Metaforsa 3/3.plus

Revision as of 10:23, 3 April 2024 by Support (talk | contribs) (Created page with "Датчики руху слід підключати до будь-якого вільного входу in1-in28, при цьому їхнє живлення подаєть...")
Other languages:
Deutsch • ‎English • ‎Nederlands • ‎bosanski • ‎dansk • ‎español • ‎français • ‎italiano • ‎lietuvių • ‎magyar • ‎polski • ‎português • ‎română • ‎slovenčina • ‎slovenščina • ‎čeština • ‎русский • ‎српски / srpski • ‎українська • ‎Ἀρχαία ἑλληνικὴ
MF3/MF3.plus
METAFORSA 3 MF3-14.png
Output ports
Number of switched channels10
Number of dimming channels4
Peak load16 A
Max load per dimming channel0.5 A (110 W at 220 V)
Dimmer typeMOSFET
Input ports
Number of discrete inputs28
General
Max CAN devices4 (can be extended with the license) 99 (for Metaforsa 3.plus)
Max CAN bus length800 m (twisted pair CAT5e)
Max current per CAN bus500 mA
Other
Supply voltage11.5...27.5 V DC
Dimentions9U, 156x90x58 mm


Вступ

Інструкція з монтажу METAFORSA SMART HOUSE описує процедуру встановлення, збирання, експлуатації та налаштування системи. Під час роботи з системою обов'язково дотримуйтеся всіх вимог, викладених у цьому посібнику. Невиконання цих вимог може призвести до пошкодження пристрою, його відмови, ураження електричним струмом, пожежі та інших непередбачених ситуацій. Виробник залишає за собою право вносити зміни до цієї інструкції без попереднього повідомлення. Цей посібник є невід'ємною частиною системи і повинен знаходитися у кінцевого користувача.

Особливості

  • Підтримка 10 універсальних виходів:
    • Світло
    • Клапани опалення NC/NO
    • жалюзі
    • 1 або 2-полюсні ворота
    • 1 або 2-полюсні клапани
    • Замки НЗ/НЕТ
    • Блоки вентиляторних котушок
  • 4 виходи дімування
  • 28 підтримуваних входів:
    • Кнопки
    • Світлодіодні кнопки
    • перемикачі
    • швидкісні перемикачі
    • Датчики витоку
    • Датчики руху
    • Датчики температури
    • Світлодіодні стрічки
    • 3-4-5 канальна RGB стрічка
    • Стрічки WS2812B
    • Пристрій RS485 (тільки для Metaforsa 3.plus)
  • Порт розширення
  • Реле з контактами AgSnO2, розрахованими на пусковий струм 80 А 20 мс
  • Підключення до хмари та керування всіма системами будинку
  • Голосове керування (Siri, Alexa, Google Home)

Вимоги техніки безпеки

УВАГА! Усі роботи, пов’язані з установкою, підключенням, налаштуванням, сервісним обслуговуванням і технічною підтримкою, повинні виконуватися кваліфікованим персоналом з достатніми навичками та досвідом роботи з електрообладнанням.''

Щоб уникнути ризику пожежі, ураження електричним струмом, пошкодження системи та/або отримання травми, установку й збірку системи слід виконувати відповідно до наведених нижче інструкцій:


  • всі роботи по підключенню повинні виконуватися без електроживлення;
  • використовуйте відповідні інструменти та засоби індивідуального захисту від ураження електричним струмом;
  • не використовуйте пошкоджені кабелі, дроти та роз'єми;
  • не допускайте згинання кабелів та проводів;
  • не перетискайте та не перегинайте кабелі та дроти, застосовуючи надмірну силу. В іншому випадку внутрішні провідники кабелю та проводів можуть бути оголені або зламані;
  • не використовуйте для підключення розетку з поганими контактами;
  • не перевищуйте граничні параметри навантаження, зазначені в цьому посібнику;
  • переріз жил кабелю живлення повинен відповідати технічним вимогам щодо граничної густини струму, типу ізоляції та матеріалу жил. Малий переріз може призвести до перегріву кабелю та пожежі.


