Metaforsa 3/3.plus

From Larnitech wiki page
Revision as of 13:26, 3 April 2024 by FuzzyBot (talk | contribs) (Updating to match new version of source page)
Jump to navigation Jump to search
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF3/MF3.plus
METAFORSA 3 MF3-14.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs28
General
Max CAN devices4 (can be extended with the license) 99 (for Metaforsa 3.plus)
Max CAN bus length800 m (twisted pair CAT5e)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x90x58 mm


Введение

Руководство по установке модуля METAFORSA описывает порядок его установки, сборки, эксплуатации и настройки. При работе с системой необходимо строго соблюдать все требования, изложенные в данном руководстве. Несоблюдение этих требований может привести к повреждению устройства, его выходу из строя, поражению электрическим током, возгоранию и другим последствиям. Производитель оставляет за собой право вносить изменения в данное руководство без предварительного уведомления. Это руководство является неотъемлемой частью системы и должно храниться у конечного потребителя.

Функции

  • Поддержка 10 универсальных выходов:
    • освещение
    • Клапаны отопления
    • жалюзи
    • 1 или 2-полюсные ворота
    • 1 или 2-полюсные клапаны
    • NC/NO замки
    • Вентиляторы
  • 4 выхода диммирования
  • 28 входов, поддерживающих:
    • Кнопки
    • Светодиодные кнопки
    • Переключатели
    • Корневые выключатели
    • Датчики протечек
    • Датчики движения
    • Датчики температуры
    • Светодиодные ленты
    • 3-4-5-канальные RGB-полосы
    • WS2812B полоски
    • Устройства RS485 (только для Metaforsa 3.plus)
  • Дополнительный порт
  • Реле с контактами AgSnO2, рассчитанными на пусковой ток 80A 20 мс
  • Подключение к облаку и управление всеми системами дома
  • Голосовое управление (Siri, Alexa, Google Home)

Требования безопасности

ВНИМАНИЕ! Все работы, связанные с установкой, подключением, настройкой, обслуживанием и поддержкой, должны выполняться квалифицированным персоналом, имеющим достаточные навыки и опыт работы с электрооборудованием.

Во избежание риска возгорания, поражения электрическим током, повреждения системы и/или травм, установка и сборка системы должны выполняться в соответствии с инструкциями, перечисленными ниже:


  • все работы по подключению должны выполняться без питания;
  • используйте соответствующие инструменты и средства индивидуальной защиты от поражения электрическим током;
  • не используйте поврежденные кабели, провода и разъемы;
  • избегайте сгибания кабелей и проводов;
  • не защемляйте и не перегибайте кабели и провода, прилагая чрезмерное усилие. В противном случае внутренние проводники кабеля и проводов могут быть зачищены или сломаны;
  • не используйте для подключения розетки с плохими контактами;
  • не превышайте предельные параметры нагрузки, указанные в данном руководстве;
  • на сечение проводов питания распространяются требования к предельной плотности тока, типу изоляции и материалу проводов. Светлое сечение может привести к перегреву кабеля и возгоранию.


При работе с системой после подачи напряжения НИКОГДА:

  • не производите подключение/отключение разъемов;
  • не открывайте модули и датчики.

Конфигурация и назначение системы

Назначение системы

Модуль METAFORSA - это готовое решение для автоматизации жилых и коммерческих помещений, гостиничных комплексов, которое включает в себя самые востребованные функции Умного дома.


Устройство имеет 10 каналов управления, 4 канала диммирования и 28 входных каналов в количестве.


Универсальные выходы можно использовать для управления: ! Универсальные входы позволяют подключать:
Освещение Кнопки/светодиодные кнопки/переключатели
Полы с подогревом Датчики протечки
Шторы Детекторы движения
Приводы для ворот Датчики температуры
Водоснабжение Светодиодные ленты/3-4-5 канальные RGB ленты/WS2812B ленты
Клапаны отопления Устройства RS485*

* - Только для Metaforsa 3.plus


Порт расширения


Порт расширения позволяет модернизировать систему, подключая дополнительное оборудование, такое как модуль управления светодиодным освещением, диммированием, измерительными приборами и другими элементами. Комплект, полностью готовый к установке, включает в себя базовое оборудование и программное обеспечение.

