Metaforsa2 MF-14

From Larnitech wiki page
Revision as of 13:39, 4 March 2024 by Support (talk | contribs) (Created page with "====Collegamento attuatore cancello bipolare====")
Jump to navigation Jump to search
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF-14
Metaforsa2.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs24
Number of digital inputs4
General
Max CAN devices50
Max CAN bus length800 m (twisted pair 5 cat)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x110x58 mm


Introduzione

Il Manuale di Installazione METAFORSA SMART HOUSE descrive la procedura per la sua installazione, montaggio, funzionamento e impostazione. Mentre si lavora con il sistema, è necessario rispettare rigorosamente tutti i requisiti stabiliti nel presente manuale. La mancata osservanza di tali norme potrebbe causare danni al dispositivo, guasti, scosse elettriche, incendi e altre conseguenze. Il produttore si riserva il diritto di apportare modifiche al presente manuale senza preavviso. Il presente manuale è parte integrante del sistema e rimarrà presso il cliente finale.

Caratteristiche

  • Supporto per 10 uscite universali:
    • Luci
    • Valvole di riscaldamento NC/NO
    • Persiane
    • Cancelli unipolari o bipolari
    • Valvole a 1 o 2 poli
    • Serrature NC/NO
    • Ventilconvettori
  • 4 uscite dimmerabili
  • 24 ingressi discreti che supportano:
    • Pulsanti
    • Interruttori
    • interruttori reed
    • sensori di perdite
    • rilevatori di movimento
  • 4 ingressi digitali per un massimo di 8 sensori di temperatura
  • Porta di estensione
  • Relè con contatti AgSnO2 classificati per corrente di spunto di 80 A 20 ms
  • Connessione al cloud e controllo di tutti i sistemi domestici
  • Controllo vocale (Siri, Alexa, Google Home)
  • Il motore dei plug-in consente di espandere le possibilità del sistema (ad esempio l'integrazione con Satel, Philips Hue, luci IKEA)
  • Sicurezza contro le intrusioni non autorizzate garantita dalla crittografia RSA/AES256
  • Notifiche push dal sistema sul tuo telefono (è possibile riceverle anche tramite i messenger Telegram e Viber)
  • Cronologia (vengono memorizzati i dati del contatore per 1 anno)
  • Plug and play (possibilità di estensione rapida e semplice del sistema)
  • Aggiornamenti regolari del sistema
  • Ampio database di script costantemente aggiornato per soddisfare tutte le tue esigenze
  • Backup giornalieri automatici via cloud con possibilità di ripristinare la configurazione iniziale
  • Open API (che permette di integrare Larnitech in altri sistemi)
  • Interfaccia Web LT SETUP interattiva e intuitiva disponibile per la configurazione avanzata
  • Collega e usa
  • È un kit del sistema Smart Home completamente pronto per l'installazione

Safety requirements

ATTENZIONE! Tutti i lavori relativi all'installazione, collegamento, impostazione, assistenza e supporto devono essere eseguiti da personale qualificato con sufficienti competenze ed esperienza nel lavoro con apparecchiature elettriche.

Per evitare il rischio di incendio, scossa elettrica, danni al sistema e/o lesioni personali, l’installazione e il montaggio del sistema devono essere eseguiti in conformità con le istruzioni di seguito elencate:


  • tutti i lavori di collegamento devono essere effettuati in assenza di alimentazione;
  • utilizzare strumenti adeguati e protezioni personali contro le scosse elettriche;
  • non utilizzare cavi, fili e connettori danneggiati;
  • evitare di piegare cavi e fili;
  • non pizzicare o piegare i cavi e i fili applicando una forza eccessiva. In caso contrario, i conduttori interni del cavo e dei fili potrebbero essere spellati o rotti;
  • non utilizzare prese di corrente con contatti scadenti per la connessione;
  • non superare il limite dei parametri di carico specificati in questo manuale;
  • la sezione dei conduttori di alimentazione è soggetta alle specifiche relative al limite di densità di corrente, al tipo di isolamento e al materiale dei cavi. La sezione leggera può provocare il surriscaldamento del cavo e un incendio.


