Metaforsa 3/3.plus

Revision as of 07:58, 8 April 2024 by Support (talk | contribs) (Created page with "====Priključak svjetla/električni kontaktor/termički aktuator grijanja====")
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF3/MF3.plus
METAFORSA 3 MF3-14.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs28
General
Max CAN devices4 (can be extended with the license) 99 (for Metaforsa 3.plus)
Max CAN bus length800 m (twisted pair CAT5e)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x90x58 mm


Uvod

Uputstvo za instalaciju METAFORSA SMART HOUSE opisuje proceduru za njegovu instalaciju, montažu, rad i podešavanje. Dok radite sa sistemom, morate se striktno pridržavati svih zahtjeva navedenih u ovom priručniku. Nepridržavanje može dovesti do oštećenja uređaja, njegovog kvara, strujnog udara, požara i drugih ispada. Proizvođač zadržava pravo izmjene ovog priručnika bez prethodne najave. Ovaj priručnik je sastavni dio sistema i ostaće krajnjem korisniku.

Karakteristike

  • Podržava 10 univerzalnih izlaza:
    • Svjetla
    • NC/NO ventili za grijanje
    • Blinds
    • 1 ili 2-polne kapije
    • 1 ili 2-polni ventili
    • NC/NO brave
    • Fan coil jedinice
  • 4 izlaza za zatamnjivanje
  • 28 ulaza koji podržavaju:
    • Dugmad
    • LED dugmad
    • Prekidači
    • Reed prekidači
    • Senzori curenja
    • Detektori pokreta
    • Temperaturni senzori
    • LED trake
    • 3-4-5 kanalne RGB trake
    • WS2812B trake
    • RS485 uređaji (samo za Metaforsa 3.plus)
  • Priključak za proširenje
  • Releji sa AgSnO2 kontaktima predviđeni za udarnu struju od 80A 20ms
  • Cloud konekcija i kontrola svih kućnih sistema
  • Upravljanje glasom (Siri, Alexa, Google Home)

Sigurnosni zahtjevi

OPREZ! Sve radove vezane za instalaciju, povezivanje, postavljanje, servis i podršku mora izvoditi kvalifikovano osoblje sa dovoljnim vještinama i iskustvom u radu sa električnom opremom.

Kako bi se izbjegao rizik od požara, strujnog udara, oštećenja sistema i/ili ličnih ozljeda, instalacija i montaža sistema moraju se izvesti u skladu sa uputstvima navedenim u nastavku:


  • svi radovi na priključenju moraju se izvoditi bez struje;
  • koristite odgovarajući alat i ličnu zaštitu od strujnog udara;
  • ne koristite oštećene kablove, žice i konektore;
  • izbjegavajte savijanje kablova i žica;
  • nemojte štipati ili savijati kablove i žice primenom prekomerne sile. U suprotnom, unutrašnji provodnici kabla i žica mogu biti ogoljeni ili slomljeni;
  • nemojte koristiti strujnu utičnicu sa lošim kontaktima za povezivanje;
  • nemojte prekoračiti ograničenje parametara opterećenja navedeno u ovom priručniku;
  • presjek žice provodnika za napajanje podliježe specifikacijama za ograničenje gustine struje, vrstu izolacije i materijal žice. Lagani dio može dovesti do pregrijavanja kabla i požara.


Prilikom rada sa sistemom nakon napajanja naponom NIKAD:

  • izvršiti spajanje/odspajanje konektora;
  • otvoreni moduli i senzori.

Konfiguracija sistema i svrha

Svrha sistema

METAFORSA SMART HOUSE je gotovo rešenje za automatizaciju stambenih i poslovnih prostora, hotelskih kompleksa koje uključuje najpoželjnije karakteristike Pametne kuće.


Uređaj ima 10 kontrolnih kanala, 4 kanala za zatamnjivanje i 28 ulaznih kanala br.


Univerzalni izlazi se mogu koristiti za upravljanje: Univerzalni ulazi vam omogućavaju da povežete:
Rasveta Dugmad/LED tipke/preklopne jedinice
Utičnice Magnetni reed prekidači
Podno grijanje Senzori curenja
Zavjesa Detektori pokreta
Aktivatori za kapije Senzori temperature
Vodovod LED trake/3-4-5 kanalne RGB trake/WS2812B trake
Ventili za grijanje RS485 uređaji*

* – Samo za Metaforsa 3.plus


Port za proširenje


Port za proširenje omogućava nadogradnju sistema povezivanjem pomoćne opreme, kao što je upravljački modul za LED rasvjetu, dimiranje, mjerne uređaje i druge elemente. Paket, koji je potpuno spreman za instalaciju, uključuje osnovni hardver i softver.