При роботі з системою після подачі напруги НІКОЛИ:

  • підключати/відключати роз'єми;
  • розкривати модулі та датчики.

Конфігурація та призначення системи

Призначення системи

METAFORSA SMART HOUSE - це готове рішення для автоматизації житлових і комерційних приміщень, готельних комплексів, яке включає в себе найбільш необхідні функції "розумного будинку".


Пристрій має 10 каналів керування, 4 канали регулювання яскравості та 28 вхідних каналів.


Універсальні виходи можна використовувати для керування: Універсальні входи дозволяють підключати:
Освітлення Кнопки / світлодіодні кнопки / перемикачі
| Магнітні герконові вимикачі
Датчики протікання
Датчики руху
| Датчики температури
|Світлодіодні стрічки/3-4-5-канальні RGB стрічки/WS2812B стрічки
| Пристрій RS485*

* - Тільки для Metaforsa 3.plus


Порт розширення


The expansion port allows you to upgrade the system by connecting auxiliary equipment, such as the control module for LED lighting, dimming, metering devices and other elements. The package, which is completely ready-to-install, includes the basic hardware and software.

Вміст пакування

У комплект поставки входить

Мейнфрейм METAFORSA 3/3.plus 1 шт
Блок живлення MEANWELL DR-15-12 1 шт
Датчик руху CW-MSD 3 шт.
Датчик протікання FW-WL.B 2 шт
Термочутливий елемент FW-TS 4 шт.
Магнітний геркон (датчик положення вікна/дверей) 4 шт.
Завадозахисний фільтр для Ethernet-кабелю 1 шт
Шнур живлення 1 шт

Основні технічні характеристики системи

Основні технічні характеристики та характеристики модуля METAFORSA 3/3.plus наведені в таблиці 1

Таблиця 1'
Специфікація Значення
'Вихідні порти'
Кількість комутованих каналів 10
Кількість переключених груп 10
Кількість каналів затемнення 4
Напруга комутації 0-250 В змінного/постійного струму
Пікове навантаження (один канал) 16А
Пікове навантаження (прилад) 160А
Максимальне навантаження на канал диммування 0,5 A (110 Вт при 220 В)
Тип диммера MOSFET
Тип навантаження диммера R,C
Тип затемнення задній край
Тип підключення кабелю живлення роз'єм
Допустимий перетин кабелю живлення для підключення до розетки:
одножильний кабель
багатожильний кабель
багатожильний кабель з наконечником

0,5 … 4 мм2
0,5 … 4 мм2
0,5 … 2,5 мм2
'Вхідні порти'
Кількість дискретних входів 28
Максимальний струм на роз'ємах постійної напруги 5 мА*
'Інше'
Робоча температура навколишнього середовища 0 … +45°С
Температура зберігання/транспортування -10 … +50°С
Допустима вологість 0 … 95% (без конденсації)
Електропостачання 11,5 … 27,5 В постійного струму
24 В, 0,75 А Рекомендовано
Максимальний попит 0,5А
Доступні інтерфейси Ethernet, CAN
Тип автобуса CAN (4-провідний)
CAN (4-провідний) 800 м** (кручена пара CAT5e)
Тип проводу CAN FTP Cat 5E
Тип підключення CAN Роз'єм
Максимальна довжина цифрової лінії 30 м
Цифрова лінія Wirde типу UTP/FTP Cat 5E
максимальна довжина локальної мережі 100 м
Тип проводу LAN UTP/FTP Cat 5E
Тип підключення LAN Роз'єм RJ-45
Кількість портів RS485 1***
Швидкість передачі даних 1200-115200 б/с***
Габаритні характеристики 9U, 156x90x58 мм
Матеріал оболонки ABS
Обшивка IP40
Тип установки обладнання DIN-рейка (EN 60715)
Вага 400 г