Quando si lavora con il sistema dopo l'alimentazione di tensione MAI:

  • effettuare la connessione/sconnessione dei connettori;
  • moduli e sensori aperti.

Configurazione del sistema e scopo

Scopo del sistema

METAFORSA SMART HOUSE è una soluzione pronta per l'automazione di locali residenziali e commerciali, complessi alberghieri che include le funzionalità più desiderate di Smart House.


Il dispositivo dispone di 10 canali di controllo, 4 canali di regolazione, 24 canali di sensori in ingresso e una porta di connessione per sensori digitali.


Le uscite universali possono essere utilizzate per controllare: Gli ingressi universali consentono di collegare:
Illuminazione Pulsanti/unità di commutazione
Connettori presa Interruttori magnetici
Riscaldamento a pavimento Interruttori magnetici
Attuatori per tende/cancelli Sensori di perdite
Valvole di alimentazione acqua/riscaldamento


Porta di collegamento sensori digitali


La porta di connessione dei sensori digitali consente di collegare una varietà di sensori digitali, come sensori di temperatura, luce ambientale, umidità e altro.


Porta di espansione


La porta di espansione consente di aggiornare il sistema collegando apparecchiature ausiliarie, come il modulo di controllo per illuminazione a LED, dimmerazione, dispositivi di misurazione e altri elementi. Il pacchetto, completamente pronto per l'installazione, comprende l'hardware e il software di base.

Contenuto della confezione

Il pacchetto viene fornito di serie con:

Mainframe METAFORSA MF-14.А 1 pc
Alimentatore MEANWELL DR-15-12 1 pc
Sensore di movimento CW-MSD 3 pezzi
Sensore perdite FW-WL.A 2 pezzi
Elemento termosensibile FW-TS.A 4 pezzi
Interruttore reed magnetico (sensore di posizione finestra/porta) 4 pezzi
Filtro antirumore del cavo Ethernet 1 pc
Cavo di alimentazione 1 pc

Specifiche tecniche di base del sistema

Le specifiche e le caratteristiche di base del modulo METAFORSA MF-14.A sono riportate nella tabella 1

Table1
Specification Meaning
Porte di uscita
Numero di canali commutati 10
Numero di gruppi commutati 10
Numero di canali di regolazione 4
Tensione di commutazione 0-250 V CA/CC
Carico di punta (un canale) 16A
Carico di punta (dispositivo) 160A
Carico massimo per canale di regolazione 0,5 A (110 W a 220 V)
Tipo dimmer MOSFET
Tipo di carico dimmer R, C
Tipo di regolazione bordo d'uscita
Tipo di collegamento del cavo di alimentazione connettore
Sezione consentita del cavo di alimentazione da collegare alla presa:
cavo a un conduttore
cavo a più conduttori
cavo a più conduttori con punta

0,5 … 4mm2
0,5 … 4mm2
0,5...2,5 mm2
Porte di ingresso
Numero di ingressi discreti 24
Numero di ingressi digitali 4
Corrente nominale massima sui connettori di tensione continua 50 mA
Altro
Temperatura ambiente operativa 0...+45°С
Temperatura di stoccaggio/trasporto -20...+60°С
Umidità consentita 0...95% (senza condensa)
Alimentazione 12...27,5 V CC
24 V, 0,75 A consigliati
Richiesta massima 0,5А
Interfacce disponibili Ethernet, PUÒ, OneWire
Tipo di autobus CAN (4 fili)
CAN (4 fili) 800 m* (doppino twistato 5 cat)
Tipo di cavo CAN FTP Cat 5E
Tipo di connessione CAN connettore
Lunghezza massima linea digitale 30 metri
Tipo linea digitale UTP/FTP Cat 5E
Lunghezza massima LAN 100 metri
Tipo di cavo LAN UTP/FTP Cat 5E
Tipo di connessione LAN Connettore RJ-45
Specifiche dimensionali 9U, 156x110x58 mm
Materiale calotta Plastica ABS
Carcassa IP40
Tipo di installazione dell'apparecchiatura Guida DIN (EN 60715)
Peso 400 g

* – per le linee lunghe è necessaria l'installazione di alimentatori aggiuntivi; la lunghezza massima della linea può essere ridotta da diversi fattori di interferenza

Struttura generale del Sistema

La vista generale del modulo è mostrata in fig. 1


Fig. 1 Module general view


1 — connettore per l'applicazione del carico
2 — connettore per applicazione dimmerazione lampade
3 — connettore di alimentazione
4 — Connettore di rete Ethernet
5-6 — connettori per sensori digitali e pulsanti/unità di commutazione
7 — Connettore interfaccia OneWire (per sensori digitali)
8 — connettore per modulo di espansione.