Комплектация

В стандартную комплектацию входят:

Основной модуль METAFORSA 3/3.plus 1 шт.
Блок питания MEANWELL DR-15-12 1 шт.
Датчик движения CW-MSD 3 шт.
Датчик утечки FW-WL.B 2 шт.
Чувствительный к температуре элемент FW-TS 4 шт.
Магнитный геркон (датчик положения окна/двери) 4 шт.
Фильтр помех для Ethernet-кабеля 1 шт.
Шнур питания 1 шт.

Основные технические характеристики системы

Основные спецификации и характеристики модуля METAFORSA 3/3.plus приведены в таблице 1

Таблица 1
Спецификация Значение
Выходные порты
Количество переключаемых каналов 10
Количество коммутируемых групп 10
Количество каналов регулировки яркости 4
Коммутируемое напряжение 0–250 В переменного/постоянного тока
Пиковая нагрузка (один канал) 16А
Пиковая нагрузка (устройство) 160А
Максимальная нагрузка на канал диммирования 0,5 А (110 Вт при 220 В)
Тип диммера МОП-транзистор
Тип нагрузки диммера Р, Ц
Тип затемнения задняя кромка
Тип подключения кабеля питания разъем
Допустимое сечение кабеля электропитания для подключения к розетке:
одножильный кабель
многожильный кабель
многожильный кабель с наконечниками

0,5 … 4 мм2
0,5 … 4 мм2
0,5…2,5мм2
Входные порты
Количество дискретных входов 28
Максимальный номинальный ток на разъемах постоянного тока 5 мА*
Другое
Рабочая температура окружающей среды 0 … +45°С
Температура хранения/транспортировки -10…+50°С
Допустимая влажность 0…95 % (без конденсации)
Источник питания 11,5…27,5 В пост. тока
24 В, 0,75 А Рекомендуется
Максимальный спрос 0,5А
Доступные интерфейсы Ethernet, CAN
Тип автобуса CAN (4-проводной)
CAN (4-проводной) 800 м** (витая пара CAT5e)
Тип провода CAN FTP-категория 5E
Тип соединения CAN Разъем
Максимальная длина цифровой линии 30 м
Цифровая линия проводного типа UTP/FTP категории 5E
Максимальная длина локальной сети 100 м
Тип провода локальной сети UTP/FTP категории 5E
Тип подключения к локальной сети Разъем RJ-45
Количество портов RS485 1***
Скорость передачи данных 1200-115200 б/с***
Размерные характеристики 9U, 156x90x58 мм
Материал корпуса АБС
Корпус IP40
Тип установки оборудования DIN-рейка (EN 60715)
Вес 400 г

* – Выходные каналы следует подключать только с помощью усилителя, который использует сигнал ШИМ 5 В с выхода ввода-вывода в качестве входного.

** – для длинных линий требуется установка дополнительных блоков питания; максимальная длина линии может быть уменьшена из-за различных факторов помех

*** – только для Metaforsa 3.plus

Общая структура системы

Общий вид модуля представлен на рис. 1


Рис. 1 Общий вид модуля


1 — разъем для приложения нагрузки
2 — разъем для применения диммирующих ламп
3 — разъем питания
4 — Разъем сети Ethernet
5-6 — разъемы для универсальных каналов ввода/вывода
7 — разъем для модуля расширения.


Общая схема внешних разъемов устройства METAFORSA В верхней части корпуса (рис. 1) расположены:


  • разъем (1) - подключение устройств;
  • разъем (2) - подключение диммирующего освещения;


В нижней части корпуса (рис. 1) расположены:


  • разъем (3) — подключение питания модуля;
  • разъем (4) — подключение к сети Ethernet;
  • разъемы (5-6) — универсальное подключение каналов ввода-вывода — кнопки, герконы, светодиодные кнопки, датчики протечки, датчики движения, датчики температуры, светодиодные ленты, 3-4-5-канальные RGB ленты, ленты WS2812B, устройства RS485 ( Только для Metaforsa 3.plus);
  • разъем (7) — подключение модуля расширения.

Конфигурация и назначение контактов каждого разъема показаны в Таблице 2.