* – Вихідні канали слід підключати лише за допомогою підсилювача, який використовує сигнал 5 В ШІМ від виходу IO як вхід

** – для довгих ліній потрібна установка додаткових блоків живлення; максимальна довжина лінії може бути зменшена різними факторами перешкод

*** – Лише для Metaforsa 3.plus

Загальна структура Системи

Загальний вигляд модуля показано на 'мал. 1


 


1 — роз'єм для додатка навантаження
2 — роз'єм для підключення диммерів
3 — роз’єм живлення
4 — Мережевий роз'єм Ethernet
5-6 — роз'єми для універсальних каналів введення/виведення
7 — роз'єм для модуля розширення.


Огляд зовнішніх роз'ємів пристрою METAFORSA: У верхній частині корпусу (мал. 1) є:


  • роз'єм (1) — для підключення пристроїв;
  • роз'єм (2) — для підключення диммованих ламп;


У нижній частині корпусу (рис. 1) є:


  • роз'єм (3) — підключення блоку живлення;
  • роз'єм (4) — підключення до мережі Ethernet;
  • роз’єми (5-6) — підключення універсальних каналів вводу/виводу – кнопки, геркони, світлодіодні кнопки, датчики протікання, датчики руху, датчики температури, світлодіодні стрічки, 3-4-5 канальні стрічки RGB, стрічки WS2812B, пристрій RS485 (Тільки для Metaforsa 3.plus);
  • роз'єм (7) — підключення модуля розширення.

Фізична конфігурація та призначення контактних точок кожного роз’єму показані в таблиці 2.

Таблиця 2'
З'єднувач Контакт Призначення
  1-10 Застосування навантаження (світлові лампи, термоприводи тощо)
80px|frameless D1-4, L, N Застосування навантаження (регулювання ламп)
Індикатори стану пристрою Індикатори стану модуля описані в таблиці 3
  +24V
GND
+24V — живлення модуля від зовнішнього джерела живлення 24V GND — загальний
80px|frameless RJ45 Роз'єм для підключення до локальної мережі
80px|frameless In1-14, In15-28 GND Підключення контрольних пристроїв (кнопки, світлодіодні кнопки, магнітні геркони, датчики руху, датчики протікання, датчики температури та ін.):
In1 … In28 — логічні входи
GND — загальний
80px|frameless VCC
GND
L
H
Підключення зовнішніх модулів для CAN-шини
VСС — вихід 24В для живлення зовнішніх пристроїв
GND — загальний
L — шина даних CAN-L
H — шина даних CAN-H
Table3
Indicator Status Description
Power   Power
  Power not available
Activity   Data communication
  Data communication not available
Error   No errors
  Communication error
   Module overheat
    Dimmer outputs module overload
     Absence of power on dimmers, if in configuration

Установка та збірка системи

Перед підключенням системи необхідно:


  • Встановіть датчики та виконавчі механізми (якщо вони не встановлені), налаштуйте датчики та виконавчі механізми;
  • встановіть модуль і блок живлення.


Примітка: Модуль повинен бути встановлений поблизу джерела живлення.


УВАГА! Напруга змінного струму повинна подаватись на вхід системи через вузол автоматичного вимикача. Його слід встановити поблизу джерела живлення.
  1. 'Потужність вузла автоматичного вимикача повинна відповідати навантажувальній здатності;
  2. 'До модуля не можна підключати нічого, крім фазних проводів, нульовий провід підключається окремо.'


Типова схема підключення модуля METAFORSA 3/3.plus наведена на мал. 3

 


Підключення приводів

Підключення освітлення/електроконтактора/термоприводу опалення

 
Fig. 4
Такі виконавчі пристрої, як світло, електричний контактор, нагрівальний термопривід, слід вмикати на будь-який з виходів 1 - 10, нульовий провід і провід заземлення слід підключати безпосередньо до розподільного щита. Приклад підключення показано на рис.4.