Sadržaj paketa

Paket standardno dolazi sa:{| class="wikitable" |- | Mainframe METAFORSA 3/3.plus || 1 kom |- | Jedinica za napajanje MEANWELL DR-15-12 || 1 kom |- | Senzor pokreta CW-MSD || 3 kom |- | Senzor curenja FW-WL.B || 2 kom |- | Element osjetljiv na temperaturu FW-TS || 4 kom |- | Magnetski reed prekidač (senzor položaja prozora/vrata) || 4 kom |- | Filter šuma za Ethernet kabl || 1 kom |- | Kabl za napajanje || 1 kom |}

Osnovne tehničke specifikacije sistema

Osnovne specifikacije i karakteristike modula METAFORSA 3/3.plus prikazane su u tabeli 1

Tabel 1
Specifikacija Značenje
Izlazni portovi
Broj komutiranih kanala 10
Broj komutiranih grupa 10
Broj kanala za zatamnjivanje 4
Komutacijski napon 0-250 V AC/DC
Vršno opterećenje (jedan kanal) 16A
Vršno opterećenje (uređaj) 160A
Maksimalno opterećenje po kanalu za zatamnjenje 0.5A (110W na 220V)
Tip dimera MOSFET
Tip opterećenja dimera R,C
Vrsta zatamnjenja zadnja ivica
Vrsta priključka kabla za napajanje konektor
Dozvoljeni deo kabla za napajanje za povezivanje u utičnicu:
jednožilni kabl
kabl sa više provodnika
kabl sa više provodnika

0,5 … 4mm2
0,5 … 4mm2
0,5 … 2,5 mm2
Ulazni portovi
Broj diskretnih ulaza 28
Maksimalna struja na konektorima jednosmjernog napona 5 mA*
Ostalo
Radna temperatura okoline 0 … +45°S
temperatura skladištenja/transporta -10 … +50°S
Dozvoljena vlažnost 0 … 95% (bez kondenzacije)
Napajanje 11,5 … 27,5 V DC
24V, 0,75A Preporučeno
Maksimalna potražnja 0.5A
Dostupni interfejsi Ethernet, CAN
Tip autobusa CAN (4-žični)
CAN (4-žični) 800 m** (upredeni par CAT5e)
CAN tip žice FTP Cat 5E
CAN tip veze Konektor
Maksimalna dužina digitalne linije 30 m
Digital line Wide type UTP/FTP Cat 5E
LAN maksimalna dužina 100 m
vrsta LAN žice UTP/FTP Cat 5E
LAN tip veze Konektor RJ-45
RS485 portovi kol 1***
Brzina prijenosa podataka 1200-115200 b/s***
Dimenzionalne specifikacije 9U, 156x90x58 mm
Materijal ljuske ABS
Kućište IP40
Tip ugradnje opreme DIN šina (EN 60715)
Težina 400 g

* – Izlazne kanale treba povezati samo pomoću pojačala koje koristi 5V PWM signal iz IO izlaza kao ulaz

** – potrebna je ugradnja dodatnih jedinica za napajanje za duge linije; maksimalna dužina linije može biti smanjena različitim faktorima interferencije

*** – Samo za Metaforsa 3.plus

Opća struktura sistema

Opšti izgled modula je prikazan na 'sl. 1


 


1 — konektor za primenu opterećenja
2 — konektor za primenu lampi za prigušivanje
3 — konektor za napajanje
4 — Ethernet mrežni konektor
5-6 — konektori za univerzalne ulazno/izlazne kanale
7 — konektor za modul za proširenje.


Pregled eksternih konektora uređaja METAFORSA: Na vrhu kućišta (sl. 1) nalazi se:


  • konektor (1) — Veza uređaja;
  • konektor (2) — Priključak lampi za prigušivanje;


Na dnu kućišta (sl. 1) nalazi se:


  • konektor (3) — priključak za napajanje modula;
  • konektor (4) — Ethernet mrežna veza;
  • konektori (5-6) — povezivanje univerzalnih ulazno/izlaznih kanala – dugmad, reed prekidači, LED dugmad, senzori curenja, senzori pokreta, senzori temperature, LED trake, 3-4-5 kanalne RGB trake, WS2812B trake, RS485 uređaji ( Samo za Metaforsa 3.plus);
  • konektor (7) — priključak modula za proširenje.

Fizička konfiguracija i dodjela kontaktnih mjesta svakog konektora prikazani su u tablici 2.

