidas 1 – 10, el cable neutro y el cable de tierra se conectan directamente al cuadro de distribución. El ejemplo de conexión se muestra en la Fig.5.


Conexión de la válvula bipolar de suministro de agua/gas

Precaución: Antes de aplicar energía a la válvula, es necesario asegurarse de que la configuración de salida del módulo METAFORSA sea correcta. La configuración incorrecta puede provocar la aplicación de voltaje simultáneamente a ambos canales de la válvula, lo que puede resultar en la falla del módulo y/o falla del equipo conectado a él, e incluso un incendio.
 
Fig. 6
Se utilizan dos puntos de contacto adyacentes (por ejemplo, 3, 4) para conectar la válvula bipolar de suministro de agua/gas; en estas condiciones el cable neutro y el cable de tierra están conectados directamente al cuadro. El ejemplo de conexión se muestra en Fig.6.


Conexión del actuador de puerta unipolar

Precaución: Antes de aplicar energía al módulo, debe configurar correctamente el acceso a la aplicación. Los contactos mal configurados pueden provocar el fallo del módulo y/o del equipo conectado al mismo, e incluso un incendio.

 
Fig. 7
Se utiliza cualquier punto de contacto (por ejemplo, 3) para conectar los controladores de accionamiento de puerta unipolares. El ejemplo de conexión se muestra en la Fig.7.


Conexión del actuador de puerta bipolar

Precaución: Antes de aplicar energía al módulo, debe configurar correctamente las salidas en la aplicación. Los contactos configurados incorrectamente pueden provocar una alimentación simultánea de ambos canales, provocando el fallo del módulo y/o del equipo conectado al mismo, e incluso un incendio.

 
Fig. 8
Se deben utilizar dos puntos de contacto adyacentes (por ejemplo, 3, 4) para conectar el controlador de accionamiento de puerta bipolar. El ejemplo de conexión se muestra en la Fig.8.


Conexión del actuador de cortina/persiana/persiana con control de fuerza de 220 V

Precaución: Antes de aplicar energía al módulo, debe configurar correctamente las salidas en la aplicación. Los contactos configurados incorrectamente pueden provocar una alimentación simultánea de ambos canales, provocando el fallo del módulo y/o del equipo conectado al mismo, e incluso un incendio.

 
Fig. 9
Se deben utilizar dos puntos de contacto adyacentes (por ejemplo, 3, 4) para conectar el actuador de cortina/persiana/rolladens; en estas condiciones el cable neutro y el cable de tierra se conectan directamente al cuadro. El ejemplo de conexión se muestra en la Fig.9.


Conexión del actuador de cortina/persiana/persiana con control de bajo voltaje

Precaución: Antes de aplicar energía al módulo, debe configurar correctamente las salidas en la aplicación. Los contactos configurados incorrectamente pueden provocar una alimentación simultánea de ambos canales, provocando el fallo del módulo y/o del equipo conectado al mismo, e incluso un incendio.

 
Fig. 10
Se deben utilizar dos puntos de contacto adyacentes (por ejemplo, 3, 4) para conectar el actuador de cortina/persiana/rolladens con el control de bajo voltaje. El ejemplo de conexión se muestra en la Fig.10.

Conexión de elementos sensores/interruptores/botones

Conexión de sensores de movimiento/sensores de fuga

Los sensores de movimiento deben conectarse a cualquier entrada libre in1-in28; en estas condiciones su alimentación está conectada a los puntos de contacto de +5V y GND del grupo correspondiente. El ejemplo de conexión se muestra en la Fig.11.

 
Fig. 11 connection of motion sensors/leakage sensors


Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 12-13.

 

Fig. 12 connection of buttons/switching units
 

Fig. 13 connection of the magnetic reed switches (window/door position sensors)

Connection of temperature sensors

Temperature sensors are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 14.

 

Fig. 14 connection of temperature sensors

RGB connection scheme

CAUTION! Output channels should only be connected using amplifier which uses 5V PWM signal from IO output as input

 

Fig. 15 RGB connection

WS2812B connection scheme

 

Fig. 16 WS2812B connection

RS485 connection scheme

CAUTION! RS485 connection is only available for Metaforsa 3.plus and only occurs on 21 channel

 

Fig. 17 RS485 connection

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 18.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

io char[28] 98 io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • '0' - led-dimmer
  • '1' - halogen-dimmer
  • '2' - linear-dimmer
  • '3'..'6' - RGB-3..6 channels
  • 'z' - WS2812B -string
  • 'e' - led-button inverse
  • 'd' - led-button
  • 'c' - button inverse
  • 'b' - button
  • 's' - switch
  • 'k' - contact inverse
  • 'h' - contact
  • 'l' - leak
  • 'n' - Neptun
  • 'v' - motion inverse
  • 'm' - motion
  • 'r' - thermo-resistor
  • 't' - DALLAS
  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK'

