Metaforsa2 MF-14

From Larnitech wiki page
Revision as of 11:12, 4 March 2024 by Support (talk | contribs) (Created page with "{{ConExC |Attention : Avant de mettre le module sous tension, vous devez correctement configurer l'accès à l'application. Des contacts mal configurés peuvent entraîner une...")
Jump to navigation Jump to search
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF-14
Metaforsa2.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs24
Number of digital inputs4
General
Max CAN devices50
Max CAN bus length800 m (twisted pair 5 cat)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


Présentation

Le manuel d'installation METAFORSA SMART HOUSE décrit la procédure d'installation, de montage, de fonctionnement et de réglage. Lorsque vous travaillez avec le système, vous devez strictement respecter toutes les exigences énoncées dans ce manuel. Le non-respect de ces consignes peut entraîner des dommages à l'appareil, une panne, un choc électrique, un incendie et d'autres conséquences. Le fabricant se réserve le droit d'apporter des modifications à ce manuel sans préavis. Ce manuel fait partie intégrante du système et doit rester chez le client final.

Caractéristiques

  • 10 sorties universelles prises en charge :
    • Lumières
    • Vannes de chauffage NC/NO
    • Stores
    • Portails 1 ou 2 pôles
    • Vannes 1 ou 2 pôles
    • Verrouillage NC/NO
    • Ventilo-convecteurs
  • 4 sorties de gradation
  • 24 entrées discrètes prenant en charge :
    • Boutons
    • Commutateurs
    • interrupteurs à lames
    • capteurs de fuite
    • détecteurs de mouvement
  • 4 entrées numériques pour jusqu'à 8 capteurs de température
  • Port d'extension
  • Relais avec contacts AgSnO2 évalués pour un courant d'appel de 80 A et 20 ms
  • Connexion au cloud et contrôle de tous les systèmes de la maison
  • Contrôle vocal (Siri, Alexa, Google Home)
  • Le moteur de plugins permet d'étendre les possibilités du système (par exemple, intégration avec les lumières Satel, Philips Hue, IKEA)
  • Sécurité contre les intrusions non autorisées assurée avec le cryptage RSA/AES256
  • Notifications push du système sur votre téléphone (également possible de recevoir via les messageries Telegram et Viber)
  • Historique (les données du compteur pendant 1 an sont stockées)
  • Plug and play (possibilité d'extension rapide et conviviale du système)
  • Mises à jour régulières du système
  • Grande base de données de scripts constamment mise à jour pour répondre à tous vos besoins
  • Sauvegardes quotidiennes automatiques via cloud avec possibilité de restaurer la configuration initiale
  • Open API (qui permet d'intégrer Larnitech dans d'autres systèmes)
  • Interface Web LT SETUP interactive et conviviale disponible pour une configuration avancée
  • Brancher et utiliser
  • Il s'agit d'un kit système Smart Home entièrement prêt à installer

Exigences de sécurité

ATTENTION ! Tous les travaux liés à l'installation, au raccordement, à la configuration, à l'entretien et à l'assistance doivent être effectués par du personnel qualifié possédant les compétences et l'expérience suffisantes pour travailler avec des équipements électriques.

Pour éviter tout risque d'incendie, de choc électrique, de dommages au système et/ou de blessures corporelles, l'installation et l'assemblage du système doivent être effectués conformément aux instructions répertoriées ci-dessous :


  • tous les travaux de raccordement doivent être effectués sans électricité ;
  • utiliser des outils appropriés et une protection personnelle contre les chocs électriques ;
  • n'utilisez pas de câbles, fils et connecteurs endommagés ;
  • éviter de plier les câbles et les fils ;
  • ne pincez pas et ne pliez pas les câbles et les fils en appliquant une force excessive. Sinon, les conducteurs internes du câble et des fils pourraient être dénudés ou cassés ;
  • n'utilisez pas la prise de courant avec de mauvais contacts pour vous connecter ;
  • ne dépassez pas la limite des paramètres de charge spécifiée dans ce manuel ;
  • la section des fils des conducteurs d'alimentation est soumise aux spécifications relatives à la limite de densité de courant, au type d'isolation et au matériau du fil. Une section légère peut entraîner une surchauffe du câble et un incendie.


Lorsque vous travaillez avec le système après l'alimentation en tension JAMAIS :

  • effectuer la connexion/déconnexion des connecteurs ;
  • Modules et capteurs ouverts.

Configuration et objectif du système

Objectif du système

METAFORSA SMART HOUSE est une solution prête à l'emploi pour l'automatisation des locaux résidentiels et commerciaux, des complexes hôteliers qui comprend les fonctionnalités les plus recherchées de Smart House.