Tabela 2
Konektor Kontakt Dodatak
  1-10 Primjena opterećenja (svjetleće lampe, termički aktuatori, itd.)
  D1-4, L, N Aplikacija opterećenja (zatamnjene lampe)
Indikatori statusa uređaja Indikatori statusa modula su opisani u tablici 3
  +24V
GND
+24V — napajanje modula preko eksternog napajanja od 24 V GND — zajedničko
  RJ45 Konektor za LAN povezivanje
  In1-14, In15-28 GND Povezivanje upravljačkih uređaja (tipke, LED tipke, magnetni reed prekidači, detektori pokreta, senzori curenja, senzori temperature, itd.):
In1 … In28 — logički ulazi
GND — zajednički
  VCC
GND
L
H
Veza eksternih modula za CAN-bus
VSS — 24V izlaz za napajanje eksternih uređaja
GND — uobičajena
L — CAN-L sabirnica podataka
H — CAN-H sabirnica podataka
Table3
Indicator Status Description
Power   Power
  Power not available
Activity   Data communication
  Data communication not available
Error   No errors
  Communication error
   Module overheat
    Dimmer outputs module overload
     Absence of power on dimmers, if in configuration

Instalacija i montaža sistema

Prije povezivanja sistema morate:


  • ugradite senzor i aktuatore (ako nisu prethodno instalirani), postavite senzore i aktuatore;
  • lokacija modula i napajanja.


Napomena: Modul mora biti instaliran blizu izvora napona napajanja.


OPREZ! Napon napajanja naizmeničnom strujom mora biti obezbeđen na ulaz sistema kroz sklop prekidača. Treba ga instalirati blizu izvora napajanja.
  1. Snaga sklopa prekidača mora biti u skladu sa kapacitetom opterećenja;
  2. Ništa drugo osim faznih provodnika se ne može spojiti na modul, neutralna žica se spaja zasebno.


Tipični dijagram povezivanja modula METAFORSA 3/3.plus prikazan je na 'sl. 3.

 


Priključak aktuatora

Priključak svjetla/električni kontaktor/termički aktuator grijanja

 
Fig. 4
Such actuators as light, electric contactor, heating thermal actuator should be switched on any of the outputs 1 – 10, the neutral wire and the ground wire should be connected directly to the switchboard. The example of connection is shown in Fig.4.


Connection of high load device

  Recomended contactors:
  • ABB ESB series
  • Schneider Acti 9 iCT series
  • Hager ESC series.


Connection of single-pole water/gas supply valve

Caution: Before applying power to the load, make sure that the output configuration of METAFORSA module is correct. The incorrect configuration or incorrect connection can cause the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 5
The single pole water/gas supply valve is connected to any of the outputs of 1 – 10, the (neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.5.


Connection of double-pole water/gas supply valve

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
 
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Connection of single-pole gate actuator

Caution: Before applying power to the module, you should properly configure access to the application. The contacts incorrectly configured can result in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 7
Any contact point (for example, 3) is used to connect the single-pole gate drive controllers. The example of connection is shown in Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

 
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors/leakage sensors

The motion sensors/leakage sensors should be connected to any free input in1-in28; in these conditions their power is connected to the contact points of +5V and GND of the relevant group. The example of connection is shown in Fig.11.

 
Fig. 11 connection of motion sensors/leakage sensors


Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 12-13.

 

Fig. 12 connection of buttons/switching units
 

Fig. 13 connection of the magnetic reed switches (window/door position sensors)

Connection of temperature sensors

Temperature sensors are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 14.

 

Fig. 14 connection of temperature sensors

RGB connection scheme

CAUTION! Output channels should only be connected using amplifier which uses 5V PWM signal from IO output as input

 

Fig. 15 RGB connection

WS2812B connection scheme

 

Fig. 16 WS2812B connection

RS485 connection scheme

CAUTION! RS485 connection is only available for Metaforsa 3.plus and only occurs on 21 channel

 

Fig. 17 RS485 connection

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 18.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

io char[28] 98 io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • '0' - led-dimmer
  • '1' - halogen-dimmer
  • '2' - linear-dimmer
  • '3'..'6' - RGB-3..6 channels
  • 'z' - WS2812B -string
  • 'e' - led-button inverse
  • 'd' - led-button
  • 'c' - button inverse
  • 'b' - button
  • 's' - switch
  • 'k' - contact inverse
  • 'h' - contact
  • 'l' - leak
  • 'n' - Neptun
  • 'v' - motion inverse
  • 'm' - motion
  • 'r' - thermo-resistor
  • 't' - DALLAS
  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK'

hw string 98 - hw="...", where
  • pwm_invert – PWM inverting [1, 0];
  • lbn_bright – brightness of led buttons, range (0 - 255);
  • f – by default PWM frequency is 1000, range (1 - 5000).