Таблица 2
Разъем Контакт Назначение
Out.png 1-10 Приложение нагрузки (световые лампы, термоприводы и т. д.)
Dimm.png D1-4, L, N Применение нагрузки (регулирование яркости ламп)
Индикаторы состояния устройства Индикаторы состояния модуля описаны в таблице 3.
24vconn.png +24V
GND
+24В — питание модуля от внешнего источника питания 24 В GND — общий
Rj45.jpg RJ45 Разъем для подключения к локальной сети
IOC CONN.png In1-14, In15-28 GND Подключение управляющих устройств (кнопок, светодиодных кнопок, герконов, датчиков движения, датчиков протечек, датчиков температуры и т.п.):
In1 … In28 — логические входы
GND — общий
Can.jpg VCC
GND
L
H
Подключение внешних модулей для CAN-шины
VСС — Выход 24В для питания внешних устройств
GND — общий
L — Шина данных CAN-L
H — Шина данных CAN-H
Table3
Indicator Status Description
Power G.png Power
E.png Power not available
Activity Y.png Data communication
E.png Data communication not available
Error E.png No errors
R.png Communication error
R.pngR.png Module overheat
R.pngR.pngR.png Dimmer outputs module overload
R.pngR.pngR.pngR.png Absence of power on dimmers, if in configuration

Установка и сборка системы

Перед подключением системы необходимо:


  • определить места установки датчиков и реле (если они не были предварительно установлены), установить датчики и реле;
  • определить места установки модуля и блока питания.


Примечание: модуль необходимо устанавливать рядом с источником питания.


ВНИМАНИЕ! Напряжение переменного тока должно подаваться на вход системы через автоматический выключатель (предохранитель). Он должен быть установлен рядом с источником питания.
  1. Мощность предохранителя должна соответствовать допустимой нагрузке;
  2. К модулю нельзя подключать ничего, кроме фазных проводов, нейтральный провод подключается отдельно.


Типовая схема подключения модуля METAFORSA 3/3.plus представлена на рис. 3.

Fig. 3


Подключение реле

Подключение освещения/электрического контактора/термореле отопления

lamp
Fig. 4
Такие реле, как освещение, электрический контактор, термореле отопления должны быть подключены к любому из выходов 1-10, а нейтральный провод и заземление должны быть подключены непосредственно к распределительному щиту. Пример подключения показан на рис. 4.


Подключение устройства с высокой нагрузкой

Contactor Рекомендуемые контакторы:
  • ABB серии ESB
  • Schneider Acti 9 серии iCT
  • Hager серии ESC.


Подключение однополюсного клапана подачи воды/газа

Внимание: прежде чем подавать питание на нагрузку, убедитесь, что конфигурация выходов модуля METAFORSA правильна. Неправильная конфигурация или неправильное подключение могут привести к выходу из строя модуля и/или выходу из строя подключенного к нему оборудования и даже пожару.
valve
Рис. 5
Однополюсный клапан подачи воды/газа подключается к любому из выходов 1 – 10, нулевой провод и заземляющий провод подключаются непосредственно к распределительному щиту. Пример подключения показан на рис. Рис.5.


Подключение двухполюсного клапана подачи воды/газа

Внимание: перед подачей питания на клапан необходимо убедиться в правильности выходной конфигурации модуля METAFORSA. Неправильная конфигурация может привести к подаче напряжения одновременно на оба канала клапана, что может привести к выходу из строя модуля и/или выходу из строя подключенного к нему оборудования и даже пожару.
valve
Рис. 6
Две соседние точки контакта (например, 3, 4) используются для подключения двухполюсного клапана подачи воды/газа; в этих условиях нейтральный провод и заземляющий провод подключаются непосредственно к распределительному щиту. Пример подключения показан на Рис.6.


Подключение однополюсного привода ворот

Внимание: перед подачей питания на модуль необходимо правильно настроить доступ к контактам в приложении. Неправильно настроенные контакты могут привести к выходу модуля из строя и/или к отказу подключенного к нему оборудования, и даже к возгоранию.

1pgate
Fig. 7
Для подключения однополюсных контроллеров приводов ворот используется любой контакт (например, 3). Пример подключения показан на рис. 7.


Подключение двухполюсного привода ворот

Внимание! Перед подачей питания на модуль необходимо правильно настроить выходы в приложении. Неправильно настроенные контакты могут привести к одновременной подаче питания на оба канала, что может привести к выходу модуля из строя и/или отказу подключенного к нему оборудования, и даже к возгоранию.