Підключення пристроїв з високим навантаженням

  Рекомендовані контактори:
  • ABB серії ESB
  • Серія Schneider Acti 9 iCT
  • Серія Hager ESC.


Підключення однополюсного клапана подачі води/газу

Застереження: перед подачею живлення до навантаження переконайтеся, що вихідна конфігурація модуля METAFORSA правильна. Неправильна конфігурація або неправильне підключення може спричинити вихід модуля з ладу та/або збій підключеного до нього обладнання та навіть пожежу.'
 
Мал. 5
Однополюсний клапан подачі води/газу під’єднується до будь-якого з виходів 1–10 (нульовий дріт і дріт заземлення підключаються безпосередньо до розподільного щита. Приклад підключення показано на Мал.5.


Підключення двополюсного клапана подачі води/газу

Застереження: перед подачею живлення на клапан, необхідно переконатися, що вихідна конфігурація модуля METAFORSA правильна. Неправильна конфігурація може спричинити подачу напруги одночасно на обидва канали клапана, що може призвести до виходу з ладу модуля та/або поломки підключеного до нього обладнання та навіть пожежі.'
 
'Мал. 6
Дві суміжні контактні точки (наприклад, 3, 4) використовуються для підключення двополюсного клапана подачі води/газу; в цих умовах нульовий провід і провід заземлення підключаються безпосередньо до розподільного щита. Приклад підключення показано на Мал.6.


Підключення однополюсного приводу воріт

Увага! Перед подачею живлення на модуль слід правильно налаштувати доступ до застосунку. Неправильне налаштування контактів може призвести до виходу модуля з ладу та/або несправності підключеного до нього обладнання і навіть до пожежі.

 
Fig. 7
Будь-яка контактна точка (наприклад, 3) використовується для підключення однополюсних контролерів приводу воріт. Приклад підключення показано на Рис.7.


Підключення двополюсного приводу воріт

Увага! Перед подачею живлення на модуль необхідно правильно налаштувати виходи в застосунку. Неправильно налаштовані контакти можуть призвести до одночасної подачі живлення на обидва канали, що призведе до виходу модуля з ладу та/або несправності підключеного до нього обладнання і навіть до пожежі.

 
Fig. 8
Для підключення двополюсного контролера приводу воріт слід використовувати дві сусідні контактні точки (наприклад, 3, 4). Приклад підключення показано на мал.8.


Підключення приводу штор/жалюзі/жалюзі з керуванням навантаженням 220В

Увага! Перед подачею живлення на модуль необхідно правильно налаштувати виходи в застосунку. Неправильно налаштовані контакти можуть призвести до одночасної подачі живлення на обидва канали, що призведе до виходу модуля з ладу та/або несправності підключеного до нього обладнання і навіть до пожежі.

 
Fig. 9
Для підключення приводу штор/жалюзі/ролетів слід використовувати дві сусідні контактні точки (наприклад, 3, 4), при цьому нульовий провід і провід заземлення підключаються безпосередньо до розподільного щита. Приклад підключення показаний на Мал.9.


Підключення приводу штор/жалюзі/жалюзі з низьковольтним керуванням

Увага! Перед подачею живлення на модуль необхідно правильно налаштувати виходи в застосунку. Неправильно налаштовані контакти можуть призвести до одночасної подачі живлення на обидва канали, що призведе до виходу модуля з ладу та/або несправності підключеного до нього обладнання і навіть до пожежі.

 
Fig. 10
Для підключення приводу штори/жалюзі/ролети з низьковольтним керуванням слід використовувати дві сусідні контактні точки (наприклад, 3, 4). Приклад підключення показано на Мал.10.

Підключення датчиків/перемикачів/кнопок

Підключення датчиків руху/датчиків протікання

Датчики руху слід підключати до будь-якого вільного входу in1-in28, при цьому їхнє живлення подається на клеми +5В і GND відповідної групи. Приклад підключення показано на Мал.11.

 
Fig. 11 connection of motion sensors/leakage sensors


Connection of buttons/switches/magnetic reed switches

Buttons and reed switches are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 12-13.