Panoramica dei connettori esterni del dispositivo METAFORSA: Nella parte superiore dell'involucro (fig. 1) sono presenti:


  • connettore (1) — Connessione dispositivi;
  • connettore (2) — Collegamento lampade dimmerabili;


Nella parte inferiore dell'involucro (fig. 1) sono presenti:


  • connettore (3) — connessione alimentazione modulo;
  • connettore (4) — connessione di rete Ethernet;
  • connettori (5-6) — quattro connettori a sei punti per il collegamento di sensori digitali: sensori di movimento, perdite, interruttori reed e *sensori pulsante/unità di commutazione;
  • connettore (7) — Connessione bus sensori digitali OneWire;
  • connettore (8) — collegamento del modulo di espansione.

La configurazione fisica e l'assegnazione dei punti di contatto di ciascun connettore sono mostrate nella tabella 2.


Table2
Connettore Contatto Assegnazione
Out.png 1-10 Applicazione del carico (lampade, attuatori termici, ecc.)
Dimm.png D1-4, L, N Applicazione di carico (lampade dimmerabili)
Device status indicators Gli indicatori di stato del modulo sono descritti nella tabella 3
24vconn.png +24V
GND
+24V — alimentazione del modulo tramite un alimentatore esterno da 24 V GND — comune
Rj45.jpg RJ45 Connettore per connettività LAN
Inputs.png In1-12, In13-24 GND Collegamento dei dispositivi di controllo (pulsanti, interruttori magnetici, sensori di movimento o di perdita): +12V — uscita alimentazione sensore +12 V
In1 … In24 — ingressi logici (0-12 V)
GND — comune
OW.png OneWire Collegamento sensori digitali (temperatura)
VCC — uscita alimentazione sensori +5 V
OW1-OW4 — bus dati OneWire
GND — comune
Can.jpg VCC
GND
L
H
Collegamento moduli esterni per bus CAN
VСС — uscita 24V per alimentazione dispositivi esterni
GND — comune
L — bus dati CAN-L
H — bus dati CAN-H
Table3
Indicator Status Description
Power G.png Power
E.png Power not available
Activity Y.png Data communication
E.png Data communication not available
Error E.png No errors
R.png Communication error
R.pngR.png Module overheat
R.pngR.pngR.png Dimmer outputs module overload
R.pngR.pngR.pngR.png Absence of power on dimmers, if in configuration

Installazione e assemblaggio del sistema

Prima di collegare il sistema è necessario:


  • posizionare il sensore e gli attuatori (se non preinstallati), impostare i sensori e gli attuatori;
  • posizionare il modulo e l'alimentatore.


Nota: il modulo deve essere installato vicino alla fonte di tensione di alimentazione.


ATTENZIONE! La tensione di alimentazione CA deve essere fornita all'ingresso del sistema attraverso il gruppo dell'interruttore. Dovrebbe essere installato vicino all'alimentatore.
  1. La potenza del gruppo interruttore deve essere conforme alla capacità di carico;
  2. Al modulo non è possibile collegare altro che i conduttori di fase, il filo neutro è collegato separatamente.


Schema tipico di collegamento del modulo METAFORSA MF-14.A è mostrato in fig. 3.

Fig. 3


Collegamento degli attuatori

Collegamento luci/contattore elettrico/termico attuatore riscaldamento

lamp
Fig. 4
Tali attuatori come luce, contattore elettrico, attuatore termico di riscaldamento devono essere accesi su una qualsiasi delle uscite 1 – 10, il filo neutro e il filo di terra devono essere collegati direttamente al quadro elettrico. L'esempio di collegamento è mostrato in Fig.4.


Collegamento di un dispositivo a carico elevato

Contactor Contattori consigliati:
  • Serie ABB ESB
  • Serie Schneider Acti 9 iCT
  • Serie ESC Hager.