L'appareil dispose de 10 canaux de contrôle, 4 canaux de gradation, 24 canaux de capteurs entrants et un port de connexion de capteurs numériques.


Les sorties universelles peuvent être utilisées pour contrôler : Les entrées universelles permettent de connecter :
Éclairage Boutons/unités de commutation
Connecteurs de prise Interrupteurs à lames magnétiques
Chauffage au sol Capteurs de mouvements
Actionneurs de rideaux/portails Capteurs de fuite
Vannes d'alimentation en eau/chauffage


Port de connexion des capteurs numériques


Le port de connexion des capteurs numériques vous permet de connecter une variété de capteurs numériques, tels que des capteurs de température, de lumière ambiante, d'humidité et autres.


Port d'extension


Le port d'extension vous permet de mettre à niveau le système en connectant des équipements auxiliaires, tels que le module de commande pour l'éclairage LED, la gradation, les dispositifs de mesure et d'autres éléments. Le package, entièrement prêt à installer, comprend le matériel et les logiciels de base.

Contenu du paquet

Le package est livré en standard avec :

Ordinateur central METAFORSA MF-14.А 1 pc
Bloc d'alimentation MEANWELL DR-15-12 1 pc
Capteur de mouvement CW-MSD 3 pièces
Capteur de fuite FW-WL.A 2 pièces
Élément sensible à la température FW-TS.A 4 pièces
Interrupteur à lames magnétique (capteur de position de fenêtre/porte) 4 pièces
Filtre anti-bruit pour câble Ethernet 1 pc
Cordon d'alimentation 1 pc

Spécifications techniques de base du système

Les spécifications et caractéristiques de base du module METAFORSA MF-14.A sont présentées dans le tableau 1.

Table1
Spécification Signification
Ports de sortie
Nombre de canaux commutés dix
Nombre de groupes commutés dix
Nombre de canaux de variation 4
Tension de commutation 0-250 V CA/CC
Charge de pointe (un canal) 16A
Charge de pointe (appareil) 160A
Charge maximale par canal de gradation 0,5A (110W à 220V)
Type de variateur MOSFET
Type de charge de gradateur R,C
Type de gradation bord de fuite
Type de connexion du câble d'alimentation connecteur
Section autorisée du câble d'alimentation à connecter dans la prise :
câble à un seul conducteur
câble à plusieurs conducteurs
câble à plusieurs conducteurs à pointe

0,5 … 4 mm2
0,5 … 4 mm2
0,5 … 2,5 mm2
Ports d'entrée
Nombre d'entrées discrètes 24
Nombre d'entrées numériques 4
Courant maximum nominal sur les connecteurs de tension continue 50mA
Autre
Température ambiante de fonctionnement 0 … +45°С
Température de stockage/transport -20 … +60°С
Humidité admissible 0 … 95 % (sans condensation)
Alimentation 12 … 27,5 V CC
24 V, 0,75 A recommandé
Demande maximale 0,5А
Interfaces disponibles Ethernet, CAN, OneWire
Type de bus CAN (4 fils)
CAN (4 fils) 800 m* (paire torsadée 5 cat)
Type de fil CAN FTP catégorie 5E
Type de connexion CAN connecteur
Longueur maximale de la ligne numérique 30 m
Type de câble de ligne numérique UTP/FTP catégorie 5E
Longueur maximale du réseau local 100 m
Type de fil LAN UTP/FTP catégorie 5E
Type de connexion LAN Connecteur RJ-45
Spécifications dimensionnelles 9U, 156x110x58mm
Matériau de la coque Plastique ABS
Boîtier IP40
Type d'installation de l'équipement Rail DIN (EN 60715)
Poids 400g

* – l'installation d'unités d'alimentation supplémentaires est requise pour les longues lignes ; la longueur maximale de la ligne peut être réduite par divers facteurs d'interférence

Structure générale du système

La vue générale du module est présentée dans la fig. 1


Fig. 1 Module general view


1 — connecteur pour application de charge
2 — connecteur pour application de lampes à gradation
3 - câble d'alimentation
4 — Connecteur réseau Ethernet
5-6 — connecteurs pour capteurs numériques et boutons/unités de commutation
7 — Connecteur d'interface OneWire (pour capteurs numériques)
8 — connecteur pour module d'extension.