 

Fig. 12 connection of buttons/switching units
 

Fig. 13 connection of the magnetic reed switches (window/door position sensors)

Connection of temperature sensors

Temperature sensors are connected to any free input in1-in28, while their second contact point is connected to GND point of the relevant METAFORSA module group. The example of connection is shown in Fig. 14.

 

Fig. 14 connection of temperature sensors

RGB connection scheme

CAUTION! Output channels should only be connected using amplifier which uses 5V PWM signal from IO output as input

 

Fig. 15 RGB connection

WS2812B connection scheme

 

Fig. 16 WS2812B connection

RS485 connection scheme

CAUTION! RS485 connection is only available for Metaforsa 3.plus and only occurs on 21 channel

 

Fig. 17 RS485 connection

Connection of auxiliary equipment.

Expansion modules include Larnitech equipment connected through the CAN-bus. Such equipment includes: dimmers, RGB-backlit control modules, multimode sensors, etc. The equipment connected to the expansion port is defined automatically and does not require any preset tuning. Connector contact pin assignment is defined in Table 4. The example of connection is shown in Fig. 18.

 
Caution! The 120 ohm terminating resistors should be installed at the end connectors between L and H contact points of CAN-bus. Ensure the connection is correct. The incorrect connection may cause sensor and/or module malfunction.

Module installation and connection procedure

ATTENTION! You must precisely follow the recommendations listed in the Security Requirements section hereof.
  1. Install the module in the switchboard on the DIN-rail and fix it with the special latch on the module base.
  2. Fasten the supply unit on the left side of the module.
  3. Connect the connector (4) having the noise filter pre-installed which is supplied complete with the module.
  4. Connect the connectors (5), (6).
  5. Connect the connectors (1), (2).
  6. Connect the connector (3).
  7. Apply power to the supply unit of METAFORSA module.
  8. Wait until the module is loaded, then configure it in accordance with the System Setup Instructions.
  9. Apply power to the connectors (1), (2).
  10. Check all equipment for proper operation.

METAFORSA module shut-off and deinstallation procedure

  1. De-energize the module by disconnecting the circuit breaker assembly of the load power supply and METAFORSA module supply unit. Verify the voltage is absent on the terminals (1), (2) of the connector wires and on the input terminals of the supply unit.
  2. Disconnect the load power supply connectors (1), (2).
  3. Disconnect the connector (3).
  4. Disconnect the connectors (4)-(6).
  5. Remove the module from the DIN-rail, releasing the latch at the bottom of the module base.

Hardware setup

To configure and control METAFORSA SMART HOUSE, you must install Larnitech software on your smartphone or tablet, which is available in App Store and Play Market. After installation, follow the System Setup Instructions.

Fault diagnostics and handling

The following are some possible faults and ways of fault handling. If you have any difficulty, or face the fault undeclared here, please contact the Technical Support: [1] or [support@larnitech.com]. There are also some tips in the FAQ section at our website [2].

The actuators do not operate:

  • ensure the outputs are properly configured in the application (see System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.6;
  • ensure the power is supplied to the input power contact , i.e. all circuit breaker assembly are ON.
  • verify the operability of the connected equipment.

The module is off, indication absent:

  • check the connection to 24V supply unit as shown in table 2 (contacts pin assignment);
  • check the connection of the supply unit to 220V power mains, the indicator should be ON.

Network connection fault:

  • ensure the Ethernet cable is properly wired and connected to the connector;
  • ensure the LED status indicators are ON on the Ethernet connector;
  • check the LAN configuration is correct, Ethernet cable loops are absent;
  • METAFORSA module and the device you are connecting from are in the same network.

hold integer 0-10000 1-10 by default hold is the same as runtime hold is the bridging time in miliseconds, is used for gate and jalousie, lock; Example: hold=3500


The sensors do not operate:

  • ensure the inputs are properly configured in the application (System Setup Instructions);
  • check the connection is correct in accordance with table 2 and paragraph 3.7;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the power supply availability on the sensors;
  • check the integrity of lines laid to the sensors.