Example:

1hw="io='4---zdd----t--' pwm_invert=1 lbn_bright=255 f=1000"
Only for Metaforsa 3.plus
cfg string 98 9600/8N1 cfg='SPEED/BPS', where
  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"
[Protocol] string 98 Protocol setting is described by protocol parameter. The following

protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"
echo on; off 98 'off' For settings check out and testing echo parameter can be used. Module

echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"
 1		<item addr="349:1" auto-period="600" cfgid="197" name="Lamp 1" type="lamp"/>
 2		<item addr="349:2" auto-period="600" cfgid="197" name="Lamp 2" type="lamp"/>
 3		<item addr="349:3" auto-period="600" cfgid="197" name="Lamp 3" type="lamp"/>
 4		<item addr="349:4" auto-period="600" cfgid="197" name="Lamp 4" type="lamp"/>
 5		<item addr="349:5" auto-period="600" cfgid="197" name="Lamp 5" type="lamp"/>
 6		<item addr="349:6" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
 7			<automation name="Eco" temperature-level="16"/>
 8			<automation name="Comfort" temperature-level="22"/>
 9			<automation name="Hot" temperature-level="25"/>
10		</item>
11		<item addr="349:7" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
12			<automation name="Eco" temperature-level="16"/>
13			<automation name="Comfort" temperature-level="22"/>
14			<automation name="Hot" temperature-level="25"/>
15		</item>
16		<item addr="349:8" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
17			<automation name="Eco" temperature-level="16"/>
18			<automation name="Comfort" temperature-level="22"/>
19			<automation name="Hot" temperature-level="25"/>
20		</item>
21		<item addr="349:9" cfgid="197" name="Jalousie" sub-type="120" type="jalousie"/>
22		<item addr="349:11" auto-period="600" cfgid="197" name="Dimmer 1" type="dimmer-lamp"/>
23		<item addr="349:12" auto-period="600" cfgid="197" name="Dimmer 2" type="dimmer-lamp"/>
24		<item addr="349:13" auto-period="600" cfgid="197" name="Dimmer 3" type="dimmer-lamp"/>
25		<item addr="349:14" auto-period="600" cfgid="197" name="Dimmer 4" type="dimmer-lamp"/>
26		<item addr="349:16" cfgid="197" name="Door 1" type="door-sensor"/>
27		<item addr="349:17" cfgid="197" name="Door 2" type="door-sensor"/>
28		<item addr="349:18" cfgid="197" name="Door 3" type="door-sensor"/>
29		<item addr="349:19" cfgid="197" name="Door 4" type="door-sensor"/>
30		<item addr="349:20" cfgid="197" name="Door 5" type="door-sensor"/>
31		<item addr="349:21" cfgid="197" name="Door 6" type="door-sensor"/>
32		<item addr="349:22" cfgid="197" name="Door 7" type="door-sensor"/>
33		<item addr="349:23" cfgid="197" name="Door 8" type="door-sensor"/>
34		<item addr="349:24" cfgid="197" name="Door 9" type="door-sensor"/>
35		<item addr="349:25" cfgid="197" name="Door 10" type="door-sensor"/>
36		<item addr="349:26" cfgid="197" name="Door 11" type="door-sensor"/>
37		<item addr="349:27" cfgid="197" name="Door 12" type="door-sensor"/>
38		<item addr="349:28" cfgid="197" name="Door 13" type="door-sensor"/>
39		<item addr="349:29" cfgid="197" name="Door 14" type="door-sensor"/>
40		<item addr="349:30" cfgid="197" name="Door 15" type="door-sensor"/>
41		<item addr="349:31" cfgid="197" name="Door 16" type="door-sensor"/>
42		<item addr="349:32" cfgid="197" name="Door 17" type="door-sensor"/>
43		<item addr="349:33" cfgid="197" name="Door 18" type="door-sensor"/>
44		<item addr="349:34" cfgid="197" name="Door 19" type="door-sensor"/>
45		<item addr="349:35" cfgid="197" name="Door 20" type="door-sensor"/>
46		<item addr="349:36" cfgid="197" name="Door 21" type="door-sensor"/>
47		<item addr="349:37" cfgid="197" name="Door 22" type="door-sensor"/>
48		<item addr="349:38" cfgid="197" name="Door 23" type="door-sensor"/>
49		<item addr="349:39" cfgid="197" name="Door 24" type="door-sensor"/>
50		<item addr="349:40" cfgid="197" name="Door 24" type="door-sensor"/>
51		<item addr="349:41" cfgid="197" name="Door 25" type="door-sensor"/>
52		<item addr="349:43" cfgid="197" name="IR receiver" type="ir-receiver"/>
53		<item addr="349:44" cfgid="197" name="RS485" type="com-port"/>
54		<item addr="349:90" cfgid="197" name="Current" system="yes" type="current-sensor"/>
55		<item addr="349:95" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
56		<item addr="349:96" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
57		<item addr="349:97" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
58		<item addr="349:98" cfgid="197" hw="out='LLLLLHHHB-' dm='LLLL' io='KKKKKKKKKKKKKKKKKKKKUKKKKKK-'" logic-ver="19" name="Temperature" sn="2533726919" system="yes" type="temperature-sensor"/>
59		<item addr="349:100" cfgid="197" name="RS232" type="com-port"/>