Only for Metaforsa 3.plus
cfg string 98 9600/8N1 cfg='SPEED/BPS', where
  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"
[Protocol] string 98 Protocol setting is described by protocol parameter. The following

protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"
echo on; off 98 'off' For settings check out and testing echo parameter can be used. Module

echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"
 1		<item addr="349:1" auto-period="600" cfgid="197" name="Lamp 1" type="lamp"/>
 2		<item addr="349:2" auto-period="600" cfgid="197" name="Lamp 2" type="lamp"/>
 3		<item addr="349:3" auto-period="600" cfgid="197" name="Lamp 3" type="lamp"/>
 4		<item addr="349:4" auto-period="600" cfgid="197" name="Lamp 4" type="lamp"/>
 5		<item addr="349:5" auto-period="600" cfgid="197" name="Lamp 5" type="lamp"/>
 6		<item addr="349:6" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
 7			<automation name="Eco" temperature-level="16"/>
 8			<automation name="Comfort" temperature-level="22"/>
 9			<automation name="Hot" temperature-level="25"/>
10		</item>
11		<item addr="349:7" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
12			<automation name="Eco" temperature-level="16"/>
13			<automation name="Comfort" temperature-level="22"/>
14			<automation name="Hot" temperature-level="25"/>
15		</item>
16		<item addr="349:8" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
17			<automation name="Eco" temperature-level="16"/>
18			<automation name="Comfort" temperature-level="22"/>
19			<automation name="Hot" temperature-level="25"/>
20		</item>
21		<item addr="349:9" cfgid="197" name="Jalousie" sub-type="120" type="jalousie"/>
22		<item addr="349:11" auto-period="600" cfgid="197" name="Dimmer 1" type="dimmer-lamp"/>
23		<item addr="349:12" auto-period="600" cfgid="197" name="Dimmer 2" type="dimmer-lamp"/>
24		<item addr="349:13" auto-period="600" cfgid="197" name="Dimmer 3" type="dimmer-lamp"/>
25		<item addr="349:14" auto-period="600" cfgid="197" name="Dimmer 4" type="dimmer-lamp"/>
26		<item addr="349:16" cfgid="197" name="Door 1" type="door-sensor"/>
27		<item addr="349:17" cfgid="197" name="Door 2" type="door-sensor"/>
28		<item addr="349:18" cfgid="197" name="Door 3" type="door-sensor"/>
29		<item addr="349:19" cfgid="197" name="Door 4" type="door-sensor"/>
30		<item addr="349:20" cfgid="197" name="Door 5" type="door-sensor"/>
31		<item addr="349:21" cfgid="197" name="Door 6" type="door-sensor"/>
32		<item addr="349:22" cfgid="197" name="Door 7" type="door-sensor"/>
33		<item addr="349:23" cfgid="197" name="Door 8" type="door-sensor"/>
34		<item addr="349:24" cfgid="197" name="Door 9" type="door-sensor"/>
35		<item addr="349:25" cfgid="197" name="Door 10" type="door-sensor"/>
36		<item addr="349:26" cfgid="197" name="Door 11" type="door-sensor"/>
37		<item addr="349:27" cfgid="197" name="Door 12" type="door-sensor"/>
38		<item addr="349:28" cfgid="197" name="Door 13" type="door-sensor"/>
39		<item addr="349:29" cfgid="197" name="Door 14" type="door-sensor"/>
40		<item addr="349:30" cfgid="197" name="Door 15" type="door-sensor"/>
41		<item addr="349:31" cfgid="197" name="Door 16" type="door-sensor"/>
42		<item addr="349:32" cfgid="197" name="Door 17" type="door-sensor"/>
43		<item addr="349:33" cfgid="197" name="Door 18" type="door-sensor"/>
44		<item addr="349:34" cfgid="197" name="Door 19" type="door-sensor"/>
45		<item addr="349:35" cfgid="197" name="Door 20" type="door-sensor"/>
46		<item addr="349:36" cfgid="197" name="Door 21" type="door-sensor"/>
47		<item addr="349:37" cfgid="197" name="Door 22" type="door-sensor"/>
48		<item addr="349:38" cfgid="197" name="Door 23" type="door-sensor"/>
49		<item addr="349:39" cfgid="197" name="Door 24" type="door-sensor"/>
50		<item addr="349:40" cfgid="197" name="Door 24" type="door-sensor"/>
51		<item addr="349:41" cfgid="197" name="Door 25" type="door-sensor"/>
52		<item addr="349:43" cfgid="197" name="IR receiver" type="ir-receiver"/>
53		<item addr="349:44" cfgid="197" name="RS485" type="com-port"/>
54		<item addr="349:90" cfgid="197" name="Current" system="yes" type="current-sensor"/>
55		<item addr="349:95" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
56		<item addr="349:96" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
57		<item addr="349:97" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
58		<item addr="349:98" cfgid="197" hw="out='LLLLLHHHB-' dm='LLLL' io='KKKKKKKKKKKKKKKKKKKKUKKKKKK-'" logic-ver="19" name="Temperature" sn="2533726919" system="yes" type="temperature-sensor"/>
59		<item addr="349:100" cfgid="197" name="RS232" type="com-port"/>