The auxiliary equipment does not operate:

  • check the connection is correct in accordance with table 2 and paragraph 3.8-9;
  • ensure the METAFORSA module is ON: circuit breaker assembly is closed, indication on the supply unit is ON, the module indication corresponds to the operating status – table 3;
  • check the integrity of the CAN lines, voltage supply on the modules.

HW Settings

Name Type, range SUBID Default Description
runtime integer 0-100 1-10 15 runtime is the open/close time in seconds, is used for jalousie, gate, valve(2 pole);


Example: runtime=15

runtimeopen integer 0-60000 Blinds subId Runtimeopen is the open time in milliseconds, is used for blinds; Example: runtimeopen=15000
runtimeclose integer 0-60000 Blinds subId Runtimeclose is the close time in milliseconds, is used for blinds; Example: runtimeclose=15000
hold integer 0-10000 1-10 500 hold is the bridging time in milliseconds, is used for gate and jalousie (by default hold is the same as runtime for jalousie and gate), lock; Example: hold=3500
def string 'ON' 1-10 'OFF' def is the element status is set after restart, is used for lamp, heating, valve(1 pole); Example: def='ON'
stop Char ‘R’ 1-7 (for 2-pole gate and blinds) If it is declared then by Stop command during the motion, the same impulse appears as it was at the beginning of the motion. Pole, an which the stop-impules is formed, is defined by the parameter Stop value. If it is ‘r’ or ‘R’ then stop-impulse is produced on the opposite to the start-impulse pole. If any other value is delcared (e.g., ‘d’ ) then the stop-impulse is on the same pole. If a Runtime passed after the beginning of the motion then the stop-impulse is not formed. Example: stop=’r’
out char[10] 98 'LLLLHHHHP-' Each char is responsible for the type of a particular channel
  • 'L'-Lamp;
  • 'M'-Lamp Inverse;
  • 'J'-Heating NO, valve-heating, normally open;
  • 'H'-Heating NC, valve-heating, normally closed;
  • 'B'-Blinds (2 pole), jalousie/curtains;
  • 'C'-Blinds Inverse (2 pole), jalousie/curtains, invert open-close;
  • 'G'-Gate (2 pole), 2 pole gate;
  • 'D'-Gate (2 pole) Inverse, 2 pole gate, invert open-close;
  • 'X'-Gate (1 pole /short press), 1 pole gate;
  • 'Z'-Gate (1 pole) Inverse, 1 pole gate, invert open-close;
  • 'V'-Valve (2 pole), 2 pole valve;
  • 'W'-Valve (2 pole) Inverse, 2 pole valve, invert open-close;
  • 'R'-Valve (1 pole), 1 pole valve,;
  • 'S'-Valve (1 pole) Inverse, 1 pole valve, invert open-close;
  • 'K'-Lock (short press);
  • 'N'-Lock (short press) Inverse;
  • 'P'-Blinds (2 pole);
  • 'O'-Blinds Inverse (2 pole), invert open-close;
  • 'F'-FanCoil. Group1 (Lamp Toggle). For fancoil speed control;
  • 'E'-FanCoil. Group2 (Lamp Toggle). For fancoil speed control;
  • 'Q'-FanCoil. Group3 (Lamp Toggle). For fancoil speed control;
  • 'U'-FanCoil. Group4 (Lamp Toggle). For fancoil speed control;
  • 'I'-FanCoil. Group5 (Lamp Toggle). For fancoil speed control;
  • '-'-none, nothing is connected.