Présentation des connecteurs externes de l'appareil METAFORSA : Au sommet du boîtier (fig. 1) se trouvent :


  • connecteur (1) — Connexion des appareils ;
  • connecteur (2) — Connexion des lampes à gradation ;


Au bas du boîtier (fig. 1) se trouve :


  • connecteur (3) — connexion d'alimentation du module ;
  • connecteur (4) — connexion réseau Ethernet ;
  • connecteurs (5-6) — quatre connecteurs à six points pour la connexion de capteurs numériques – capteurs de mouvement, de fuite, de commutateurs à lames et *capteurs de bouton/unité de commutation ;
  • connecteur (7) — Connexion bus des capteurs numériques OneWire ;
  • connecteur (8) — connexion du module d'extension.

La configuration physique et l'affectation des points de contact de chaque connecteur sont présentées dans le tableau 2.


Table2
Connecteur Contact Affectation
Out.png 1-10 Application de charge (lampes lumineuses, actionneurs thermiques, etc.)
Dimm.png D1-4, L, N Application de charge (lampes à gradation)
Indicateurs d'état de l'appareil Les indicateurs d'état du module sont décrits dans le tableau 3
24vconn.png +24V
GND
+24V — alimentation du module par une alimentation externe 24 V GND — commun
Rj45.jpg RJ45 Connecteur pour la connectivité LAN
Inputs.png In1-12, In13-24 GND Connexion des dispositifs de contrôle (boutons, interrupteurs magnétiques, capteurs de mouvement ou de fuite) : +12 V — sortie d'alimentation du capteur +12 V
In1 … In24 — entrées logiques (0-12 V)
GND — commun
OW.png OneWire Connexion des capteurs numériques (température)
VCC — sortie d'alimentation des capteurs +5 V
OW1-OW4 — bus de données OneWire
GND — commun
Can.jpg VCC
GND
L
H
Connexion de modules externes pour bus CAN
VСС — Sortie 24 V pour alimentation des appareils externes
GND — commun
L — Bus de données CAN-L
H — Bus de données CAN-H
Table3
Indicator Status Description
Power G.png Power
E.png Power not available
Activity Y.png Data communication
E.png Data communication not available
Error E.png No errors
R.png Communication error
R.pngR.png Module overheat
R.pngR.pngR.png Dimmer outputs module overload
R.pngR.pngR.pngR.png Absence of power on dimmers, if in configuration

Installation et assemblage du système

Avant de connecter le système, vous devez :


  • localiser le capteur et les actionneurs (s'ils ne sont pas préinstallés), régler les capteurs et les actionneurs ;
  • sitez le module et l'alimentation.


Remarque : Le module doit être installé à proximité de la source de tension d'alimentation.


ATTENTION ! La tension d’alimentation CA doit être fournie à l’entrée du système via l’ensemble disjoncteur. Il doit être installé à proximité de l'alimentation électrique.
  1. La puissance de l'ensemble disjoncteur doit être conforme à la capacité de charge;
  2. Rien d'autre que les conducteurs de phase ne peut être connecté au module, le fil neutre est connecté séparément.


Le schéma typique de connexion du module METAFORSA MF-14.A est présenté dans la fig. 3.

Fig. 3


Connexion des actionneurs

Raccordement des lumières/contacteur électrique/actionneur thermique de chauffage

lamp
Fig. 4
Les actionneurs tels que l'éclairage, le contacteur électrique, l'actionneur thermique de chauffage doivent être allumés sur l'une des sorties 1 à 10, le fil neutre et le fil de terre doivent être connectés directement au tableau. L'exemple de connexion est présenté dans la Fig.4.


Connexion d'un appareil à charge élevée

Contactor Contacteurs recommandés :
  • Série ABB ESB
  • Série Schneider Acti 9 iCT
  • Série Hager ESC.


Raccordement d'une vanne d'alimentation eau/gaz unipolaire

Attention : Avant de mettre sous tension la charge, assurez-vous que la configuration de sortie du module METAFORSA est correcte. Une configuration incorrecte ou une connexion incorrecte peut provoquer une panne du module et/ou une panne de l'équipement qui y est connecté, voire un incendie.
valve
Fig. 5
La vanne d'alimentation en eau/gaz unipolaire est connectée à l'une des sorties 1 – 10, le fil neutre et le fil de terre sont connectés directement au tableau. L'exemple de connexion est illustré dans Fig.5.