Collegamento valvola unipolare alimentazione acqua/gas

Attenzione: prima di dare alimentazione al carico, assicurarsi che la configurazione di uscita del modulo METAFORSA sia corretta. L'errata configurazione o l'errato collegamento possono causare il guasto del modulo e/o il guasto delle apparecchiature ad esso collegate, fino ad un incendio.
valve
Fig. 5
La valvola unipolare di alimentazione acqua/gas è collegata a una qualsiasi delle uscite 1 – 10, il filo neutro e il filo di terra sono collegati direttamente al quadro elettrico. L'esempio di collegamento è mostrato in Fig.5.


Collegamento valvola bipolare alimentazione acqua/gas

Caution: Before applying power to the valve, it is necessary to ensure the output configuration of METAFORSA module is correct. The incorrect configuration can cause the voltage application simultaneously to both channels of the valve, which may result in the module failure and/or failure of the equipment connected to it, and even a fire.
valve
Fig. 6
Two adjacent contact points (for example, 3, 4) are used to connect the double-pole water/gas supply valve; in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.6.


Collegamento attuatore cancello unipolare

Attenzione: prima di alimentare il modulo, è necessario configurare correttamente l'accesso all'applicazione. I contatti configurati in modo errato possono provocare il guasto del modulo e/o il guasto delle apparecchiature ad esso collegate, fino ad un incendio.

1pgate
Fig. 7
Qualsiasi punto di contatto (ad esempio 3) viene utilizzato per collegare i controller di azionamento del cancello unipolari. L'esempio di collegamento è mostrato in Fig.7.


Collegamento attuatore cancello bipolare

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

2pgate
Fig. 8
Two adjacent contact points (for example, 3, 4) should be used to connect the double-pole gate drive controller. The example of connection is shown in Fig.8.


Connection of curtain/jalousie/shutter actuator with 220V force control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

Pjalousie
Fig. 9
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator, in these conditions the neutral wire and the ground wire are connected directly to the switchboard. The example of connection is shown in Fig.9.


Connection of curtain/jalousie/shutter actuator with low-voltage control

Caution: Before applying power to the module, you must properly configure the outputs in the application. The contacts configured incorrectly can lead to simultaneous power supply to both channels, resulting in the module failure and/or failure of the equipment connected to it, and even a fire.

ljalousie
Fig. 10
Two adjacent contact points (for example, 3, 4) should be used to connect the curtain/jalousie/rolladens actuator with low-voltage control. The example of connection is shown in Fig.10.

Connection of sensing elements/switches/buttons

Connection of motion sensors

The motion sensors should be connected to any free input in1-in24; in these conditions their power is connected to the contact points of +12V and GND of the relevant group. The example of connection is shown in Fig.11.

ms
Fig. 11


Connection of FW-WL.A leakage sensors

FW-WL.A leakage sensors are connected to any free input in1 – in24, in these conditions the power should be connected to +12V and GND points of the relevant group. The example of connection is shown in fig. 12.

Leak1.png

Fig12
Leak2.png

Fig13

Configuration and connection of the FW-WL.A sensor 1. Terminals:

+12V — sensor power is connected to the contact point of METAFORSA “+12V”;
OW — sensor pickup signal;
GND — common, connected to GND contact of METAFORSA.

2. Sensor preset switch (optionally):

1 — sensor sensitivity (ON – high, OFF – low);
2 — indicator colour setting (ON – blue, OFF – green).

3. LED status indicator.

Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in24, while their second contact point is connected to GND point of the relevant METAFORSA module group, + 12V power outputs – not in use. The example of connection is shown in Fig. 14-15.

Buttons.png

Fig14 connection of buttons/switching units
Reed-sv.png

Fig15 connection of the magnetic reed switches (window/door position sensors)

Connection of digital sensors

The OW adapter (Fig. 16a) is supplied along with METAFORSA module with the possibility to connect up to 8 digital sensors to it. In these conditions, several devices can be connected to one channel (Fig. 16b). The connected sensors are detected automatically and do not require any original setting.