2pgate
Fig. 8
Для подключения двухполюсного контроллера привода ворот используются два смежных контакта (например, 3 и 4). Пример подключения показан на рис. 8.


Подключение привода штор/жалюзи/ставней с регулировкой усилия 220 В

Внимание! Перед подачей питания на модуль необходимо правильно настроить выходы в приложении. Неправильно настроенные контакты могут привести к одновременной подаче питания на оба канала, что может привести к выходу модуля из строя и/или отказу подключенного к нему оборудования, и даже к возгоранию.

Pjalousie
Fig. 9
Для подключения привода штор/жалюзи/ставней используются два смежных контакта (например, 3 и 4), а нейтральный провод и заземление подключаются непосредственно к распределительному щиту. Пример подключения показан на рис. 9


Подключение привода штор/жалюзи/ставней с низковольтным управлением

Внимание! Перед подачей питания на модуль необходимо правильно настроить выходы в приложении. Неправильно настроенные контакты могут привести к одновременной подаче питания на оба канала, что может привести к выходу модуля из строя и/или отказу подключенного к нему оборудования, и даже к возгоранию.

2pgate
Fig. 8
Для подключения привода штор/жалюзи/ставней с низковольтным управлением используются два смежных контакта (например, 3 и 4). Пример подключения показан на рис. 10.

Подключение датчиков/выключателей/кнопок

Подключение датчиков движения/датчиков протечек

Датчики движения подключаются к любому из свободных входов 1-28, а их питание подключается к контактам +5V и GND соответствующей группы. Пример подключения показан на рис. 11

IOC CONN LM.png
Рис. 11 подключение датчиков движения/протечек


Подключение кнопок/переключателей/герконов

Кнопки и герконы подключаются к любому свободному входу in1-in28, а их вторая точка контакта подключается к точке GND соответствующей группы модулей METAFORSA. Пример подключения показан на рис. 12-13.

Buttons MF3.png

Рис. 12 подключение кнопок/переключателей
Reed-sv MF3.png

Рис. 13 подключение магнитных герконов (датчиков положения окна/двери)

Подключение датчиков температуры

Датчики температуры подключаются к любому свободному входу in1-in28, а их вторая точка контакта подключается к точке GND соответствующей группы модулей METAFORSA. Пример подключения показан на рис. 14.

IOC CONN T.png

Fig. 14 connection of temperature sensors

RGB connection scheme

CAUTION! Output channels should only be connected using amplifier which uses 5V PWM signal from IO output as input

IOC RGB EX.png

Fig. 15 RGB connection

WS2812B connection scheme

IOC CONN WS.png

Fig. 16 WS2812B connection

RS485 connection scheme

CAUTION! RS485 connection is only available for Metaforsa 3.plus and only occurs on 21 channel

MF3plus rs485.png

Fig. 17 RS485 connection

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 18.

CAN MF3.png
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

io char[28] 98 io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • '0' - led-dimmer
  • '1' - halogen-dimmer
  • '2' - linear-dimmer
  • '3'..'6' - RGB-3..6 channels
  • 'z' - WS2812B -string
  • 'e' - led-button inverse
  • 'd' - led-button
  • 'c' - button inverse
  • 'b' - button
  • 's' - switch
  • 'k' - contact inverse
  • 'h' - contact
  • 'l' - leak
  • 'n' - Neptun
  • 'v' - motion inverse
  • 'm' - motion
  • 'r' - thermo-resistor
  • 't' - DALLAS
  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK'

Only for Metaforsa 3.plus
cfg string 98 9600/8N1 cfg='SPEED/BPS', where
  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"
[Protocol] string 98 Protocol setting is described by protocol parameter. The following

protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"
echo on; off 98 'off' For settings check out and testing echo parameter can be used. Module

echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"
 1		<item addr="349:1" auto-period="600" cfgid="197" name="Lamp 1" type="lamp"/>
 2		<item addr="349:2" auto-period="600" cfgid="197" name="Lamp 2" type="lamp"/>
 3		<item addr="349:3" auto-period="600" cfgid="197" name="Lamp 3" type="lamp"/>
 4		<item addr="349:4" auto-period="600" cfgid="197" name="Lamp 4" type="lamp"/>
 5		<item addr="349:5" auto-period="600" cfgid="197" name="Lamp 5" type="lamp"/>
 6		<item addr="349:6" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
 7			<automation name="Eco" temperature-level="16"/>
 8			<automation name="Comfort" temperature-level="22"/>
 9			<automation name="Hot" temperature-level="25"/>
10		</item>
11		<item addr="349:7" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
12			<automation name="Eco" temperature-level="16"/>
13			<automation name="Comfort" temperature-level="22"/>
14			<automation name="Hot" temperature-level="25"/>
15		</item>
16		<item addr="349:8" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
17			<automation name="Eco" temperature-level="16"/>
18			<automation name="Comfort" temperature-level="22"/>
19			<automation name="Hot" temperature-level="25"/>
20		</item>
21		<item addr="349:9" cfgid="197" name="Jalousie" sub-type="120" type="jalousie"/>
22		<item addr="349:11" auto-period="600" cfgid="197" name="Dimmer 1" type="dimmer-lamp"/>
23		<item addr="349:12" auto-period="600" cfgid="197" name="Dimmer 2" type="dimmer-lamp"/>
24		<item addr="349:13" auto-period="600" cfgid="197" name="Dimmer 3" type="dimmer-lamp"/>
25		<item addr="349:14" auto-period="600" cfgid="197" name="Dimmer 4" type="dimmer-lamp"/>
26		<item addr="349:16" cfgid="197" name="Door 1" type="door-sensor"/>
27		<item addr="349:17" cfgid="197" name="Door 2" type="door-sensor"/>
28		<item addr="349:18" cfgid="197" name="Door 3" type="door-sensor"/>
29		<item addr="349:19" cfgid="197" name="Door 4" type="door-sensor"/>
30		<item addr="349:20" cfgid="197" name="Door 5" type="door-sensor"/>
31		<item addr="349:21" cfgid="197" name="Door 6" type="door-sensor"/>
32		<item addr="349:22" cfgid="197" name="Door 7" type="door-sensor"/>
33		<item addr="349:23" cfgid="197" name="Door 8" type="door-sensor"/>
34		<item addr="349:24" cfgid="197" name="Door 9" type="door-sensor"/>
35		<item addr="349:25" cfgid="197" name="Door 10" type="door-sensor"/>
36		<item addr="349:26" cfgid="197" name="Door 11" type="door-sensor"/>
37		<item addr="349:27" cfgid="197" name="Door 12" type="door-sensor"/>
38		<item addr="349:28" cfgid="197" name="Door 13" type="door-sensor"/>
39		<item addr="349:29" cfgid="197" name="Door 14" type="door-sensor"/>
40		<item addr="349:30" cfgid="197" name="Door 15" type="door-sensor"/>
41		<item addr="349:31" cfgid="197" name="Door 16" type="door-sensor"/>
42		<item addr="349:32" cfgid="197" name="Door 17" type="door-sensor"/>
43		<item addr="349:33" cfgid="197" name="Door 18" type="door-sensor"/>
44		<item addr="349:34" cfgid="197" name="Door 19" type="door-sensor"/>
45		<item addr="349:35" cfgid="197" name="Door 20" type="door-sensor"/>
46		<item addr="349:36" cfgid="197" name="Door 21" type="door-sensor"/>
47		<item addr="349:37" cfgid="197" name="Door 22" type="door-sensor"/>
48		<item addr="349:38" cfgid="197" name="Door 23" type="door-sensor"/>
49		<item addr="349:39" cfgid="197" name="Door 24" type="door-sensor"/>
50		<item addr="349:40" cfgid="197" name="Door 24" type="door-sensor"/>
51		<item addr="349:41" cfgid="197" name="Door 25" type="door-sensor"/>
52		<item addr="349:43" cfgid="197" name="IR receiver" type="ir-receiver"/>
53		<item addr="349:44" cfgid="197" name="RS485" type="com-port"/>
54		<item addr="349:90" cfgid="197" name="Current" system="yes" type="current-sensor"/>
55		<item addr="349:95" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
56		<item addr="349:96" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
57		<item addr="349:97" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
58		<item addr="349:98" cfgid="197" hw="out='LLLLLHHHB-' dm='LLLL' io='KKKKKKKKKKKKKKKKKKKKUKKKKKK-'" logic-ver="19" name="Temperature" sn="2533726919" system="yes" type="temperature-sensor"/>
59		<item addr="349:100" cfgid="197" name="RS232" type="com-port"/>