Raccordement de la vanne d'alimentation eau/gaz bipolaire

Attention : Avant de mettre sous tension la vanne, il est nécessaire de s'assurer que la configuration de sortie du module METAFORSA est correcte. Une configuration incorrecte peut provoquer l'application simultanée de tension sur les deux canaux de la vanne, ce qui peut entraîner une panne du module et/ou une panne de l'équipement qui y est connecté, et même un incendie.
valve
Fig. 6
Deux points de contact adjacents (par exemple 3, 4) sont utilisés pour connecter la vanne bipolaire d'alimentation eau/gaz ; dans ces conditions le fil neutre et le fil de terre sont connectés directement au tableau. L'exemple de connexion est présenté dans la Fig.6.


Raccordement actionneur de portail unipolaire

Attention : Avant de mettre le module sous tension, vous devez correctement configurer l'accès à l'application. Des contacts mal configurés peuvent entraîner une panne du module et/ou une panne de l'équipement qui y est connecté, voire un incendie.

1pgate
Fig. 7
N'importe quel point de contact (par exemple 3) est utilisé pour connecter les contrôleurs de portail unipolaires. L'exemple de connexion est présenté dans la Fig.7.


Connection of double-pole gate actuator

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

2pgate
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

Pjalousie
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

ljalousie
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors

The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11.

ms
Fig. 11


Connection of FW-WL.A leakage sensors

FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12.

Leak1.png

Fig12
Leak2.png

Fig13

Configuration and connection of the FW-WL.A sensor 1. Terminals:

+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.

2. Sensor preset switch (optionally):

1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).

3. LED status indicator.

Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in24, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-15.

Buttons.png

Fig14 connection of buttons/switching units
Reed-sv.png

Fig15 connection of the magnetic reed switches (window/door position sensors)

Connection of digital sensors

The OW adapter (Fig. 16a) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b). The connected sensors are detected automatically and do not require any original setting.

Ow1Conn.png

Fig16 a
Ow2Conn.png

Fig16 b

Configuration and connection of the OW adapter

Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 17.

Canex.png
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSBBBBSSSSSS' 12 buttons; 12 switches.

 1<item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> 
 2<item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> 
 3    <automation name="Eco" temperature-level="16" uniq_id="3781"/> 
 4    <automation name="Comfort" temperature-level="22" uniq_id="3782"/> 
 5    <automation name="Hot" temperature-level="25" uniq_id="3783"/> 
 6</item> 
 7<item addr="339:3" cfgid="40" hw="runtime=9" name="Jalousie" sub-type="120" type="jalousie" uniq_id="32"/> 
 8<item addr="339:5" cfgid="40" hw="runtime=13" name="Gate" sub-type="120" type="gate" uniq_id="3784"/> 
 9<item addr="339:7" cfgid="40" hw="hold=4600" name="Gate" sub-type="120" type="gate" uniq_id="3785"/> 
10<item addr="339:8" cfgid="40" hw="runtime=10" name="Valve" type="valve" uniq_id="3786"/> 
11<item addr="339:11" cfgid="40" name="Motion" type="motion-sensor" uniq_id="17"/> 
12<item addr="339:12" cfgid="40" name="Motion" type="motion-sensor" uniq_id="18"/> 
13<item addr="339:13" cfgid="40" name="Motion" type="motion-sensor" uniq_id="19"/> 
14<item addr="339:16" cfgid="40" name="Leak" type="leak-sensor" uniq_id="21"/> 
15<item addr="339:17" cfgid="40" name="Leak" type="leak-sensor" uniq_id="41"/> 
16<item addr="339:19" cfgid="40" name="Switch" type="switch" uniq_id="22"/> 
17<item addr="339:20" cfgid="40" name="Switch" type="switch" uniq_id="23"/> 
18<item addr="339:21" cfgid="40" name="Switch" type="switch" uniq_id="24"/> 
19<item addr="339:22" cfgid="40" name="Switch" type="switch" uniq_id="25"/> 
20<item addr="339:23" cfgid="40" name="Door" type="door-sensor" uniq_id="26"/>
21<item addr="339:24" cfgid="40" name="Door" type="door-sensor" uniq_id="27"/> 
22<item addr="339:25" cfgid="40" name="Door" type="door-sensor" uniq_id="28"/> 
23<item addr="339:26" cfgid="40" name="Door" type="door-sensor" uniq_id="29"/> 
24<item addr="339:30" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3772"/> 
25<item addr="339:31" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3773"/> 
26<item addr="339:32" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3774"/> 
27<item addr="339:33" cfgid="40" hw="offset='-10.8'" name="Temperature" type="temperature-sensor" uniq_id="3775"/> 
28<item addr="339:34" cfgid="40" hw="offset='25.1'" name="Temperature" type="temperature-sensor" uniq_id="3776"/> 
29<item addr="339:35" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3777"/> 
30<item addr="339:36" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3778"/> 
31<item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/>