Ow1Conn.png

Fig16 a
Ow2Conn.png

Fig16 b

Configuration and connection of the OW adapter

Caution: Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 17.

Canex.png
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

in char[24] 98 'BBBBBBBBBBBBMMMLLLKKKKKK' Each char is responsible for the type of a particular channel
  • 'B'-Button;
  • 'C'-nButton;
  • 'S'-Switch;
  • 'K'-Contact;
  • 'H'-nContact;
  • ‘L’-Leak, Built-in floor (EW-WL) or on-the-floor (FW-WL) leakage sensor
  • ‘N’-Third party leakage sensor;
  • 'M'-Motion, ​motion sensor;
  • 'V'-nMotion, motion sensor;
  • '-'-none

Example: in='MMMMMMMMMMMMLLLLLLLLLLLL' 12 motion sensors and 12 leak-sensors; in='BBBBBBBBSSSSSSBBBBSSSSSS' 12 buttons; 12 switches.

 1<item addr="339:1" auto-period="600" cfgid="40" hw="def='ON'" name="Lamp" type="lamp" uniq_id="3779"> 
 2<item addr="339:2" cfgid="40" hw="def='ON'" name="Radiator" type="valve-heating" uniq_id="3780"> 
 3    <automation name="Eco" temperature-level="16" uniq_id="3781"/> 
 4    <automation name="Comfort" temperature-level="22" uniq_id="3782"/> 
 5    <automation name="Hot" temperature-level="25" uniq_id="3783"/> 
 6</item> 
 7<item addr="339:3" cfgid="40" hw="runtime=9" name="Jalousie" sub-type="120" type="jalousie" uniq_id="32"/> 
 8<item addr="339:5" cfgid="40" hw="runtime=13" name="Gate" sub-type="120" type="gate" uniq_id="3784"/> 
 9<item addr="339:7" cfgid="40" hw="hold=4600" name="Gate" sub-type="120" type="gate" uniq_id="3785"/> 
10<item addr="339:8" cfgid="40" hw="runtime=10" name="Valve" type="valve" uniq_id="3786"/> 
11<item addr="339:11" cfgid="40" name="Motion" type="motion-sensor" uniq_id="17"/> 
12<item addr="339:12" cfgid="40" name="Motion" type="motion-sensor" uniq_id="18"/> 
13<item addr="339:13" cfgid="40" name="Motion" type="motion-sensor" uniq_id="19"/> 
14<item addr="339:16" cfgid="40" name="Leak" type="leak-sensor" uniq_id="21"/> 
15<item addr="339:17" cfgid="40" name="Leak" type="leak-sensor" uniq_id="41"/> 
16<item addr="339:19" cfgid="40" name="Switch" type="switch" uniq_id="22"/> 
17<item addr="339:20" cfgid="40" name="Switch" type="switch" uniq_id="23"/> 
18<item addr="339:21" cfgid="40" name="Switch" type="switch" uniq_id="24"/> 
19<item addr="339:22" cfgid="40" name="Switch" type="switch" uniq_id="25"/> 
20<item addr="339:23" cfgid="40" name="Door" type="door-sensor" uniq_id="26"/>
21<item addr="339:24" cfgid="40" name="Door" type="door-sensor" uniq_id="27"/> 
22<item addr="339:25" cfgid="40" name="Door" type="door-sensor" uniq_id="28"/> 
23<item addr="339:26" cfgid="40" name="Door" type="door-sensor" uniq_id="29"/> 
24<item addr="339:30" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3772"/> 
25<item addr="339:31" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3773"/> 
26<item addr="339:32" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3774"/> 
27<item addr="339:33" cfgid="40" hw="offset='-10.8'" name="Temperature" type="temperature-sensor" uniq_id="3775"/> 
28<item addr="339:34" cfgid="40" hw="offset='25.1'" name="Temperature" type="temperature-sensor" uniq_id="3776"/> 
29<item addr="339:35" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3777"/> 
30<item addr="339:36" cfgid="40" name="Temperature" type="temperature-sensor" uniq_id="3778"/> 
31<item addr="339:98" cfgid="40" hw="out='LHB-G-XV--' in='MMM--LL-BBBBKKKK'" name="Temperature" system="yes" type="temperature-sensor" uniq_id="30"/>