Example: out='LLB-G-V-W-'

dm char[4] 98 ‘LLLL’ Each char is responsible for the type of a particular channel
  • ‘g’ – use like halogen dimer-lamp
  • ‘s’ – Soft Switch, lamp, when on/off power is supplied/deenergised smoothly (500msec)
  • ‘k’ – Switch, lamp, when on/off power is supplied/deenergised immediately
  • ‘l’ – LED Function, dimmable LED lamps
  • ‘v’ – linear Function of dimming
  • ‘-‘ – Channel disabled
  • ‘+’ – Regular channel

Example: dm=’skl-‘

def integer 0-250 11-14 100 The default brightness level in case of a power reset (1..250). Example: def=250
min integer 0-100 11-14 0 Minimum dimming level, example: min=10
max integer 0-100 11-14 100 Maximum dimming level, example max=95
start integer 0-100 11-14 0 The Start function is used for lamps that lack the minimal voltage to get turned on. If the set value is lower than the start value, the lamp is turned on at the start value and them the light is dimmed down to the set level. Example: start=60
force integer 0-100 11-14 10 Time duration of the starting value (measured in milliseconds). Example: force=20
runtime integer 0-60000 11-14 1000 Runtime is the speed of changing the brightness from ‘min’ to ‘max’ (measured in milliseconds). Example: runtime=1000
offset integer (+/- 0…39) 39-46 '0' sensor values offset; For example, offset is -3.8 :

Example: hw="offset='-3.8'"

io char[28] 98 io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK' Each char is responsible for the type of a particular channel
  • '0' - led-dimmer
  • '1' - halogen-dimmer
  • '2' - linear-dimmer
  • '3'..'6' - RGB-3..6 channels
  • 'z' - WS2812B -string
  • 'e' - led-button inverse
  • 'd' - led-button
  • 'c' - button inverse
  • 'b' - button
  • 's' - switch
  • 'k' - contact inverse
  • 'h' - contact
  • 'l' - leak
  • 'n' - Neptun
  • 'v' - motion inverse
  • 'm' - motion
  • 'r' - thermo-resistor
  • 't' - DALLAS
  • '-' - none

Example: io='KKKKKKKKKKKKKKKKKKKKKKKKKKKK'

Only for Metaforsa 3.plus
cfg string 98 9600/8N1 cfg='SPEED/BPS', where
  • SPEED – baud rate [1200..115200];
  • B – data length [7,8];
  • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)];
  • S – stop bit length [1, 1.5 or 2].

Example:

1hw="cfg='9600/8N1'"
[Protocol] string 98 Protocol setting is described by protocol parameter. The following

protocols are supported:

  • 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
  • 'dmx', DMX protocol;
  • 'CO2' for connecting Larnitech CO2 sensors;
  • 'salda' for connecting Salda ventilation.

Example:

1hw="cfg='9600/8N1' modbus"
echo on; off 98 'off' For settings check out and testing echo parameter can be used. Module

echo-reply can be turned on or off with the help of this parameter.Echo parameter value:

  • 'off'
  • 'on'

Example:

1hw="cfg='9600/8N1' echo='off'"
 1		<item addr="349:1" auto-period="600" cfgid="197" name="Lamp 1" type="lamp"/>
 2		<item addr="349:2" auto-period="600" cfgid="197" name="Lamp 2" type="lamp"/>
 3		<item addr="349:3" auto-period="600" cfgid="197" name="Lamp 3" type="lamp"/>
 4		<item addr="349:4" auto-period="600" cfgid="197" name="Lamp 4" type="lamp"/>
 5		<item addr="349:5" auto-period="600" cfgid="197" name="Lamp 5" type="lamp"/>
 6		<item addr="349:6" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
 7			<automation name="Eco" temperature-level="16"/>
 8			<automation name="Comfort" temperature-level="22"/>
 9			<automation name="Hot" temperature-level="25"/>
10		</item>
11		<item addr="349:7" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
12			<automation name="Eco" temperature-level="16"/>
13			<automation name="Comfort" temperature-level="22"/>
14			<automation name="Hot" temperature-level="25"/>
15		</item>
16		<item addr="349:8" cfgid="197" name="Radiator" temperature-lag="0.2" type="valve-heating">
17			<automation name="Eco" temperature-level="16"/>
18			<automation name="Comfort" temperature-level="22"/>
19			<automation name="Hot" temperature-level="25"/>
20		</item>
21		<item addr="349:9" cfgid="197" name="Jalousie" sub-type="120" type="jalousie"/>
22		<item addr="349:11" auto-period="600" cfgid="197" name="Dimmer 1" type="dimmer-lamp"/>
23		<item addr="349:12" auto-period="600" cfgid="197" name="Dimmer 2" type="dimmer-lamp"/>
24		<item addr="349:13" auto-period="600" cfgid="197" name="Dimmer 3" type="dimmer-lamp"/>
25		<item addr="349:14" auto-period="600" cfgid="197" name="Dimmer 4" type="dimmer-lamp"/>
26		<item addr="349:16" cfgid="197" name="Door 1" type="door-sensor"/>
27		<item addr="349:17" cfgid="197" name="Door 2" type="door-sensor"/>
28		<item addr="349:18" cfgid="197" name="Door 3" type="door-sensor"/>
29		<item addr="349:19" cfgid="197" name="Door 4" type="door-sensor"/>
30		<item addr="349:20" cfgid="197" name="Door 5" type="door-sensor"/>
31		<item addr="349:21" cfgid="197" name="Door 6" type="door-sensor"/>
32		<item addr="349:22" cfgid="197" name="Door 7" type="door-sensor"/>
33		<item addr="349:23" cfgid="197" name="Door 8" type="door-sensor"/>
34		<item addr="349:24" cfgid="197" name="Door 9" type="door-sensor"/>
35		<item addr="349:25" cfgid="197" name="Door 10" type="door-sensor"/>
36		<item addr="349:26" cfgid="197" name="Door 11" type="door-sensor"/>
37		<item addr="349:27" cfgid="197" name="Door 12" type="door-sensor"/>
38		<item addr="349:28" cfgid="197" name="Door 13" type="door-sensor"/>
39		<item addr="349:29" cfgid="197" name="Door 14" type="door-sensor"/>
40		<item addr="349:30" cfgid="197" name="Door 15" type="door-sensor"/>
41		<item addr="349:31" cfgid="197" name="Door 16" type="door-sensor"/>
42		<item addr="349:32" cfgid="197" name="Door 17" type="door-sensor"/>
43		<item addr="349:33" cfgid="197" name="Door 18" type="door-sensor"/>
44		<item addr="349:34" cfgid="197" name="Door 19" type="door-sensor"/>
45		<item addr="349:35" cfgid="197" name="Door 20" type="door-sensor"/>
46		<item addr="349:36" cfgid="197" name="Door 21" type="door-sensor"/>
47		<item addr="349:37" cfgid="197" name="Door 22" type="door-sensor"/>
48		<item addr="349:38" cfgid="197" name="Door 23" type="door-sensor"/>
49		<item addr="349:39" cfgid="197" name="Door 24" type="door-sensor"/>
50		<item addr="349:40" cfgid="197" name="Door 24" type="door-sensor"/>
51		<item addr="349:41" cfgid="197" name="Door 25" type="door-sensor"/>
52		<item addr="349:43" cfgid="197" name="IR receiver" type="ir-receiver"/>
53		<item addr="349:44" cfgid="197" name="RS485" type="com-port"/>
54		<item addr="349:90" cfgid="197" name="Current" system="yes" type="current-sensor"/>
55		<item addr="349:95" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
56		<item addr="349:96" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
57		<item addr="349:97" cfgid="197" name="Temperature" system="yes" type="temperature-sensor"/>
58		<item addr="349:98" cfgid="197" hw="out='LLLLLHHHB-' dm='LLLL' io='KKKKKKKKKKKKKKKKKKKKUKKKKKK-'" logic-ver="19" name="Temperature" sn="2533726919" system="yes" type="temperature-sensor"/>
59		<item addr="349:100" cfgid="197" name="RS232" type="com-port"/>